REPAIR / REPLACEMENT OF LT PANEL INCLUDING ALLIED WORKS OF WATER SUPPLY INSTALLATION AT AGRA
2026_MES_784757_1
8012/1203/E8
Open Tender
Civil Works
Item Rate
180 days
GE (W) Agra
Please refer tender document
9 documents required · 9 mandatory
₹500
GE (W) Agra
₹60,000
17 Aug 2026
17 Aug 2026
14 Sept 2026
17 Aug 2026
7 Sept 2026
1 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installing, testing & commissioning of LT starter panel of cubical indoor type 3 phase 4 wire bus bar chamber & aluminum bus bar of rating 1000 amps for phases and neutral with sleeves including panel wiring with totally enclosed,(CPRI approved) 1100 volts, AC supply, factory made fully compartmentalized made out of 2 mm thick CRCA steel sheet for load bearing and 2 mm thick for non-load bearing of size not less than 1800x1475x400mm and portions vermin proof, protection of enclosure IP:54 class protection complete with powder coating paint including suitable angle iron size 75x75x5mm for mounting stand with suitable configuration multi-function digital meter with CT & selector switches for measuring current, voltage, PF & indicating lamps for each phase including taking down old U/S LT panel with accessories complete all as specified and directed, comprising with the following MCCB/ ACB’s duly mounted and inter connected. (Note: -All Type Test Certificates and Design verification with switch gears (ACB & MCCB) as per confirming to IS:61439/2011 Part-1 and part -2, short circuit test 4000 AMP 65 KA. from CPRI shall be submitted by the contractor before executing the job.)
INCOMER: -
(a) MCCB 630 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 50 KA - 1No
OUTGOING: -
(a) MCCB 350 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 36 KA - 3 Nos
(b) MCCB 63 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 30 KA - 1 Nos
(c) MCB 40A SPN 10kA – 03 Nos
(d) Fully Automatic Star Delta Starter 150HP – 03Nos (each starter contains)
(i) Contactor 300A 3 pole - 02Nos
(ii) Contactor 250A 3 pole - 01No
(iii) MPR protection relay (protection against Thermal, Overload, Earth Fault, single Phasing, Current unbalance, Phase sequence reversal, Locked Rotor, Under Current, LED's for trip indication for each fail safe) – 01No
(iv) Add on Block 2NO-2NC – 03Nos
(v) Star Delta Timer – 01No
(vi) MCB 10A SP 10kA – 01No
(vii) MCCB 250 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 25 KA -1No
Metering: -
(a) Digital Volt meter 0-500 volt with selector switch with MCBs - 01 No
(b) Digital Amp meter with selector switch of CT ratio 400/5 - 01 No
(c) Indication lamps R, Y, B LED type with 3 Nos of 2A MCBs - 1 set
(d) Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's. | 1 | EACH | - | - |
| 2 | Supply, installing, testing & commissioning of LT starter panel of cubical indoor type 3 phase 4 wire bus bar chamber & aluminum bus bar of rating 1600 amps for phases and neutral with sleeves including panel wiring with totally enclosed, 1100 volts, AC supply, factory made fully compartmentalized made out of 2 mm thick CRCA steel sheet for load bearing and 2 mm thick for non-load bearing of size not less than 1800x1475x400mm and portions vermin proof, protection of enclosure IP:54 class protection complete with powder coating paint including suitable angle iron size 75x75x5mm flat iron frame work/supports with suitable configuration multi-function digital meter with CT & selector switches for measuring current, voltage, PF & indicating lamps for each phase including taking down old U/S LT panel with accessories complete all as specified and directed, comprising with the following MCCB & ACB’s duly mounted and inter connected. (Note: -All Type Test Certificates and Design verification with switch gears (ACB & MCCB) as per confirming to IS:61439/2011 Part-1 and part -2, short circuit test 4000 AMP 65 KA. from CPRI shall be submitted by the contractor before executing the job.)
INCOMER: - (a) MCCB 630 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 50 KA - 1No
OUTGOING: - (a) MCCB 350 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 36 KA - 04 Nos
(b) MCCB 63 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 30 KA - 01 Nos
(c) MCB 40A SPN 10kA – 02 Nos
(d) Fully Automatic Star Delta Starter 120HP – 04Nos (each starter contains)
(i) Contactor 250A 3 pole - 02Nos
(ii) Contactor 200A 3 pole - 01No
(iii) MPR protection relay (protection against Thermal, Overload, Earth Fault, single Phasing, Current unbalance, Phase sequence reversal, Locked Rotor, Under Current, LED's for trip indication for each fail safe) – 01No
(iv) Add on Block 2NO-2NC – 03Nos
(v) Star Delta Timer – 01No
(vi) MCB 10 A SP 10kA – 01No
(vii) MCCB 250 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 25 KA -1No
Metering: -
(a) Digital Volt meter 0-500 volt with selector switch with MCBs - 01 No
(b) Digital Amp meter with selector switch of CT ratio 400/5 - 01 No
(c) Indication lamps R, Y, B LED type with 3 Nos of 2A MCBs - 1 set
(d) Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's. | 1 | EACH | - | - |
| 3 | Supply, installing, testing & commissioning of LT starter panel of cubical indoor type 3 phase 4 wire bus bar chamber & aluminum bus bar of rating 400 amps for phases and neutral with sleeves including panel wiring with totally enclosed, 1100 volts, AC supply, factory made fully compartmentalized made out of 2 mm thick CRCA steel sheet for load bearing and 2 mm thick for non-load bearing of size not less than 1000x1275x400mm and portions vermin proof, protection of enclosure IP:54 class protection complete with powder coating paint including suitable angle iron size 75x75x5mm /flat iron frame work/supports with suitable configuration multi-function digital meter with CT & selector switches for measuring current, voltage, PF & indicating lamps for each phase including taking down old U/S LT panel with accessories complete all as specified and directed, comprising with the following MCCB & ACB’s duly mounted and inter connected. (Note: -All Type Test Certificates and Design verification with switch gears (ACB & MCCB) as per confirming to IS:61439/2011 Part-1 and part -2, short circuit test 4000 AMP 65 KA. from CPRI shall be submitted by the contractor before executing the job.)
INCOMER: -
(a) MCCB 250 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 50 KA - 1No
OUTGOING: -
(a) MCCB 100 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 36 KA - 03 Nos
(b) MCCB 63 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 30 KA - 01 Nos
(c) MCB 40A SPN 10kA – 02 Nos
(d) Fully Automatic Star Delta Starter 20HP – 03Nos (each starter contains)
(i) Contactor 60A 3 pole - 02Nos
(ii) Contactor 40A 3 pole - 01No
(iii) MPR protection relay (protection against Thermal, Overload, Earth Fault, single Phasing, Current unbalance, Phase sequence reversal, Locked Rotor, Under Current, LED's for trip indication for each fail safe) – 01No
(iv) Add on Block 2NO-2NC – 03Nos
(v) Star Delta Timer – 01No
(vi) MCB 10 A SP 10kA – 01No
(vii) MCCB 160 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 36 KA - 01 Nos
Metering: -
(a) Digital Volt meter 0-500 volt with selector switch with MCBs - 01 No
(b) Digital Amp meter with selector switch of CT ratio 400/5 - 01 No
(c) Indication lamps R, Y, B LED type with 3 Nos of 2A MCBs - 1 set
(d) Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's. | 3 | EACH | - | - |
| 4 | Supply, installing, testing & commissioning of LT starter panel of cubical indoor type 3 phase 4 wire bus bar chamber & aluminum bus bar of rating 400 amps for phases and neutral with sleeves including panel wiring with totally enclosed, 1100 volts, AC supply, factory made fully compartmentalized made out of 2 mm thick CRCA steel sheet for load bearing and 2 mm thick for non-load bearing of size not less than 1000x1275x400mm and portions vermin proof, protection of enclosure IP:54 class protection complete with powder coating paint including suitable angle iron size 75x75x5mm /flat iron frame work/supports with suitable configuration multi-function digital meter with CT & selector switches for measuring current, voltage, PF & indicating lamps for each phase including taking down old U/S LT panel with accessories complete all as specified ans directed, comprising with the following MCCB & ACB’s duly mounted and inter connected. (Note: -All Type Test Certificates and Design verification with switch gears (ACB & MCCB) as per confirming to IS:61439/2011 Part-1 and part -2, short circuit test 4000 AMP 65 KA. from CPRI shall be submitted by the contractor before executing the job.)
INCOMER: - (a) MCCB 160 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 50 KA - 1No
OUTGOING: -(a) MCCB 63 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 36 KA - 03 Nos
(b) MCB 40A SPN 10kA – 02 Nos
(c) Fully Automatic Star Delta Starter 05 HP – 03Nos (each starter contains)
(i) Contactor 32A 3 pole - 02Nos
(ii) Contactor 25A 3 pole - 01No
(iii) MPR protection relay (protection against Thermal, Overload, Earth Fault, single Phasing, Current unbalance, Phase sequence reversal, Locked Rotor, Under Current, LED's for trip indication for each fail safe) – 01No
(iv) Add on Block 2NO-2NC – 03Nos
(v) Star Delta Timer – 01No
(vi) MCB 10 A SP 10kA – 01No
(vii) MCCB 160 AMPS 4 pole suitable for 3 phase AC Supply,50 HZ, 36 KA - 01 Nos
Metering: -
(a) Digital Volt meter 0-500 volt with selector switch with MCBs - 01 No
(b) Digital Amp meter with selector switch of CT ratio 400/5 - 01 No
(c) Indication lamps R, Y, B LED type with 3 Nos of 2A MCBs - 1 set
(d) Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's. | 1 | EACH | - | - |
| 5 | M&L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6mm size, buried directly in ground (earth pit not less than 3.25M deep below normal ground level) with top edge of the plate not less than 1.5M below normal ground level connected to and including galvanized steel earth strip 32 x 6mm, including 40mm bore GI light grade protection pipe as earth lead strip connected to the earth plate by means of GI bolts, nuts, washers and earth plate surrounded by 150mm thick alternate layers of charcoal or cock dust & common salt 20mm bore medium grade GI watering pipe PCC pit in PCC 1:3:6 type C-1 (using 20mm graded stone aggregate) cover 50mm thick of precast RCC 1:2:4 type B-1 (using 20mm graded stone aggregate) duly reinforced with 8mm deformed or twisted bars @ 100mm c/c both ways, GI wire mesh, GI sheet funnel necessary excavation in soft/loose soil and deposited the surplus soil to a distance n.exc 50mtr away from starting point complete all as specified and shown in electrical plate No 3 of MES standard schedule of rates 2009 Part-I all as specified and directed. | 12 | Each | - | - |
| 6 | S&F in replacement for XLPE unarmoured, LT 1100V grade (heavy duty) copper conductor cable 3 core 95 sqmm confirming to IS7098(Part-I) 1988, laid in existing RCC covered duct/Sub way/along wall/MS bracket. Note : The Cables shall be fixed to LT panel with suitable size brass/stain less steel cable glands, copper lugs and rate deemed to be included in rate quoted for respective item | 60 | RM | - | - |
| 7 | Supply, laying & testing cable XLPE insulated, armoured heavy duty electric cable with stranded aluminium conductor, 1100 volts grade cross sectional area 50 Sqmm. 3.5 core Confirming to relevant IS including taking dwon old u/s cable, cable cover etc complete all as specified and directed by Engineer-in-charge. Note : The Cables shall be fixed to LT panel with suitable size brass/stain less steel cable glands, lugs and rate deemed to be included in rate quoted for respective item | 600 | RM | - | - |
| 8 | Supply, laying & testing cable XLPE insulated, armoured heavy duty electric cable with stranded aluminium conductor, 1100 volts grade cross sectional area 185 Sqmm. 3.5 core Confirming to relevant IS including taking dwon old u/s cable, cable cover etc complete all as specified and directed by Engineer-in-charge. Note : The Cables shall be fixed to LT panel with suitable size brass/stain less steel cable glands, lugs and rate deemed to be included in rate quoted for respective item. | 255 | RM | - | - |
| 9 | Supply and fixing in replacment of Manual Changeover switch 630 Amps ,4 Pole, 415 Volt ,I-O-II operation supplied with bridging bars,extended shaft and IP65 pistol type handle with SS Enclosure and make electric connection complete all as specified and as directed. | 3 | Each | - | - |
| 10 | Supply and fixing in replacment of Manual Changeover switch 200 Amps ,4 Pole, 415 Volt ,I-O-II operation supplied with bridging bars,extended shaft and IP65 pistol type handle with SS Enclosure and make electric connection complete all as specified and as directed. | 3 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.15 MB
Tender.pdf
Tender Documents • 0.52 MB
BOQ_879344.xls
BOQ • 1.54 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].