| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.5 LAccepted-AOC 1ST FLOOR GURJEET MARKET DHANGU ROAD | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹24.5 L+₹86,598 (3.66%)Rejected-AOC MASTER BUILDING DALHOUSIE ROAD DALHOUSIE ROAD PATHANKOT PATHANKOT GURDASPUR PUNJAB 145001 | PATHANKOT | PUNJAB | 145001 | L2 | Rejected-AOC MORE THAN LOWEST | |
| 3 | L3₹29.2 L+₹5.5 L (23.3%)Rejected-AOC | L3 | Rejected-AOC MORE THAN LOWEST |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
17 Oct 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (NORTH) MAMUN
GE (NORTH) MAMUN C/O 56APO
REPAIR/ MAINTENANCE OF HT/LT DISTRIBUTION NETWORK SYSTEM UNDER AGE E/M-I OF GE (N) MAMUN.
2020_MES_378453_1
GE(N)/M- /2020-21
Open Tender
Civil Works
Item Rate
180 days
GE (N) Mamun
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE(NORTH) MAMUN
₹50,000
Yes
11 Jan 2021
17 Sept 2020
20 Oct 2020
17 Sept 2020
17 Oct 2020
3 Oct 2020
60 days
Amount
Excavating in trenches in Soft of soil, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out complete all as specified and directed.
Excavation in trenches in soft soil n. exc. 1.5 Mtr in width and exc. 1.5 Mtr but not exc. 3.00 Mtr In depth and getting out all as required for laying of cable/ poles all as specified and directed.
Removing excavated material to a distance not exceeding 50 Mtr and deposting where directed at a level not exc. 1.5 mtr above the starting point all as specified and directed.
Returing filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm each all as required and directed.
M&L for Sub Class 'B' bricks old size, laid dry flat over the cable abutting each other, length of cable equal to width of brick all as required as in protection of cable all as specified and directed.
Material and labour for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm thick after laying, stretching and testing the cable all as specified and directed.
Material and Labour for pre cast cement concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregrate for foundation filling as mass concrete including necessary form work complete all as specified.
Material and Labour for pre cast cement concrete 1:3:6 type C-1 using 20 mm graded crushed stone aggregrate for foundation/ coping of poles/stay and transformer complete all as specified & directed.
Taking out from trenches or wall/ pole or pipe cable LT 1100 volts grade heavy duty , armoured with steel strip of wire , with stranded aluminium conductor any core for rectification of faults or replacement. Seggregating serviceable cable and unserviceable lenght by meggering or any other suitable and recommended method. Removing unserviceable cable from site and keeping aside serviceable for reuse at same location or any other location under AGE E/M-I all as rquired at site or directed for cable size 50Sqmm to 70 Sqmm. (Earth work will be measured and paid separately under respective item).
All as per Ser item No 09 but for cable size 90 Sqmm to 120 Sqmm.
All as per Ser item No 09 but for cable size 185 Sqmm to 240 Sqmm.
Supply & laying in trenches or fixed to wall/pole or passing through pipe cable LT 1100 volts grade heavy duty,XLPE insulated , armoured heavy duty electric cable , with aluminium conductor of size 50 Sqmm x 3.5 core all as specified and directed.
All as per Ser item No 12 but for cable size 70 Sqmm x 3.5 core.
All as per Ser item No 12 but for cable size 95 Sqmm X 3.5 core.
All as per Ser item No 12 but for cable size 120 Sqmm X 3.5 core.
All as per Ser item No 12 but for cable size 185 Sqmm X 3.5 core.
All as per Ser item No 12 but for cable size 240 Sqmm X 3.5 core.
Taking out from trenches or wall/ pole/ pipe or road crossing, HT cable 11000 volts grade heavy duty , armoured with steel strip of wire , with stranded aluminium conductor of any size upto 95 Sqmm, any core , for rectification of faults or replacement. Seggregating serviceable cable and unserviceable lenght by meggering or any other suitable and recommended method. Removing unserviceable from site and keeping aside serviceable for reuse at same location or any other location complete all as rquired at site or directed. (Earth work will be measured and paid separately under respective item).
All as per Ser item No 18 but for cable size 185 Sqmm to 240 Sqmm.
Supply only, testing and commissioning of HT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty ) with alumn conductor, 11KV grade, suitable for earthed system, with aluminium conductor of size 95 Sqmm 3 core.
All as per Ser item No 20 but for cable size 185 Sqmm.
All as per Ser item No 20 but for cable size 240 Sqmm.
Material and labour for detection of any type of fault in HT underground Line (laid in soil at plane area or forest area) with the help of Cable fault locator machine. Cable fault locator including conveyance shall be provided by the Contractor. Span of faulty cable will be trace out by the agencies by meggering HT cable. Note : 1. Detection of fault in one span of length will be measured as Each Job. 2. Technicians will be employed by the working agencies. 3. Material for repair and replacement will be measured saperately.
Material and labour for dismantling and taking down old UNSV Steel tubular any size and removal from site complete all as specified and directed.
Material and labour for dismantling and taking down old UNSV concrete pole any size and removal from site complete all as specified and directed.
Material and labour for erection of steel tubular swaged pole 11 mtr long with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP 55, including painting with anti corrosive paint internally complete and externally up to planting depth, alternative green & white strips of 30 cm height upto 1.5 mtr above ground level all as required at site or directed .
Material and labour for prestresed cement concrete pole 11 mtr long, 152 mm x 152 mm at top and 152 mm x 260 mm at bottom class-9 complete, erected truly in vertical position and painting the poles with synthetic enamel paint upto 1.5 mtr from the coping above the ground level with alternate layer of 30 cm width with black and yellow paint complete all as specified and directed .
Erection of good quality safe & secure pole retrived from Item No 24 & 25 the steel tubular pole or prestresed cement concrete pole 11 mtr long, erected truly in vertical position and painting the poles with synthetic enamel paint upto 1.5 mtr from the coping above the ground level with alternate layer of 30 cm width with black and yellow paint, complete all as specified and directed . Note : Other material of works measured and paid separately (Excavation, concrete for foundation, pole coping and cross arm with nuts& bolts etc.)
Taking down carefully aluminium conductor of any size from OH Lines (running on 9/11 poles) after unbinding from insulators for replacement of multijointed / undersize conductors all as specified and directed .
Restringing and restretching the aluminium conductor reterived from taking down item including necessary binding with insulators using alunimium binding wire, connections of incoming and out going cables complete all as specified and directed.
M&L for ACSR conductor of any size drawn straight horizontal on over head lines on poles including binding with insulators using aluminium binding wire, jointing jumpers etc including connections of incoming and out going cables complete all as specified and directed.
Restretching aluminium conductor or GI wire on existing over head lines (running on 9/11 Mtrs pole) without removing including unbinding from insulator and rebinding to insulator using aluminium binding wire , connections of incoming and out going cables, binding with spacers where required, complete all as specified. (Note :- For measurement length of each conductor shall be taken seperately.)
Trimming up of tree branches upto 3 mtr all around HT overhead lines, removing cut branches from site as directed, Note :- (i) The overhead lines will be kept clear from all trees by trimming of tree branches with 3 mtr all around the line. Necessary permission will be obtained from department by contractor one day prior to trimming in particular area and shut down of that area will be arranged by department. (ii) Total length of line cleared will be measured for the purpose of payment, irrespective of the No of trees required to be trimed.
Material and labour for dismantling cross-arms of M.S. channel or angle sections etc. from poles complete all as specified and directed .
Material and labour for cross arms, bracings, supports, clamps and back plates fabricated from steel section including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape ors size as indicated or directed and inclusive of oneprimer coat, one under coat and one finishing coat of alumn paint all as specified and directed .
Dismantling insulators of any type, any size all as directed.
Fixing of shackle type insulators of 100mm high, 115mm dia porcelain, vitreous, white, brown or green insulators for working pressure 11000 volts complete all as specified, required at site all as specified and directed .
Fixing only Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade all as specified and directed .
M&L for shackle type insulators of 100 mm high, 115 mm dia porcelain, vitreous, white, brown or green insulators for working pressure 11000 volts complete all as specified, required at site or directed.
M&L for polimeric Pin type,insulator including and connected acessaries for fittng 11000 volts all as directed.
M&L for polimeric Disc type insulator,45 KN with fitting T&C / B&S type assembly for tension with tension clamps for conductors, working pressure 11000 volts all as directed.
Material and labour for cable termination out door, heat shrinkable type suitable for XLPE cable of size 95 Sqmm to 120 sqmm 3 core with working voltage 11000 volts complete all as specified and direced
All as per Ser item No 42 but for size 150 Sqmm to 185 sqmm 3 core.
All as per Ser item No 42 but for size 240 Sqmm to 400 Sqmm 3 core.
Material and labour for cable termination indoor, heat shrinkable type suitable for XLPE cable of size 95 Sqmm to 120 sqmm 3 core with working voltage 11000 volts complete all as specified and direced .
All as per Ser item No 45 but for size 150 Sqmm to 185 sqmm 3 core.
All as per Ser item No 45 but for size 240 Sqmm to 400 Sqmm 3 core.
Material and labour for Cable joining kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120 Sqmm 3 Core with working voltage 11000 volts complete all as specified and direced .
All as per Ser item No 48 but for size 150 sqmm to 185 sqmm 3 core.
All as per Ser item No 48 but for size 240 sqmm 3 core.
M&L in replacement for cable termination out door, heat shrinkable type suitable for XLPE/PVC cable of size 16 Sqmm 3½ or 4core with working voltage 1100 volts all as specified and direced .
All as per Ser item No 51 but for size 25 Sqmm to 50 sqmm 3½ core.
All as per Ser item No 51 but for size 70 Sqmm to 150 sqmm 3½ core.
All as per Ser item No 51 but for size 185 Sqmm to 300 sqmm 3½ core.
M&L in replacement for Straight through cable jointing kit , heat shrinkable type suitable for XLPE/ PVC cables of size 16 Sqmm 3½ or 4core with working voltage 1100 volts all as specified and direced .
All as per Ser item No 55 but for size 25 Sqmm to 50 sqmm 3½ core.
All as per Ser item No 55 but for size 70 Sqmm to 150 sqmm 3½ core.
All as per Ser item No 55 but for size 185 Sqmm to 300 sqmm 3½ core.
Material and labour for dismantling and taking old/UNSV stay assembly all as specified and direced . .
M&L for stay assy complete with MS stay plate of size 300x300x6mm thick, stay rod 20 mm dia, stay bow, nuts, bolts and check nuts of GI all as shown in EP No 01 of SSR Part-I of 1991 or directed ( Excavation, PCC, saty wire and loop type insulators will be measured separately).
M&L for galvanized stay strand of size 7/4 mm
Material and labour for GI tubing light grade 100 mm bore with fittings laid for protection of cable under road crossing fixed to walls or pole complete all as specified and as directed.(clamps for fixing pipe, nuts, bolts washers shall be measured separately )
Material and labour for GI tubing light grade 80 mm bore with fittings laid for protection of cable under road crossing fixed to walls or pole complete all as specified and as directed.(clamps for fixing pipe, nuts, bolts washers shall be measured separately )
Supply, installation, commissioning and testing 11 KV Air break switch, gang operated for current rating upto 200Amps, triple pole, horizontal type, mechanically operated with accessories such as polymer insulator assembly (Set of 12 insulators), jumper conductor ACSR with operating mechanism worked from ground level, GI tubing 20mm bore (heavy grade), drop out fuse and steel frame including application of two coats of aluminium paint over a coat of primer complete all as specified and directed.
Dismantling of spares of GOD such as Male , Female , copper belt , belt carrier and back connector plate and pedastel (Insulator) etc all as specified and direced .
Supply and fixing of Male Contact / moving contact blade with arcing horn having brass contacts suitable for 11 KV GOD, including galvanised iron bolts, nuts and washers for fixing on post insulator or any other indicated situation all as required at site or directed .
Supply and fixing of Female contact spring loaded having brass contacts suitable for 11 KV GOD, including galvanised iron bolts, nuts and washers for fixing on post insulator or any other indicated situation all as required at site or directed .
Supply and fixing of tinned Copper braided flexible belt or jumper 200 Amp/400 Amp, suitable for 11 KV GOD, including galvanised iron bolts, nuts and washers for fixing all as required at site or directed .
Supply and fixing of MS Jumper Carrier for carrying copper braided belt , suitable for 11 KV GOD, including galvanised iron bolts, nuts and washers for fixing all as required at site or directed .
Supply and fixing of Back connector plate, suitable for 11 KV GOD, including galvanised iron bolts, nuts and washers for fixing all as required at site or directed .
M&L for polimeric insulator (Pedastal) for GOD switch gear connection including and connected accessories for fittng 11000 volts all as directed.
Material and labour for dehydration and filtration of transformer oil at site by dehydration and filtration plant including testing of trasnformer oil sample before and after dehydration and filtration complete all as specified and directed. (The dielectric strength to be achieved 40 KV at 2.5 mm gap after completion of dehydration and filtration). Note:- (i) dehydration of transformer oil in the Transformer carried out on the site by dehydration machine. (ii) All the Labour work like disconnect of cable and reassemble and drum etc, carried out by contractor by own arrangement. (iii) Prepare chart of each transformer before and after Dielectric strength , make of transformer oil as approved. (iv) Sample of treatead oil 500ml stored in bottle and given to Gvt rep.
Supply and filling up of transformer oil at various locations with new transformer oil in sealed drum complete all as specified and as directed.
Painting of Transformer of Cap upto 100 KVA after removing dust particular,Oily portion from transformer with spary pump and writing SM/MES No. and Capacity,Make etc on It as per directed .
All as per Ser item No 74 but for transformer size above 100 KVA upto 200 KVA.
All as per Ser item No 74 but for transformer size above 200 KVA upto 315 KVA.
All as per Ser item No 74 but for transformer size above 315 KVA upto 500 KVA.
All as per Ser item No 74 but for transformer size above 500 KVA upto 750 KVA.
Supply and filling up in replacement silica gel superior quality to transformer breather assy complete all as required and diercted.
Repair / servicing to HT vacuum circuit breaker 11 KV rating of capacity 250 MVA and current rating upto 630 Amps by replacing defective/wornout part incl bus bar insulating sleeves, adjustment of gaps for smooth operation all as detailed below :- (a) Cleaning of VCB with air blower and removing dust particals. (b) Cleaning of VCB by using CTC/CRC/Thinner as required and recommended by the manufacturer. (c) Checking the arcing contact gap of vacuum interrupter if gap exceeds the permissible limits, adjust as required. (d) Cleaning the main contacts to remove carbon or any other unwanted particals if visible. (e) Dismantling and cleaning the insulated surfaces and arc barrier with CTC and CRC. (f) Checking/repair replacement of all electrical wiring for electrical/manual operation of panel including measuring IR values. (g) Checking of all nuts/bolts, springs, levers, latches, connnectors etc and adjustments as required and recommended by the manufacturer. (h) Inspection of CTs and PTs. (j) Cleaning of bus bar spout. (k) Checking of all moving parts for proper functioning of VCB and adjustment as per manufacturer recommendations.
M&L for earthing complete with galvanised steel earth plate electrode, 600mm x 600mm x 6mm thick, buried directly in the ground (earth pit not less than 2.25m deep below normal (ground level) with top edge of the plate not less than 1.50m below ground level connected to galvanized iron wire 4mm dia as earth lead by means of bolts, nuts and washers of GI up to test point, GI light grade pipe 15mm bore as protection pipe, GI watering pipe 20mm bore light grade with funnel and wire mesh, charcoal and salt, 40mm thick pre-cast RCC (1:2:4) type B-1 (Nominal mix) cover reinforced with XPM (weighing n.less than 4 Kg/Sqm) with suitable steel handle, and angle iron 40X40X3mm frame and chamber of PCC (1:3:6) type C-1 (including earth work in any type of soil, removal of surplus soil to a distance n.exc.50m) and connecting, testing on completion, all as shown on electric plate No. 03 of SSR-2009 Part-I, complete all as directed.
M&L for earthing complete with galvanised steel earth plate electrode, 600mm x 600mm x 6mm thick, buried directly in the ground (earth pit not less than 2.25m deep below normal (ground level) with top edge of the plate not less than 1.50m below ground level connected to galvanized iron strip of 32x6mm as earth lead by means of bolts, nuts and washers of GI up to test point, GI light grade pipe 40mm bore as protection pipe, GI watering pipe 20mm bore light grade with funnel and wire mesh, charcoal and salt, 40mm thick pre-cast RCC (1:2:4) type B-1 (Nominal mix) cover reinforced with XPM (weighing n.less than 4 Kg/Sqm) with suitable steel handle, and angle iron 40X40X3mm frame and chamber of PCC (1:3:6) type C-1 (including earth work in any type of soil, removal of surplus soil to a distance n.exc.50m) and connecting, testing on completion, all as shown on electric plate No. 03 of SSR-2009 Part-I, complete all as directed.
Supply and fix lightning arrestor HT 11 KV 10 KA and connection with HT cable single core suitable size cable jumper complete all as specified and directed .
Disconnecting all the electrical connections from H.T. and L.T. side of unserviceable transformer of cap upto 100 KVA i.e. Jumpers/cable from the cable end box or bushings & earthing terminal of the transformers including taking down, loading, unloading of transformer & transportation by vehicle from substation to the repairing workshop including reinstallation, commissioning and testing complete all as specified and directed .
All as per srl item No 84 above but cap of transformer above 100KVA upto 315 KVA complete all as specified and directed .
All as per srl item No 84 above but cap of transformer above 315KVA upto 500 KVA complete all as specified and directed.
All as per srl item No 84 above but cap of transformer above 500 KVA upto 750 KVA complete all as specified and directed .
Opening the transformer cover along with the conservator by removing the nuts bolts then after removing the internal H.T. & L.T. connections by taking them out by removing studs, bushings, taking out the core-winding assembly out of the tank, removing out burnt HV and LV windings from the core assembly, cleaning of core assembly with CTC including necessary repairs for the unserviceable transformers having ratio 11 / 0.433 KV, draining & decanting of burnt transformer oil and cleaning of sludge deposited in the tank with CTC for the transformers. Rewinding of HV and LV coils with suitable size super enamelled copper wire/ strip (As Existing) having suitable class insulation material. Heating of core winding assembly in hot chamber for 48 hours and removing all the moisture present in it, removal of leakage of tank if any by welding, refilling transformer oil to tank, after putting the core-winding assembly into the tank, reassembling making the internal H.T. & L.T. connections by fixing the studs, bushing, fitting the top cover by replacing cork sheet gasket along with conservator, testing the transformer in the workshop duly filled with oil, all as directed by Engineer-in-Charge for various capacities as under:-
Upto 100KVA
Above 100KVA upto 200KVA
Above 200KVA upto 315KVA
Above 315KVA upto 500KVA
Above 500 KVA upto 750 KVA
Note : Unserviceable items required for repairs shall be measured and paid separately under relevant item of this schedule. Transformer oil with die electric strength not less than 40 KV either new or filtered shall be filled and shall be measured and paid seperately under respective item.
Opening the transformer cover along with the conservator by removing the nuts bolts then after removing the internal H.T. & L.T. connections by taking them out by removing studs, bushings, taking out the core-winding assembly out of the tank of transformers having ratio 11/0.433 KV, draining & decanting of transformer oil and cleaning of sludge deposited in the tank with CTC for the transformers. Heating of core winding assembly in hot chamber for 48 hours and removing all the moisture present in it, removal of leakage of tank if any by welding, refilling transformer oil to tank, after putting the core-winding assembly into the tank, reassembling, making the internal H.T. & L.T. connections by fixing the studs, bushing, fitting the top cover by replacing cork sheet gasket along with conservator, testing the transformer in the workshop duly filled with oil, all as directed for various capacities as under:-
Upto 100 KVA
Above 100 KVA upto 200 KVA
Above 200 KVA upto 315 KVA
Above 315 KVA upto 500 KVA
Above 500 KVA upto 750 KVA
Supply replacement of super enamelled copper winding wire/ strip of any size for H.T. coils of transformers all as specified.
Supply replacement super enamelled aluminium winding wire/ strip of any size for H.T. coils of transformers all as specified.
Supply replacment copper winding strip of any size for L.T. coils of transformers including providing insulation all as required all as specified and directed ..
Supply replacement of aluminium winding strip of any size for L.T. coils of transformers including providing insulation all as required all as specified and directed .
Reconditioning of LT coil of aluminium / copper wound transformer by turning the old paper insulations, straightening the entire LT Strip providing new paper insulations of superior quality and making coil of suitable design as original all as specified and directed .
Supply & fixing LT bushings 433V of suitable size for outdoor/ indoor type transformer of the capacity as under:-
Upto 100KVA
Above 100KVA upto 200KVA
Above 200KVA upto 315KVA
Above 315KVA upto 500KVA
Above 500 KVA upto 750 KVA
Supply & fixing HT bushings 11KV of suitable size for outdoor type transformer of capacities as under:-
Upto 100KVA
Above 100KVA upto 200KVA
Above 200KVA upto 315KVA
Above 315KVA upto 500KVA
Supply & fixing brass stud (for LT 433V side) of suitable size complete with one check nut, two nuts, washers and rubber seal, all as per sample for outdoor/indoor type transformer of the capacity as under:-
Upto 100KVA
Above 100KVA upto 200KVA
Above 200KVA upto 315KVA
Above 315KVA upto 500KVA
Above 500 KVA upto 750 KVA
Supply & fixing brass stud (for HT 11KV side) of suitable size complete with one check nut, two nuts, washers and rubber seal, all as per sample for outdoor/indoor type transformer of the capacity as under:-
Upto 100KVA
Above 100KVA upto 200KVA
Above 200KVA upto 315KVA
Above 315KVA upto 500KVA
Above 500 KVA upto 750 KVA
Supply & fixing in repair oil level indicator for transformer of cap upto 750KVA all as per existing and having level marking 1/4, 1/2, 3/4 and full all as directed .
Supply and fixing in repair breather assy for transformer of capacity upto 750KVA all as per existing all as directed.
Material and labour for spray painting using synthetic enamel paint of superior quality on prepared surfaces as priming with one coat of red oxide scraping of old rusted surfaces of LT/HT panel. Paint colour and quality as approved by GE/AGE E/M as per standard engineering practice with two coats all as specified and directed .
Material and labour for Mild steel plates chequered, not less than 5mm thick of grade Fe 410-W (Gde-E-250) quality-A suitable sizes for cable duct cover complete al as specified.
Supply and replacing Digital square type voltmeter for HT 11KV panel of size 96 sqmm complete all as directed.
Supply and replacing digital type ammeter square type for HT 11KV panel range as per existing and size 96 sqmm complete all as directed.
Supply and replacing indicator lamp assembly LED type of HT panels complete all as specified and directed.
M&L for testing/caliberation of protective relays, protective switch gears and all protective circuits of and 11 KV VCB panels through primary injections including testing and checking of breaker tripping/ setting on each panel complete all as directed. Note: Testing of relays shall be carried out though metering and testing sub division by SED or any other authorised agency approved by GE.
M&L for testing of protective relays of 11 KV VCB panel through secondary injections including cleaning of all protective relays their contacts and chambers with CCL 4 complete all as specified and directed.
Supply and fix lead acid battery 150AH equipped with positive plates/anodes and negative plates/cathodes , 12 Volts including copper leads of suitable size connecting with existing battery bank complete all as specified and directed.
S&F MCCB of 63Amps 3Pole, 16kA, 415 Volts with fixed thermal and fixed magnetic setting in exisitng LT panel incl connection with existing cable with suitable size of Aluminium Thimbles complete all as required at site or directed .
All as per item No 110 here in above but of size 100Amps 4Pole, 16kA.
All as per item No 110 here in above but of size 160Amps 4Pole, 25kA.
All as per item No 110 here in above but of size 200Amps 4Pole, 25kA.
All as per item No 110 here in above but of size 250Amps 4Pole, 36kA.
All as per item No 110 here in above but of size 320Amps 4Pole, 36kA.
All as per item No 110 here in above but of size 400Amps 4Pole, 36kA.
Taking out burnt unsv motor of vacuum circuit breaker for spring charging by unscrewing all nut bolts and cable connections carefully and transporting civil motor work shop, rewinding with suitable size super enamelled copper wire of exisitng gauge, refixing in its original position including testing complete all as specified and directed.
Supply and fix in replacement space heater for 11KV VCB panel as per existing specification and making proper electric connections and testing complete incl taking out old unsv space heater all as specified and directed.
INDIA ELECTRIC WORKS
KULBHUSHAN AGGARWAL
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .