Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.4 CrAccepted-AOC V P O SAROTARI TEHSIL BAROH DISTRICT KANGRA PIN 176037 HP | KANGRA | HIMACHAL PRADESH | 176037 | ₹1.4 Cr | L1 | Accepted-AOC BEING LOWEST |
| 2 | L2₹1.5 Cr+₹7.1 L (5.14%)Rejected-Finance | ₹1.5 Cr+₹7.1 L (5.14%) | L2 | Rejected-Finance Rejected being L2 |
| 3 | L3₹1.5 Cr+₹14.1 L (10.1%)Rejected-Finance BALLIA UTTAR PRADESH | BALLIA | UTTAR PRADESH | 221701 | ₹1.5 Cr+₹14.1 L (10.1%) | L3 | Rejected-Finance Rejected being L3 |
Tender Value
₹1.0 Cr
EMD Value
₹1.8 L
Closing Date
3 Mar 2020, 6:00 pmClosed
Chief Engineer
CHIEF ENGINEER (NW) KATARIBAGH, NAVAL BASE-PO KOCHI-682 004
PROVISION OF CENTRAL SEWAGE TREATMENT /SEWAGE TREATMENT PLANT AT AIR FORCE STATION LONAVLA
2020_MES_311629_1
890515_1
Open Tender
Civil Works
Lump-sum
365 days
LONAVLA
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
GE(I) Navy Lonavla
₹1.8 L
Yes
1 May 2020
3 Jan 2020
9 Mar 2020
4 Jan 2020
3 Mar 2020
20 Feb 2020
4 Jan 2020 - 15 Jan 2020
Amount
LIST OF WORKS
Total amount of Sch 'A' part-I (Buildings & Works)
Total amount of Sch 'A' part-II ( Excavation/Earthwork & Site Development)
Total amount of Sch 'A' part-III (Internal water Supply)
Total amount of Sch 'A' part-IV (External water Supply)
Total amount of Sch 'A' part-V (Sewage Disposal)
Sch 'A' Part- VI (MISCELLANEOUS) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Internal Electrification Point wiring complete with 1.5 sq mm FRLS single core PVC insulated cable 1100 V grade with multistranded copper conductor drawn through Concealed / Conduit with all accessories fixed to wall /roofs ceiling etc and incl provision of 1.5 sq mm PVC insulated and unsheathed copper conductor as earth continuity conductor and connected to common earth dolly incl MS Concealed boxes of suitable size for mounting the switches , socket outlets , fan regulators etc all as specified and directed for following. (a) One light/Fan point controlled by one switch.
(b) All as per item No. 8 above but for One socket 3 pin outlet 5 amp on independent board complete all as specified and directed
(c ) All as per item No. 8 above but for One 3 pin socket outlet 5 amp on the same board with other switches complete all as specified and directed
All as per item no 8 above but with copper conductor cable for one 3 pin socket outlet 15 amp independent board with cable 2.5 sq mm and unsheathed copper conductor 2.5 sqmm FRLS cable as earth continuity conductor and connected to common eareth dolly complete all as specified and directed
Switch piano flush type single pole one way 5 amp complete all as specified and directed
Ceiling rose three terminal/PVC polycarbonate, isolated body complete all as specified complete all as specified and directed
Switch socket combination 2 in 1, 3 pin 5/15 amp flush type complete all as specified and directed .
Switch socket combination 2 in 1,5 amp flush type complete all as specified and directed.
Socket outlet 2 in 1, 3/5 pin 5 amp multi purpose, flush type complete all as specified and directed.
MCB DB SPN 4 ways Double door with 240 Volt, 200 amps rated bus bar with all accessories fixed on the wall by using suitable size of wooden board fixed in the wall with suitable size of screws including taking down old unserviceable any type DBs all as specified and directed
MCB single pole and neutral 35-63 amps, 240 Volts, Complete all as specified and directed.
MCB 6 to 32 amps single pole 240 Volts,including taking down the existing one Complete all as specified and directed.
Indoor LED tubelight fitting with for LED Tube light ( 1 x 20 Watt LED ) surface / pendant mounting LED prewireed upto terminal block complete with all accessories and connecting up with twin core / .0076 flexible copper wire with and including LED tube light fixed on two nos PVC round / square mounting blocks complete all as required at site and as directed by Engineer -in-Charge. Cat No BCLAB 20W for Batten and BCLAB 20 Watt CW for tubelight of Bajaj or equivalent of mentioned in list of manufactures Note: Rate of two nos suspension links not exceeding 2.5 mtr long if required is deemed to be included in the quoted rate of the item
Exhaust fans AC single phase 230/ 240 V of size 300 mm sweep, heavy duty with louver complete all as specified and directed
Ceiling fan complete with electronic type regulator and accessories 230 V,1200 mm sweep. BEE 5 star rated complete all as specified and directed
Earthing complete with galvanized GI earth plate electrode of size 600x600x6.00 mm, buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to galvanized earth lead wire 4.0 mm dia by means of volts, nuts, check nut and galvanized iron or steel including earth work in any type of soil, charcoal salt 15 cm around the earth plate as shown in electrical plate No 3 of SSR part1991,20 mm dia watering pipe medium grade 1.50 mtr long GI protection pipe light grade 15 mm dia from earth pit to main board (NOTE:- maximum length of GI protection pipe with each earth shall not be less than 7.5 mtrs) including necessary pit with cover , including testing on completion complete all as specified and directed
External Electric supply XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with solid aluminium conductor of size 6 sq mm 2 core complete all as specified and directed. (For Street Light)
Unreinforced precast concrete cable cover factory made embossed the mark “LT CABLE” class LV type1 flat size 250x150x40 mm laid in trenches complete all as specified and directed
XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core complete all as specified and directed
BAJAJ make Hot dip galavanised iron pole 7 mtr long sheet thickness 3 mm. C/s A/F - top = 70mm, bottom =130 mm, base plate 200x200x12 mm, long weatherproof reinforced door opening with junction box mounting arrangement but including of junction box with 4 Nos aluminium Bus bar and including 1.0 M long single arm bracket having top 70 mm, 20 dia threaded made to J shape M20x600mm long steel grade EN8 foundation bolts - 4 nos with nuts, templates and all complete as per approved drawing Approved Equivalent Make mentioned in list of manufactures including taking down old rusted pole of any size by digging or cutting all as directed . Foundation RCC 1:1.5:3 shall be of size 550x550mm and depth 1500 mm with 8 nos. 12mm dia. tor bars as main bars and 8mm dia. tor bars stirrups @ 190 mm c/c as per approved drawing. This reinforcement shall conform to IS:1786 latest edition. The foundation shall extend above sorrounding ground/driveway level for 200 mm and have slant 63mm dia. PVC sleeve cast insitu foundation for cable entry as per the drawing. Including Excavation, PCC, RCC and reinforcement.
45 W pressure die cast aluminium housing LED street/security light, including connection with two core twisted copper flexible cable.Make - Bajaj, Cat No - BRTGF45W LED or equivalent make listed in list of manufactures
Sand cushioning in trenches for cable protection all as specified and directed ( Note : Thickness after punning down only will be measured and paid for )
Earthing complete with galvanized GI earth plate electrode of size 600x600x6.00 mm, buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to galvanized iron strip 25x4mm as earth lead by means of volts, nuts, check nut and galvanized iron or steel including earth work in any type of soil, charcoal salt 15 cm around the earth plate as shown in electrical plate No 3 of SSR part1991,20 mm dia watering pipe medium grade 1.50 mtr long GI protection pipe light grade 15 mm dia from earth pit to main board (NOTE:- maximum length of GI protection pipe with each earth shall not be less than 7.5 mtrs) including necessary pit with cover, including testing on completion
Internal Water Supply Health faucet/hand shower with 8mm dia, wall hook and easy flexible tube in crome finish 1.5m long with nuts of Make - Jaquar, Code No - ALD-573 and SHA571 or equivalent make listed in list of manufactures.
External Water Supply Cutting /breaking of cement concrete path or bituminous road of any thickness with or without reinforcement for taking up/down of GI/CI pipes and connection and making good to match existing surface by PCC (1:2:4) type B1 (Using 20 mm graded stone aggregates) complete all as specified as directed.
Construction of brick masonry valve chambers including PCC in foundation 1:4:8 (type C2) 10 cm thick rendering cement plaster internally 10mm thick and with cement mortar 1:6 PCC,1:2:4 (type B1) using 20 mm graded aggregate for coping 10 cm thick height, 3 mm thick MS plate cover with locking arrangement and angle iron frame of size 40x40x6mm including painting to plate cover with synthetic enameled black paint over one coat of red oxide primer including necessary excavation and earth work for internal dimension 900X900X900mm
Non clog vertical submersible pumps of 05 HP capacity 415 Volts, 50Hz, 3 Phase, A.C. Supply 1440 RPM, with Auto coupling, with 25 Mtrs PVC insulated flat submersible type copper flexible power cable of suitable core & size with sliuding bracket and foot bend (Flow Rate 125 lpm and Head 25 m) with chrome steel impeller and cutter, non-clog to pass 40 mm size particles including guide rail and lifting chain, cables etc complete all as specified and as directed.
LT Panel, Cubical, Multi Chamber, Outdoor Type, weather and vermin proof made out of 3 .15mm thick CRCA sheet with front opening and locking arrangement, epoxy powder coated having colour siemens grey, 150 Amps capacity aluminium bus bar for phase, 3 No's and 1 No 75 Amp bus bar for neutral, mounted on epoxy insulator including neccessary copper control wiring, heat shrinkable, RYB coloured sleeves over bus bar for identification, earth shields, circular holes at bottom / top to receive incoming and outgoing cable, cable lugs, cable gland of sizes as required floor mounting angle iron frame made out mild steel angle iron of size 40 x 40 x 6 mm grouted on PCC (1:3:6) upto required height suitable for the following control/ fitments sensible for 3 phase, 50 Hz, 415 V system complete with and including following :- INCOMING- (a) Thermal magnetic adjustable FP MCCB of capacity 63 A 25 kA - 2 No. OUT GOINGS- (a) Thermal magnetic adjustable FP MCCB of capacity 32 A 25 kA - 3 Nos. (b) Multidigital Meter :- 3 No's (c) Indicating lamp LED type :- 3 sets (d) Submersible Pump Starters for 5 HP Pump :- 02 No's
LT Panel, Cubical, Multi Chambered, Outdoor Type, weather and vermin proof made out of 3.15 mm thick CRCA sheet with front opening and locking arrangement, epoxy powder coated having colour siemens grey, 150 Amps capacity aluminium bus bar for phase, 3 No's and 1 No 75 Amp bus bar for neutral, mounted on epoxy insulator including neccessary copper control wiring, heat shrinkable, RYB coloured sleeves over bus bar for identification, earth shields, circular holes at bottom / top to receive incoming and outgoing cable, cable lugs, cable gland of sizes as required floor mounting angle iron frame made out mild steel angle iron of size 40 x 40 x 6 mm grouted on PCC (1:3:6) upto required height suitable for the following control/ fitments sensible for 3 phase, 50 Hz, 415 V system complete with and including following :- INCOMING (From Existing Panel;)- (a) (a) Thermal magnetic adjustable FP MCCB of capacity 100 A 25 kA - 1 No.. OUT GOING (For STP)- (a) Thermal magnetic adjustable FP MCCB of capacity 63 A 25 kA - 1 No.. (a) Thermal magnetic adjustable FP MCCB of capacity 32 A 25 kA - 2 No..
Excavation Earthwork & Site Development Testing drains as specified by fitting the pipes with water to a head of 1.5 m at the highest point including temporarilly fixing of bends, etc as required of exc 150mm but n.exc 300mm dia of pipe etc complete all as specified and directed
Testing manholes as specified by filling with water complete all as specified and directed
STP Design, Supply, construction, installation, testing & commissioning of package type Sewage Treatment Plant based on principle of aerobic attached growth non clogging randomly Moving Bed Bioreactor (MBBR) having capacity 50 KLD, including required foundations and the following as per the specifications given here in below and in particular specifications :- (a) One number Stilling chamber in MS FRP construction, for stabilised the pressure flow of sewage, as per drawing. (b) One number Fine Bar screen chamber in MS FRP for fine Bar screen of MSEP construction, to be installed at an angle of 60° to prevent floating objects passing through it and subsequently removing manually and dumped for further disposal, as per drawing . (c) One number Oil & Grease removal chamber in MS FRP, as per drawing . (d) One number Equalization tank in MS FRP construction, as per given specifications and drawing, to cater for the peak discharge including provision of diffused air to ensure that septic conditions do not occur in tank at all, through air grid suitable for dispersion of 15 m3/hr air to the entire bottom surface of the tank.
Item No.39 continued.. (e) Two nos. (one working and one standby) raw sewage Centrifugal monobloc self-priming pumps complete with motor and all necessary accessories and fittings, to be installed for transferring sewage from equalization tank to process. Separate valves should be provided and suction and discharge. Level sensor should be provided in the tank and interlinked with pumps for ON-OFF operation as per water level in the tank. One pressure gauge for each pump has to be provided to measure pressure at the outlet. (f) Two nos. (one working and one standby) Twin lobe Air blower complete with motor and all necessary accessories & fittings, for providing air in equalization tank & MBBR reactors. One no. Air rotameter is to be provided in each line to MBBR reactor 1 & 2/ EQT for measurement of quantity of air. (g) One Anoxic Chamber in MS FRP construction with Mixer. (h) Two Set of MBBR tank in MS FRP construction with all internals comprising of media, air grid & riser pipe, media retaining sieves, etc.
Item No.39 continued.. (j) Two nos. (one working and one standby) sewage centrifugal monobloc self-priming pumps complete with motor, with all necessary accessories and fittings for recirculating the treated sewage from outlet of MBBR 2 to anoxic tank to maintain anoxic conditions. Separate valves should be provided and suction and discharge. One pressure gauge for each pump has to be provided to measure pressure at the outlet. (k) One Set of Tube settler tank in MS FRP construction with all internals comprising of media, supporting structure & collection trough. (l) Two nos. (one working and one standby) sewage centrifugal monobloc self-priming sludge transfer pumps complete with motor and timer-based operation for set time after every set interval of time, with all necessary accessories and fittings for transferring sludge from bottom of the Tube settler to the sludge bag. Separate valves should be provided and suction and discharge. One pressure gauge for each pump has to be provided to measure pressure at the outlet. (m) One no. Chlorine Contact cum Filter feed tank in MS FRP construction.
Item No.39 continued.. (n) One set of chlorine dosing system comprising of solution tank and dosing pumps, with necessary connection for dosing of solution in chlorine contact tank. (o) Two nos. (one working and one standby) filter feed centrifugal monobloc pumps complete with motor and all necessary accessories and fittings for feeding tertiary unit, Level sensor should be provided in the chlorine contact cum filter feed tank and interlinked with pumps for ON-OFF operation as per level in the sump. Separate valves should be provided and suction and discharge. One pressure gauge for each pump has to be provided to measure pressure at the outlet. (p) One no. Dual Media filter complete with media, frontal piping, valve and pressure gauges to measure pressure across the filter. (q) One no. Activated Carbon Filter complete with media, frontal piping, valve and pressure gauges to measure pressure across the filter. (r) One no. Treated Water Tank in MSFRP construction, to collect treated water after tertiary. (s) One No. Sludge Bag system with DWPE Dosing for Sludge Dewatering .
Item No.39 continued.. (v) One lot of Power & control LT Cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminum conductor of size as shown on drawing. Note: The cost of Al thimbles/lugs and cable gland, cutting of hard surface, excavation, earth work, sand cushioning, brick protection and making good to disturbed surface etc. is included.
Notes for item No 39 to 44. :- 1. Quoted rate deemed to be inclusive of supply, installation, testing and commissioning of the complete package type STP of capacity 50 KLD including any item which is essential for satisfactory working of the STP but either not mentioned here-in-before or capacity, rating, Nos of items are not correctly mentioned here-in-before. 2. STP LT Control panel should have adequate control switches, FASD starter, Metering, Indication lamps for Motor ON / OFF / TRIP and control wiring for auto / mannual operation. 3. Before quoting the bid, Contractor or his authorised Engineer / consultant must visit the proposed site to study the site condition. 4. Execution of work at site shall commence only after approval of design details by accepting officer. 5. All Civil, Mechanical, Electrical works shall be carried out as per relevant BIS/IS/equivalent standard norms only and also in accordance with the latest edition of the Indian Electricity Act / rules formed there under and as amended from time to time. Any other works (civil mechanical & electrical) connected to installation, testing & functional requirement of package type STP capacity 50 KLD all as mentioned above and which is not mentioned or included in this schedule but necessary shall be carried out by the contractor against the rate quoted for item No 1 above. 6. Yard stick for payment shall be approved by Accepting Officer (based on BoQs and rates given by the contractor)
Notes for item No. 39 to 44 continued.. . 7. Design details of STP etc shall be in accordance with the policy issued by E-in-C’s Br MES New Delhi vide letter No. 86435/Misc/E4 (U3) dt 19 May 2017 .( 8.) Entire plant shall be tested after successful commissioning by rep of Accepting Officer and contractor shall make all arrangement without extra cost. 9. Contractor shall arrange adequate training to MES staff for operation of this STP without extra cost. 10. All consumable including chemicals required for testing & commissioning will be supplied by the contractor under item No 1 above and rate is deemed to be included in the rate quoted. 11. Rate is included for all Electrical work including installation of STP control Panel, electrical wiring from Control panel to all pump sets/Eqpts, Earting etc.12. Rate is included for all electro mechanical works including pumps and other items which are integral part of package type STP plant and essential for installation and successful operation of STP plant capacity 50 KLD as per BIS. 13. All Constructional Drawings and Technical Details shall be submitted before execution of works duly vetted by authorised Govt agencies.
Manning and Operation of STP
Provn of services for Maintenance & operation of sewage treatment plant through OEM installed under this contract of capacity 50 KLDincluding all supporting equipment such as pumps, motors, panels etc in 02 shift of 08 hours each ( 0600hrs to 1400 hrs & 1400 hrs to 2200 hrs ) including Sunday/holidays by deploying technically qualified person including supply of all consumable like chlorine, alum & limefor the first year from actual date of completion (ie; during defects liability period) as speficied and directed by Engineer -in-charge Following items shall also be demed to be included in the quoted rates for 12 months after completion of work. NOTE :(i) The contractor shall employ one operator per shift. The operator shall be qualified & experienced in field and experience not less than 2 yrs in the same field. (ii) Cost of periodical maintanance of various equipment/parts shall be deemed to be included in quoted rates of respective items. (iii) Samples of effluent shall be collected from the outlet twice in a month as directed and got tested in a lab approved by State Pollution Control Board. Cost of testing is deemed to be included in the rate quoted. (iv) The contractor shall strictly follow the operation and maintenance manual of the plant as well as dosage of chemical prescribed by testing agency.
Item No.48 (continued.. ) (iv) Periodical cleaning and removal of sludge from screen well, collection well, contact aeration tank, sludge aeration tank, settling tank, sludge drying beds, bar screen, screen through etc. (v) Mixing chemical to maintain desired quality of end product of system. (vi) To maintain all working place and area neat and clean. (vii) The Log sheet must be maintain by the contractor as directed by the Engr-in-charge. (viii) The maintenance of the plant during the defect liability period is deemed to be included in the quoted rate of STP vide item No 1 herein before. (ix) rate inclusive of all consumable for running the plant.
All as per item No. 48 here-in-before but for the second year under liability period complete all as specified and directed
Provn of services for comprehensive maintenance and operation of sewage treatment plant through OEM installed under this contract of capacity 50 KLD including all supporting equipment such as pumps, motors, panels etc in 02 shift of 08 hours each( 0600hrs to 1400 hrs & 1400 hrs to 2200 hrs) including Sunday/holidays) by deploying technically qualified person including supply of all consumable like chlorine, alum & lime for the third year after completion ( i.e two year after the defects liability period ) as speficied and directed by Engineer -in-charge.
All as per item No 51 here-in-before but for the fourth year complete all as specified and directed
Notes for item No 48 to 52 (i) The contractor shall employ one operator with one helper per shift, the operator shall be qualified & experienced in field and experience not less than 2 yrs in the same field. (ii) Cost of periodical maintanance of various equipment/parts shall be deemed to be included in quoted rates of respective items. (iii) Samples of effluent shall be collected from the outlet twice in a month as directed and got tested in a lab approved by State Pollution Control Board. Cost of testing is deemed to be included in the rate quoted. (iv) The contractor shall strictly follow the operation and maintenance manual of the plant as well as dosage of chemical prescribed by testing agency. (v) Periodical cleaning and removal of sludge from screen well, collection well, contact aeration tank, sludge aeration tank, settling tank, sludge drying beds, bar screen, screen through etc. (vi) Mixing chemical to maintain desired quality of end product of system including chemical required for the plant (vii) To maintain all working place and area neat and clean.
Notes for item No. 48 to 52 continued.. (vii) The work order for outsourcing of services shall be placed for eleven months and no price adjustment for its extension will be permissible. Necessary recovery will be made for non-operation of plant shift wise on pro rata basis of quoted rates of item. Recovery rate shall be double the rate quoted by the bidder for each shift and shall be final and binding. (viii) The Log sheet must be maintain by the contractor as directed by the Engr-in-charge (ix) Rate inclusive of all consumable materials. Rate also includes rectification of diffects during the operation within 8 hours including replacement of defective parts if any for smooth functioning of plant.
RYSA INFRATECH
Chandel Construction Company
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .