GE BHOPAL
GE BHOPAL BAIRAGARH BHOPAL
REPAIR REPLACEMENT OF LT NETWORK INCLUDING STREET LIGHT SECURITY LIGHT AND SOLAR LIGHTS AT ADM AREA CPE ITARSI UNDER GE BHOPAL
2025_MES_698151_1
8379/E8
Open Tender
Electrical and Maintenance Works
Item Rate
183 days
ITARSI
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GE BHOPAL
₹70,000
Yes
1 May 2025
15 Feb 2025
15 Mar 2025
15 Feb 2025
13 Mar 2025
1 Mar 2025
Amount
Note :(i) Please refer Sch A/ BOQ Notes before quoting the tender for all phases/ items mentioned below. (ii) Amount of Schedule of credit shall be deducted offline
Excavation in trenches in any type of soil n. exc 1.5 m wide and n. exc 1.5 m in depth and getting out for foundation of pole, laying under ground cables etc and getting out complete all as specified and as directed.
Excavation in trenches in soft/disintegrated rock exceeding 1.5 mtr wide and n.exe 3 mtr depth including getting out complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers n. exc 25 cm in soil complete all as specified and directed.
Removing excavated soil to a distance n. exc 50m and deposited at a level n.exc 1.5m above the starting point complete all as specified and directed.
M&L for river washed and screened dry sand for filling in trenches below and around the cable for cushioning including punning down as specified in relevant clause of SSR Part I complete all as specified and as directed. Note: Punned thickness of sand shall be measured and paid seperately.
Supplying and laying Class LV, Type I, flat, size 250mm x 150mm x 40mmfor cable protection cover as per IS 5820 , laid flat and dry in trenches over the cable perpendicular to the direction of cable complete all as specified and directed.
M&L for cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate in foundations, filling and mass concrete complete all as specified and directed.
M&L for cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate in copings to poles & the like, etc including weathering, slightly rounded or chamfered angles and throating as directed. including necessary form work complete all as specified and directed.
Dismantling of LT insulator of any type any size complete all as specified and directed.
M&L for shackle type porcelain vitreous white or brown insulator (LT) working pressure 1100 volts including galvnised mild steel straps of size 31X 3 mm and 12 mm dia insulator bolts, washers and nuts etc including dismantling unserviceable insulator of any size complete all as specified and directed.
M&L for pin type insulator of size 100 mm height, 65 mm dia porcelain vitreous white or brown/green insulator (LT) for working pressure 1100 volts with one galvanised spindle and two galvanised iron washers and nut including dismantling unserviceable insulator of any size complete all as specified and directed.
M&L for loop type insulator of size 60x90 mm, clearence of hole 16 mm porcelain vitreous white or brown/green insulator (LT) for working pressure 1100 volts including dismantling unserviceable insulator of any size complete all as specified and directed.
M&L for errection in position steel tubular swaged poles type 410 SP-31 (9.00 metres long) complete with cast iron base plate, finial taper plug, bolts, nuts, screws and top cover all as specified and including the following:- (a) Excavation in trenches not exceeding 1.5 mtr wide and 2 mtr deep for pole foundation and getting out in soft/ loose soil, returning filling in the excavation of soil after fixing the pole in foundation ramming earth around in layer not exc 25cm thick and disposal of surplus soil to a distance not exc 50 mtrs. (b) Material and labour for providing PCC 1:4:8 type D-2, using 40mm graded stone aggregate as in foundation, 600 X 600 mm cross section planting depth 1.8 mtr for concrete casing the pole upto GL complete all as directed. (c) Material and labour for providing PCC 1:3:6 type C-2, using 40mm graded stone aggregate for plinth block/collar above GL 300 mm high and 450mm dia all as directed. (d) Material and labour for painting of pole externally with one coat of black bituminous paint (upto planting depth) and above plinth block/concrete collar with two coat of aluminium paint over a coat of red oxide steel primer including preparation of surface including painting of 30cm wide blue bands 3 Nos. with synthetic enamel paint in alternate layer upto the height of 1.5m above plinth block. (e) Material and labour for writing letter or figures (Block, Roman, italic as Indian) with thick synthetic enamel paint of approved shade not exc height in numbering of pole all as directed.
S&F in replacement stay assembly comprising of galvanised iron stay bow of size 40 cm X14 cm, 20 mm dia & 1800 mm long GI stay rod including excavation, PCC, GI nuts MS stay plate 300 mm X 300 mm X 6 mm, 2 No thimble, 50X6 mm flat iron stay clamp, Steel stay wire 16 mm dia bolts , nuts and washers etc including taking down unserviceable stay assembly of any size complete all as shown in electrical plate No 1 of MES SSR 1991 Part 1 complete all as specified and as directed.
Dismantling cross arms, bracings, supports, clamps and back plates from existing poles (other than dismantled poles) and pole structures complete all as specified and as directed.
Fixing only cross arms, bracing, supports, clamps and back plate, obtained from demolition with & including new nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed.
M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel section including nuts, bolts, washers etc, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed and inclusive of applying one priming coat and two coats of synthetic enamel paint/aluminium paint including taking down corroded items of any type and size all as specified above complete all as specified and as directed.
Supply and fix and stringing of OH electric ACSR conductor of any size fixing to insulator with necessary binding wire of suitable size including taking down unserviceable ACSR conductor of any type and size complete all as specified and directed. Note:- (i) 3% extra will be added to the weight for sagging. (ii) Binding and jointing will not be considered for measurement and all the jumper shall be fixed with minimum 6 pg clamps and the quoted rate shall deemed to be include in the unit rate quoted.
Material and labour replacement of GI cradle guard hexagonal / rectangular with galvanised steel wire of 3.15mm to 4 mm dia including taking down unserviceable GI craddle of any size and type complete all as directed.
S&F of galvanised steel continuous earth wire of size 4.00 mm including taking down unserviceable GI earth wire of any size and type complete all as specified and as directed.
S&F of galvanised stay strand wire of size 7/4 mm including taking down unserviceable Stay wire wire of any size and type complete all as specified and as directed.
Restringing of LT over head line conductor comprising of any size ACSR conductor / GI wire on existing pole after opening from insulator by taking out of binding wire and refixing the same with suitable size of binding wire upto permissible sag after restringing including cutting of tree branches and trimming of smaller branches of any size up to 2 metre each side of OH line which touch/ falling on the OH line without damaging of 4 wire (3 phase and neutral) span exc 25.00m but n. exc 35.00m complete all as specified and as directed.
All as per item No. 22.00 here-in-before but 6 wire (3 phase, neutral and street light) span exc 25.00m but n. exc 35.00m.
M&L for GI tubing, light grade, 50mm dia with all necessary fittings, laid in trenches, under floor/road crossing, fixed on poles for cable protection fixed with the clamps made out of FI, 25 x 3mm duly painted with two coats of aluminium paint over a coat of approved primer etc. including taking down old unserviceable any size and capacity of GI pipe complete all as specified and directed.
M&L for GI tubing, light grade, 80mm dia with all necessary fittings, laid in trenches, under floor/road crossing, fixed on poles for cable protection fixed with the clamps made out of FI, 25 x 3mm duly painted with two coats of aluminium paint over a coat of approved primer etc. including taking down old unserviceable any size and capacity of GI pipe complete all as specified and directed.
M&L for PVC line spacer for LT over head line for 3 wire system complete all as specified and as directed. Note- Required T&P will be arranged by contractor no extra cost shall be paid.
S&F in replacement of three phase multi function electric energy LCD sub meter 10-60A, 3 Phase 440V LCD 4 wire KWH Meter 50HZ complete all as specified and directed.
M&L for painting to steel tubular pole with aluminium enamel paint of 9.00 Mtr including cross arms, clamps any size and nuts, bolts etc with one coat of aluminium synthetic enamel paint including preparing the surfaces free from finish particalsand making the smooth surface and numbering on pole with black ground such as pole number and source of supply, painting with radium paint around the pole at width of 10cm, similar three rounds from 1.5 m GL top on circumferance of pole complete all as specified and directed.
M&L for cutting and trimming of trees and branches to clear the over head line in the arc of HT/LT over head line feeders and removal of the trimmed branches of trees complete all as specified and directed. Notes : 1. Any ACSR conductor damaged during the cuttings of trees / branches shall be repaired and jointed / fixed by the contractor, to the entire satisfaction of Engr-in-Charge, without any extra cost and nothing extra shall be admissible from the department on this account what-so-ever. 2. The cutting / trimming of tree branches shall be done to atleast 2.00 metre radius of OH line. 3. The unit of measurement is 'SPAN' i.e. distance covered between two poles.
S&F in repairs on load change over switch 63 Amps 4 pole 415 volts 50 Hz . With S S Enclosure including taking down unserviceable one complete all as specified and directed.
S&F in repairs on load change over switch 100 Amps 4 pole 415 volts 50 Hz . With S S Enclosure including taking down unserviceable one complete all as specified and directed.
S&F of load changeover switch in sheet metal enclosure, heavy duty, 200 Amps, four pole, 415 Volts AC, 50 Hz with side handle including connectins complete all as specified and directed.
S&F of load changeover switch in sheet metal enclosure, heavy duty, 320 Amps, four pole, 415 Volts AC, 50 Hz with side handle including connectins complete all as specified and directed.
S&F in replacement of single phase multi function electric energy LCD sub meter 5-30Amp, 2 wire, 240V 50HZ complete all as specified and directed.
S&F in replacement of MCCB of follwoing sizes fixed with thermal & magnetic setting with extended terminals, replacemenr to LT panel/ Feeder piller box including connecting lugs with busbar and including mounting arrengments e.i. screws, bolt, nut, washers incl taking out old unsv complete all as specified and directed. Make-Legrand/Siemens/Schneider
(a) 400 Amp, 4 pole, 415 volts, thermal & magnetic release adjustable type with breaking capacity 36 KA complete all as specified and directed.
(b) 350 Amp, 4 pole, 415 volts, thermal magnetic release adjustable type with breaking capacity 36 KA complete all as specified and directed.
(c) 200 Amp, 4 pole, 415 volts, thermal magnetic release adjustable type with breaking capacity 36 KA complete all as specified and directed.
(d) 160 Amp, 4 pole, 415 volts, thermal magnetic release adjustable type with breaking capacity 36 KA complete all as specified and directed.
(e) 100 Amp, 4 pole, 415 volts, thermal magnetic release adjustable type with breaking capacity 16 KA complete all as specified and directed.
(f) 63 Amp, 4 pole, 415 volts, thermal magnetic release adjustable type with breaking capacity 16 KA complete all as specified and directed.
Supply, laying, commissioning and testing fixing in wall or passing through pipe, 1100 volts grade heavy duty with XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor including making input and output connections with using suitable size of thimbles, lugs, and glands complete of following cross sectional area as under including taking down Old UNSV cable complete all as specified and directed.
(a) 120 Sqmm 3.5 Core
(b) 95 Sqmm 3.5 Core
(c) 70 Sqmm 3.5 Core
(d) 50 Sqmm 3.5 Core
(e) 35 Sqmm 3.5 Core
(f) 25 Sqmm 3.5 Core
(g) 16 Sqmm 4 Core
(h) 16 Sqmm 2 Core
S&F in replacement of 1100 volts grade heavy duty cable of size 10 Sqmm 3.5 core, PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspen ded by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular complete all as specified and as directed.
S&F in replacment of 1100 Volts grade, heavy duty cable, PVC insulated copper cable, served with inner sheathing of PVC tape and overall PVC sheathed for hight mast light connection etc circular of size 4 Sqmm three core cable round type stranded conductor including taking down old unserviceable complete all as specified and as directed.
S&F in replacment of 1100 Volts grade, heavy duty cable, PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed for street light connections cable flat or cicrular of size 6 Sqmm twin core cable stranded conductor including taking down old unsv complete all as specified and as directed.
Supply, jointing, testing straight through jointing kit heat shrinkable out door type, suitable for LT 1100 Volts grade cable of size 95 Sqmm to 120 Sqmm 3.5 core complete all as specified and as directed.
Supply, jointing, testing straight through jointing kit heat shrinkable out door type, suitable for LT 1100 Volts grade cable of size 50 Sqmm to 70 Sqmm 3.5 core complete all as specified and as directed.
Supply, jointing, testing straight through jointing kit heat shrinkable out door type, suitable for LT 1100 Volts grade cable of size 25 Sqmm to 35 Sqmm 3.5 core complete all as specified and as directed.
Supply, jointing, testing end termination jointing kit heat shrinkable out door type, suitable for LT 1100 Volts grade cable of size 70 Sqmm to120 Sqmm 3.5 core complete all as specified and as directed.
Supply, jointing, testing end termination jointing kit heat shrinkable out door type, suitable for LT 1100 Volts grade cable of size 25 Sqmm to 50 Sqmm 3.5 core complete all as specified and as directed.
M&L for fixing MS sliding Locking door bolt of size not less then 12 mm dia, 250 mm length bolt, stove enameled black with bright bolt with staple plate on LT panel doors (for locking of doors) with min six nuts, bolts and washers including drilling and fixing on site complete all as specified and directed.
S&F of butt hinges, heavy weight, cold rolled mild steel, 100mm size duly welded to doors of LT panel board, etc complete all as specified and directed.
S&F in repairs LED indication lamps (RGY) (set of three) with complete connection complete all as specified and as directed.
Supply and spreading grass killer chemical all around to kill unwanted grass near or below the feeder panel and any E/M installation of cap 1 Litre bottle along with cleaning in vegetation for proper spreading of chemical to the roots by supplying adequate manpower and T&P complete all as specified and directed.
M&L for cutting of bituminous road/PCC hard standing/road/floor for laying of GI pipe upto 80mm dia (trench not more than 0.3m x 0.3m) for passing of cable including making good the disturbed surfaces all as per existing complete all as specified and directed. Note:-GI pipe shall be measured & paid separately under relevant items of this schedule.
M&L for servicing/repairing of APFC panel, any type and size upto 150 KVAR for making them functional, removing and cleaning of dusts, checking control wiring and connections, replacement of any damaged control wire, checking capacitors, tightening of all electrical connections and hardware, checking of metering devices, relays, etc, replacement of defective unserviceable parts to make the panel fuly functional complete all as specified and as directed. NOTE:- Spares required shall be paid separately as supply only item.
Supply and install in repair and Replacement of capacitor, metalized poly propylene heavy duty (MPP-H) three phase, 415 volts and 50 Hz system for permissible non-linear load 15 % of 1 to 5 KVAR required as per sample, to maintain power factor complete all as specified and as directed.
Supply and install in repair and Replacement of capacitor, metalized poly propylene heavy duty (MPP-H) three phase, 415 volts and 50 Hz system for permissible non-linear load 15 % of 10 KVAR capacity to maintain power factor complete all as specified and as directed.
Supply and install in repair and replacement of capacitor, metalized poly propylene heavy duty (MPP-H) three phase, 415 volts and 50 Hz system for permissible non-linear load 15 % of 15 KVAR capacity to maintain power factor complete all as specified and as directed.
Supply and install capacitor, metalized poly propylene heavy duty (MPP-H) three phase, 415 volts and 50 Hz system for permissible non-linear load 15 % of 25 KVAR capacity to maintain power factor complete all as specified and as directed.
S&F in repairs 3 phase contactor type (MNX 18 to 50) as per sample including taking down old unserviceable one complete all as specified and as directed.
S&F in repairs current transformer with CT required CT ratio as per existing sample complete all as specified and as directed.
S&F in repairs APFC relay set for APFC panel of size upto 150 KVAR capacity including taking down old unservicable one complete all as specified and as directed.
M&L for replacement of factory made RCC precast earthing pit cover chamber of size 400 mm x 400 mm x 300 mm & 65 mm thick complete all as specified and as directed.
M&L for earthing galvanized steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr depth below normal ground level) with top edge of earth not less than 1.5 mtr below normal ground level connected to and including galvanized steel strip 32 mm x 6 mm as earth lead upto equipment by means of steel bolts, nuts, check nuts and washers, test point made of GI strip 40x8mm, 10cm long PCC 1:2:4, type B-1 in pit with precast RCC 1:2:4 type B-1 in cover reinforced with XPM not less than 4 Kg per Sqm with 40mm bore GI light grade protection pipe, 20mm bore GI medium grade watering pipe with funnel including charcoal, dust, salt, all as shown in electric plate No 3 of SSR Part-I (2009) specifications, complete with necessary earth work in any type of soil, removal to a distance not exceeding 50 mtr including testing on completion & dismantling of existing earthing complete all as specified and as directed.
Labour only for attending day to day complaints for repairing of street light, security light, post top lantern of any size/ wattage including tighting loose electric connection, carbon deposition and any other minor defects required for its smooth functioning at Adm area CPE Itarsi by deputing skilled and qualified electrician alongwith helper at any time of the day as per site requirement complete all as specified and directed. Note:- (i) It is compulsary to attend maximum five nos complaints in a day within 24 hrs after intimation or receiving reciept of complain slip by JE/ AGE otherwise penalty of Rs 250.00 per day for non-attending the complaints will be levied on contractor. (ii) Complaints will be reported on daily basis with complaint register. (iii) Other minor items such as insulating tape, screws, small pieces of electrical cables PVC insulated copper multistranded conductor of size 2.5 Sqmm three core upto length of 1.5 m etc as required to attend the complaint is included in quoted rates. (iv) Any major items required for replacement will be paid seterately under respective item of Schedule 'A'.
S&F in repairs of LED driver suitable for 45-60Watt existing LED security/street lights of any make and model complete all as specified and as directed.
S&F in repairs of LED driver suitable for 70-100 Watt existing LED security/street lights of any make and model complete all as specified and as directed.
S&F in repairs of LED driver suitable for 120-200 Watt existing LED flood light of any make and model complete all as specified and as directed.
S&F of integral LED Street light luminaire of not less than 45 W, luman efficacy not less than 110 lm per watt, comprising of die cast alluminium housing, enclosed with glass cover in frame, IP-66 protection suitable for voltage range should be 170 to 240 Volts with glass cover and with all fixing arrangement, nuts, bolts and washer connecting to electric system with 2.5 sqmm PVC aluminium stranded conductor 2 core minimum 2.0 m length, on pole including testing complete all as specified and directed.
S&F of integral LED Street light luminaire of not less than 60 W, luman efficacy not less than 125 lm per watt, comprising of die cast alluminium housing, enclosed with glass cover in frame, IP-66 protection suitable for voltage range should be 170 to 240 Volts with glass cover and with all fixing arrangement, nuts, bolts and washer connecting to electric system with 2.5 sqmm PVC aluminium stranded conductor 2 core minimum 2.0 m length, on pole including testing complete all as specified and directed.
S&F of integral LED Street light luminaire of not less than 70 W, luman efficacy not less than 125 lm per watt, comprising of die cast alluminium housing, enclosed with glass cover in frame, IP-66 protection suitable for voltage range should be 170 to 240 Volts with glass cover and with all fixing arrangement, nuts, bolts and washer connecting to electric system with 2.5 sqmm PVC aluminium stranded conductor 2 core minimum 2.0 m length, on pole including testing complete all as specified and directed.
S&F of integral LED Street light luminaire of not less than 90 W, luman afficacy not less than 125 lm per watt, comprising of die cast alluminium housing, enclosed with glass cover in frame, IP-66 protection suitable for voltage range should be 170 to 240 Volts with glass cover and with all fixing arrangement, nuts, bolts and washer connecting to electric system with 2.5 sqmm PVC aluminium stranded conductor 2 core minimum 2.0 m length, on pole including testing complete all as specified and directed.
S&F of integral LED flood light following 100 Watt, 230 V AC High efficiency as per IS:16107 IP 66 degree of protection comprising of epoxy powder coated housing enclosed with glass cover in frame, with impact and corrosion resistant complete with driver and lamp complete with fixing arrangement, nuts, washers, bolts, clamps incl electric connection with 2.5 Sqmm PVC aluminium stranded conductor 3 core upto require length on pole, testing complete all as specified and as directed.
S&F of integral LED flood light luminaire of 120 W, high efficiency as per IS-16107, IP-66 degree of protection with pressure diecast alluminium housing and toughened glass and with all fixing arrangement, nuts, bolts, washer and clamps for fixing and connecting to electric system with 2.5 Sqmm PVC aluminium stranded conductor 2 core minimum 2.0 m length, on pole including testing complete all as specified and directed.
S&F of integral LED flood light luminaire of 150 W, high efficiency as per IS-16107, IP-66 degree of protection with pressure diecast alluminium housing and toughened glass and with all fixing arrangement, nuts, bolts, washer and clamps for fixing and connecting to electric system with 2.5 sqmm PVC aluminium stranded conductor 2 core minimum 2.0 m length, on pole inclduing testing complete all as specified and directed. Note for item no 64.00 to 70.00 Contractor shall produced manufacture test certificate and warrenty card for repair/replacement for 3 Years.
S&F in replacement for GFS Polycarbonate Thermoplastic oval shape weather proof junction boxes IP65, with internal embedded polyurethane material gasket IK-09 as per IEC 60695-2-11 for street lights size not less than 210 mmx155mmx102 mm with metric knockouts for cable entry, weather proof for outdoor installation and including glands and with 4 terminals for terminating of rating 32 Amps for three phase and neutral mounted with locking arrangement and fixed to the PCC/Steel Poles by means of suitable size of clamps with nut and bolts and incl provn for fixing 01 nos of single pole MCBs 6-32 amps, 10KA complete all as specified and as directed. Make: Hensel Cat part No-HENKFPJB-5/SINTEX/3S ENGINEERING
S&F in repairs GI pipe 40 mm dia, medium grade, for mounting bracket bent to shape 1.75 meter length and fixing arrangement with two Nos of MS clamps set, nut, bolts, washers, and applying two coats of aluminium paints over one coat of zinc oxide primer incl taking down old unsv complete all as specified and as directed.
S&F of aluminum lugs suitable for aluminum cable of size 16 Sqmm complete all as specified and as directed.
S&F of aluminum lugs suitable for aluminum cable of size 35 Sqmm complete all as specified and as directed.
S&F of aluminum lugs suitable for aluminum cable of size 50 Sqmm complete all as specified and as directed.
S&F of aluminum lugs suitable for aluminum cable of size 70 Sqmm complete all as specified and as directed.
S&F of aluminum lugs suitable for aluminum cable of size 95 Sqmm complete all as specified and as directed.
S&F of aluminum lugs suitable for aluminum cable of size 120 Sqmm complete all as specified and as directed.
S&F of Timer Switch (light sensor type nature switches), three phase plastic body degree of protection conforms to IP-64, operating illumination level for switching ON should be less than 60 lux for 30 seconds and for switching off must be greater than 10 lux for 30 seconds, multiple option switch for automatic and manual operations, capable to handle lightning load up to 8 KW, including MCB capacity 63 Amp conforms to IEC-60898 and IS-8828, Power contactor capacity 40 Amp conforms to IEC 60947-4-1, IS 13947-4-1 completely enclosed with plastic body panel conforms to IP-54 degree of protection, after taking down the burned control gears and cleaning the existing MS panel board, duly painted with two coats of epoxy coloured spray paint including taking down the existing unserviceable timer switch of any capacity and removing the site complete all as directed and as specified. Make : Kakatiya Energy systems Pvt Ltd, Model No SWADEEP- 02EC8kW1P or equivalent make in Havells/ Legrand / ABB / Schneider
S&F in repairs for Synthetic insulation mat with new synthetic insulation mat for insulation for LT panels, Transformer or DG Set of size 2mtr x1mtr x 12mm thick complete all as specified and as directed.
S&F of MCB SP 6-32 Amp, Curve C, 240 V, 10 KA complete all as specified and as directed.
S&F in reapirs /replacement of sensor of automatic street light control panel, three phase as per existing make on ground incl testing for automatic functioning of street light on timer complete all as specified and as directed.
Dismantling and taking down solar light fitting of wattage 11 to 25 watt comple with solar panel assembly, solar battery assembly, light controller, fixture mounting bracket for checking serviveablity, repair of solar lights and testing including minor repair and painting of pole with 2 coats of existing paint to make fully serviceable complete all as specified and as directed.
S&F in replacement of solar panel assembly complete with Light controller and MPPT charge controller suitable for 11 to 25 Watt solar street light as per existing make including electric connection complete all as specified and as directed.
S&F in replacement of solar light assembly suitable for 11 to 25 Watt solar street light as per existing make including electric connection and GI bracket if required complete all as specified and as directed.
S&F in replacement of Lead Acid solar battery 12V of capacity 75Ah suitable for 11 to 25 Watt solar street light as per existing make including electric connection complete all as specified and as directed. Note: Contractor shall produced warrenty card for repair/replacement for 3 Years.
M&L for earth continuity conductor or main earthing lead of 32x6 mm galvanised iron strip buried in ground or fixed to wall complete all as specified and as directed.
S&F in replacement cable pvc insulated and pvc sheathed of size 2.5 Sqmm three core stranded aluminium conductor complete all as specified and directed.
S&F in replacement maintenance free rechargeable battery 12 V, 100 AH tubular type with initial charging complete all as specified and directed. Note: Contractor shall produced warrenty card for repair/replacement for 3 Years
S&F of all-in-one integral solar light 20 Watt, Highly efficient not less than 90%, degree of protection IP 65 with built in high efficiency solar panel approved by MNRE, LED highly brightness high power light and long life lithium iron battery including BIS certified rechargeable cell with display showing for battery charging full charge, low voltage with different colour LED lamp with high efficiency microprocessor based charge controller and motion sensor. The has automatic dusk to down operation. The luminaire shall have specially designed pole mounting piece that enabled lateral as well as post top mounting and installation at varying tilts from 0 to 15 degree for optimal light distribution, including mounting pole of size 6 mtr long and earth, PCC work and electric cable for electric connection and any other parts for smooth functioning of solar lights testing complete all as specified and as directed.
Supply only in replacement of old unsv Hydraulic Crimping tool made of High-class Carbon Steel complete set with die of sizes 10 sqmm to 300 sqmm for crimping of aluminium/copper lugs in cable ends complete all as specified and as directed.
Supply only in replacement of old unserviceable Heavy Duty with High-Grade Aluminum wall reclining single Ladder as per IS 3696-2 (1991), 20 ft height, Rung Distance 280mm, Both ends connected to High-Grade Rubber Shoe for firm grip complete all as specified and as directed.
M&L for PVC line spacer for LT over head line for 2 wire system complete all as specified and as directed. Note- Required T&P will be arranged by contractor no extra cost shall be paid.
M&L for repairing of single phase electric energy meter 5-30Amp, 240V 50Hz making them functional, checking control connections, including replacement of any damaged parts etc. complete all as specified and directed.
Deduct amount of Rs. 60,290.00 for Schedule of credit (calculation will be done off line)
TANUJ CONST. CO. (BID ID -3261851)
M/S HARSH VIKAS GALAR ENGINEERING (BID ID -3262463)
Haryana EngineerService (BID ID -3256049)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .