| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.7 LAccepted-AOC NO 235 PSK ILLAM SANKARAN NAGAR CHINNAMMAN KOIL STREET AVADI CHENNAI 600 054 | CHENNAI | THIRUVALLUR | TAMIL NADU | 600054 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹40.0 L+₹5.3 L (15.3%)Rejected-Finance NO 229 ANGAPPAN STREET MITTANAMALAI AVADI IAF CHENNAI 600 055 | CHENNAI | CHENNAI | TAMIL NADU | 600055 | L2 | Rejected-Finance Not being lowest |
| Sl No | Description | Qty | Unit | PSK Enterprises L1 | muthu constructions L2 |
|---|---|---|---|---|---|
| 1.00 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth and getting out any type of soil for laying cables / pipes / erection of poles etc all as specified and as directed. | 735 | Cum | 260 ₹1,91,100 | 200 ₹1,47,000 Lowest |
| 2.00 | Removing excavated material(soil)not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as specified and as directed. | 305 | Cum | 98 ₹29,890 Lowest | 150 ₹45,750 |
| 3.00 | Returning filling in soil including spreading leveling watering well ramming in layers not exceeding 25 cm each all as specified and as directed. | 430 | Cum | 81 ₹34,830 Lowest | 150 ₹64,500 |
| 4.00 | Laying in trenches fine sieved excavated dry soil including spreading/leveling, cushioning for underground cables all as specified and as directed. | 215 | Cum | 98 ₹21,070 Lowest | 150 ₹32,250 |
| 5.00 | Supply and laying of common burnt clay building bricks, sub class B size for cable protection all as specified and as directed. | 21,600 | Each | 5.5 ₹1,18,800 Lowest | 6 ₹1,29,600 |
| 6.00Taking out from trenches/poles/wall etc LT XLPE UG Cable /PVC Sheathed aluminium conductor armoured and relaying after fault rectification duly tested in trenches/Poles/Wall of following sizes : (Note: Earth work and connected items will be measured and paid separately under respective items of schedule) | |||||
| 6.01 | 10 sq mm 2 core | 200 | RM | 125 ₹25,000 | 100 ₹20,000 Lowest |
| 6.02 | 16 sq mm 4 core | 430 | RM | 197 ₹84,710 | 160 ₹68,800 Lowest |
| 6.03 | 25 sq mm 3.5/4 core | 490 | RM | 224 ₹1,09,760 | 200 ₹98,000 Lowest |
| 6.04 | 35 sq mm 3.5 Core | 310 | RM | 242 ₹75,020 Lowest | 300 ₹93,000 |
Tender Value
₹44 L
EMD Value
₹88,000
Closing Date
10 Nov 2025, 6:00 pmClosed
Garrison Engineer, Avadi
Garrison Engineer , Muthapudupet, Air Force Area, Avadi, Chennai-55
REPAIRS AND REPLACEMENT OF PANEL BOARDS , CONNECTED CABLES, SWITCH GEARS, CHANGE OVER PANELS MISC. E/M WORKS , ARMY AREA UNDER GE AVADI.
2025_MES_737189_1
8337/E8
Open Tender
Electrical and Maintenance Works
Item Rate
260 days
GE Avadi
As per Tender Document
7 documents required · 7 mandatory
₹500
GE Avadi
₹88,000
Yes
20 Jan 2026
28 Oct 2025
12 Nov 2025
28 Oct 2025
10 Nov 2025
5 Nov 2025
28 Oct 2025 - 3 Nov 2025
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth and getting out any type of soil for laying cables / pipes / erection of poles etc all as specified and as directed.
Removing excavated material(soil)not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as specified and as directed.
Returning filling in soil including spreading leveling watering well ramming in layers not exceeding 25 cm each all as specified and as directed.
Laying in trenches fine sieved excavated dry soil including spreading/leveling, cushioning for underground cables all as specified and as directed.
Supply and laying of common burnt clay building bricks, sub class B size for cable protection all as specified and as directed.
Taking out from trenches/poles/wall etc LT XLPE UG Cable /PVC Sheathed aluminium conductor armoured and relaying after fault rectification duly tested in trenches/Poles/Wall of following sizes : (Note: Earth work and connected items will be measured and paid separately under respective items of schedule)
10 sq mm 2 core
16 sq mm 4 core
25 sq mm 3.5/4 core
35 sq mm 3.5 Core
50 sq mm 3.5 Core
70 sq mm 3.5 Core
95 sq mm 3.5 Core
120 sq mm 3.5 Core
185 sq mm 3.5 Core
Taking out from trenches/poles/wall etc LT XLPE UG Cable /PVC Sheathed aluminium conductor armoured and relaying after fault rectification duly tested in trenches/Poles/Wall of following sizes : (Note: Earth work and connected items will be measured and paid separately under respective items of schedule)
LT UG Cable 4 core 16 Sqmm
LT UG Cable 3.5/ 4 core 25 Sqmm to 3.5 core 50 Sqmm
LT UG Cable 3.5 core 70 Sqmm to 3.5 core 120 Sqmm
LT UG Cable 3.5 core 150 Sqmm to 3.5 core 185 Sqmm
Testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 1.1 KV LT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed. Note: (a) Excavation,earth work,cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Material and labour for emergency maintenance work of LT cable line during breakdown by deploying skilled electricians at faulty site including transportation and other tools and plant required at site for fault rectification.(c) Contractor or his rep shall come to the site of breakdown within two hours of notification of breakdown. In case the contractor or his rep shall not come to the site of breakdown and start attending breakdown within two hours, a penalty of Rs 600 per fault per hour shall be imposed over contractor and shall be deduct from his dues.
Supply and Fixing of Straight through joints heat shrink type for underground cable suitable for LT XLPE/ PVC sheathed/ armoured heavy duty cables with aluminium conductor all as specified and as directed of following sizes:-
3.5/ 4 core, 16 sqmm to 50 sqmm
3.5/ 4 core, 70 sqmm to 120 sqmm
3.5/ 4 core, 150 sqmm to 185 sqmm
Material and labour for GI tubing light grade for cable protection laid in trenches in road crossing or fixed to wall/Pole of following sizes including taking down old unserviceable one complete all as specified and as directed.
Bore of tube 40mm
Bore of tube 50mm
Bore of tube 80mm
Supply ,Fabricate, install, connect, test and commissioning Busbar chamber, powder coated, outdoor weather proof type, compartmentalised fabricated with 3 mm thick CRCA steel and suitable sized pressed steel frame work, top with sloping canopy, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit , chamber for aluminium busbars, separate compartment for switch gear, louvers and air vent for natural air flow, holes drilled for connection including suitable angle iron/flat iron frame work/ supports, excavation, earth work, PCC foundation etc., as required with and including following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete mounted on PCC pillars including taking down the old busbar chamber and demolition of old plain cement concrete complete all as specified and comprising of the followings:- (i) 4 Nos busbar of equal size of Aluminium conductor with PVC coloured heat shrinkable type sleeves continuous rating of 400 Amps mounted on fibre reinforced insulator.(1set), with LED indication lamps-03 Nos for RYB phases on incoming side. (ii) MCCB fixed thermal magnetic release type of capacity 200 amps, 4 pole, 36 kA.- 1 No.
Supply ,Fabricate, install, connect, test and commissioning Busbar chamber, powder coated, outdoor weather proof type, compartmentalised fabricated with 3 mm thick CRCA steel and suitable sized pressed steel frame work, top with sloping canopy, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit , chamber for aluminium busbars, separate compartment for switch gear, louvers and air vent for natural air flow, holes drilled for connection including suitable angle iron/flat iron frame work/ supports, excavation, earth work, PCC foundation etc., as required with and including following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete mounted on PCC pillars including taking down the old busbar chamber and demolition of old plain cement concrete complete all as specified and directed comprising of the followings:-
(i) 4 Nos busbar of equal size of Aluminium conductor with PVC coloured heat shrinkable type sleeves continuous rating of 400 Amps mounted on fibre reinforced insulator.(1set), with LED indication lamps-03 Nos for RYB phases on incoming side. (ii) MCCB fixed thermal magnetic release type of capacity 200 amps, 4 pole, 36 kA.- 1 Nos. (iii) On load change over siwtch 200 Amps ,4 pole 415 volts ,3 phase ,50 Hz AC - 01 No Note : MCCB shall be front handle operated.
Replacement of Aluminum Bus Bar having current rating 400 Amp duly insulated with colour coding RYB and Black all as specified and as directed including making holes on the bus bar for making necessary connections complete all as specified and directed.
Replacement of Aluminum Bus Bar having current rating 600 Amp duly insulated with colour coding RYB and Black all as specified and as directed including making holes on the bus bar for making necessary connections complete all as specified and directed.
M&L for replacement of Angle Iron for fixing Panel body shall be fixed on iron angle frame of size 40x40x5mm 40 cm grouted in 1:2:4 type 1 PCC 20 mm graded and 40 cm above the ground level duly painted with two coat of synthetic enammelled black paint over a coat of red oxide primer all as specified and directed
Replacement Ammeter meter 100x100mm 0- 200 amps of CT ratio 100/5, Digital type volts includind all electrical connection complete all as specified and directed.
Replacement Ammeter meter 100x100mm 0-4000 amps of CT ratio 100/5, Digital type volts includind all electrical connection complete all as specified and directed.
Replacement Voltmeter meter 100x100mm 0-500 Volts, DIgital type volts in cludind all electrical connection complete all as specified and directed.
Preparation of old painted surfaces ,removing dust and other deposited materials by scraping from LT panel inner and outer surface of front and rear doors including all compartment of MCCBs,busbar chamber,cable tray etc with one coat of same existing colour synthetic enamel paint by means of spray gun complete all as specified and directed.
Repair and welding work the existing panel board door with provision of new door by taking down the old rusted door and provided hinges for door, if necessary and lock arrangement with provision of suitable size of sliding bolt and cleaning the welding surfaces by rubbing and polishing with two coat of synthetic enamel paint to match with existing colour complete all as specified and directed.
Repair to the existing LT panel board/Bus bar chambers/Pole loop boxes for disconnecting faulty/burnt portion of cable and preparing fresh terminals with suitable size of new aluminium lugs,bolt, nuts and washers suitable for size of cable from 4/3.5 core x 10 Sqmm to 50 Sqmm by taking down the old burnt/rusted lugs, bolts , nuts and washers in necessary quantity as per site requirment including cleaning the busbars, provision of insulation sleeves to busbars where ever required complete all as specified and directed.
All as per above item but size of cable 3.5 core x 70 sqmm to 240 sqmm complete all as specified and as directed.
Cutting/clearing and removing the vegetation/ bush/creepers growth any nature/type around on the electric panel/feeder pillar box/busbar chamber so as to keep clean the area for easy access to carry out repair/maintenance works in electric panel/feeder pillar box/busbar chamber etc, removing from site and throwing out at a place all as specified and directed.
Supply and spreading Hard core of gauge not exceeding 63mm, deposited, spread and levelled in layers not exceeding 15cm thick watered and rammed to a true surfaces using broken stones for LT Panels yard/Transformer yard etc., complete all as specified and as directed.
Removal of UNSV PCC/Steel pole and M&L for steel tubular swaged poles complete with cast iron base plate final taper plug bolts, nuts & screw all as specified and directed Type 410 SP 31 (9 Mtr long) with two coat of aluminium paint over a coat of red oxide primer in full length of the pole with black and yellow strip up to 1.5 mtr over PCC coping alternatively including numbering the pole and necessary excavation incl dismantling the unserviceable pole etc complete all as specified and directed. (Note: Excavation, demolition of concrete, PCC for foundation, coping and connected items shall be measured and paid separately under relevant items)
Demolition of cement concrete of any description and in any position complete all as specified and directed.
M&L for PCC (1:4:8) type D2,( using 40 mm graded aggregate) as in foundations, filling and mass concrete Complete all as specified and directed.
M&L for PCC (1:3:6) type C1, (using 20 mm graded aggregate) as in foundations, for coping, filling and mass concrete with cement plastering finishing all as specified and directed.
Boring under roads without disturbing the top surface of the road for passing through the cables with using of 75 mm dia HDPE pipe. (Note : 1. Necessary infrastructure(Tools, Plants,Machinery and any eqpts) reqd for boring shall be arranged by the Contractor and rates deemed to be included for quoted rate. 2. HDPE pipe shall be measured and paid separately under relevant items) complete all as specified and directed.
M&L for 75 mm dia HDPE pipe PN-10 with fittings laid in trenches/wall for protection of underground cable when crossing the road/fixing on wall as in repair and all as specified and directed. (Make : Supreme/Prince).
M & L for Cutting of road/path for laying of GI tubing and making the good to disturbed road/ path including provision of PCC 1:2:4 type B-1 using 20mm graded stone aggregate all as specified and directed.
Material and Labour for MCCB 63 amps ,4 pole 415 volts ,3 phase ,50 Hz AC, 16 KA breaking capacity. The MCCBs shall have spreader links and barriers as standard feature of manufacturer including taking down old unserviceable one complete all as specified and as directed. Rates deemed to be included for necessary fixing arrangements with minor accessories in Panel boards complete as reqd at site.
All as per above item No. 33 above but of capacity 100/125 amps, 25 Ka including taking down old unserviceable one complete all as specified and as directed.
All as per above item 33 but of capacity 160 amps, 36 Ka including taking down old unserviceable one complete all as specified and as directed.
All as per item No. 33 above but of capacity 200 amps, 36 Ka including taking down old unserviceable one complete all as specified and as directed.
All as per Item No. 33 above but of capacity 250 amps,36 ka including taking down old unserviceable one complete all as specified and as directed.
All as per Item No. 33 above but of capacity 400 amps,36 ka including taking down old unserviceable one complete all as specified and as directed.
M&L for open enclosure type, on load change over siwtch 200 Amps ,4 pole 415 volts ,3 phase ,50 Hz AC suitable for fixing in Panels incl taking down old unsv complete all as specified and as directed.
Supply and Fixing MCB,240V,10KA,'B' curve,single pole,current carrying capacity 6 Amps, suitable for fixing in SMC box for control street/flood lights and making connections including taking down the old one complete all as specified and as directed .
Pole mounted Sheet Moulded Compound(SMC) Box weather proof type with hinged type door off white color of Size 300x200x100 mm comprising of 1 No MCB 6A complete all as specified and directed.
All as per Item No.41.00 above but size of 140x140x100 mm comprising of 1 No MCB 6A and 2 rows including taking down the old one complete all as specified and as directed.
Material and labour for 1100 volts grade heavy duty cable PVC insulated , PVC sheathed,fire resistant, round ,copper conductor, 3 core industrial cable of size 1.50 sqmm including taking down the old one complete all as specified and as directed.
Material and labour for 1100 volts grade heavy duty cable PVC insulated , PVC sheathed,fire resistant, round ,copper conductor, 3 core industrial cable of size 2.50 sqmm including taking down the old one complete all as specified and as directed.
Supply and Fixing of LED flood light fitting,230 V,AC, 50 W, LED, outdoor type,heat resistance toughened glass with frame IP 65/ 66 protection with driver, complete fixed on existing / New bracket and making connections including taking down the old one complete all as specified and as directed.
Supply and Fixing of LED flood light fitting,230 V,AC, 100/120 W, LED, outdoor type,heat resistance toughened glass with frame IP 65/ 66 protection with driver, complete fixed on existing / New bracket and making connections including taking down the old one complete all as specified and as directed.
Supply and Fixing of LED street light fitting,230 V,AC, 45 W, LED, outdoor type,heat resistance toughened glass with frame IP 65/ 66 protection with driver, complete fixed on existing / New bracket and making connections including taking down the old one complete all as specified and as directed.
Supply and Fixing of LED street light fitting,230 V,AC, 60 W, LED, outdoor type,heat resistance toughened glass with frame IP 65/ 66 protection with driver, complete fixed on existing / New bracket and making connections including taking down the old one complete all as specified and as directed.
Supply and Fixing of LED street light fitting,230 V,AC, 200 W, LED, outdoor type,heat resistance toughened glass with frame IP 65/ 66 protection with driver, complete fixed on existing / New bracket and making connections including taking down the old one complete all as specified and as directed.
M&L for street light bracket suitable for street/security light fittings upto 1.5 RM make out of GI pipe of light grade up to 32/40 mm dia proper shaped, bended, threaded and drilling holes for wire entry and MS clamp of suitable size in proper shape and designed including taking down unsv complete all as directed and specified.
Labour only, testing of earth resistance value using megger and record the reading in register, and retesting and record the reading after making arrangement as to achieve earth resistance with in permissible limit with help of saline water, salt, charcoal, magnesium suphate etc. Complete all as specified and directed. Note: (i) Salt, charcoal/coke, magenesium suplhate (MgSO4), shall be measured and paid for separately as material labour under relevant items. (ii) Testing shall be done as schedule interval and value will be noted with user/rep signature.
Material & labour, Supply of salt and mixing in water, and pouring into earth pit through watering pipe of chamber, in adequate quantity as to maintain earth resistance value within permissible limit, complete all as specified and directed.
Material and labour, Supply of Charcoal/coke powder, mixing in water and pouring into earth pit through water pipe of chamber, in adequate quantity to maintain earth resistant value within permissible limit, complete all as specified and directed.
Material and labour, Supply of magnesium sulphate (MgSO4), mixing in water and pouring into earth pit through water pipe of chamber, in adequate quantity to maintain earth resistant value within permissible limit, complete all as specified and directed.
Material and labour, test point terminal block made of gun metal or phosphorus bronze or copper, size 75mmx75mmx25mm, drilled and screwed including 3 nos. 8mm dia 25mm long hexagonal head screws, complete all as specified and directed.
Material and labour, Earth continuity conductor or main earthing lead or lightning conductor, 25mmx3.15mm aluminium strip, fixed to wall on batten with saddles and fixing screws or PVC/ Porcelain insulators etc. or recessed or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing or roof conductors and down conductors etc. as required, including brazing on both sides (over lapping) at all joints except test point, fixed as in replacement of existing strip, complete all as specified and directed.
Material & labour, brazing/ soldering on both sides (over lapping) to the copper strip of size 20mmx3mm and 25mmx3mm as earthing lead, including dismantling the old from the existing position/ equipment without disturbing the functional requirements of the equipments, and reconnecting, after repair/brazing, complete all as specified and directed.
M&L in replacement of wire mesh funnel GI type for fixing in 20/32mm dia GI light grade pipe complete all as specified & directed
M&L for earthing complete with galvanised steel earth plate electrode of size 60cm x 60cm x 6mm thick burried directly in ground vertically at a depth not less than 2.25 metre deep below normal ground level with top edge of the plate not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and electrode connections by using galvanised iron strip 25×4mm dia by means of bolts, nuts, check nuts and washers made of copper or brass and protected by light grade 15 mm dia GI pipe connected to main switch board or main control board, and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1: 2: 4 type C2 including excavation and earth work, disposal of surplus soil to a distance not exc. 50 mtr all as specified and as shown on Plate No 5 of SSR Part I (2009) all as specified and directed .
M&L for Earthing complete with galvanised steel earth plate electrode 60cm×60cm× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed.
Material and labour,Earth continuity conductor or main earthing conductor 25mmx4mm galvanised iron strip, fixed to wall on batten with saddles and fixing screws or PVC/ Porcelain insulators etc. or recessed or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required, including brazing on both sides (over lapping) at all joints complete all as specified and directed.
Repair of earth pit incl required exacavation, earth work and PCC work to make good damaged/disturbed surfaces of earth pit chamber & making new pit cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced and lifting handle on RCC cover with 8 mm MS bars at 150 mm centre to centre both ways incl supply & fixing of wire mesh and funnel including re-connection of earth wire/strip with panel/eqpts using GI nut, bolts & washer complete all as specified & directed.
muthu constructions (BID ID -3470582)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.50 MB
8337TENDERDOCUMENT.pdf
Tender Documents • 0.79 MB
BOQ_825417.xls
BOQ • 2.84 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .