Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | H1₹2.3 CrAccepted-Finance | ₹2.3 Cr | H1 | Accepted-Finance H1 Bidder |
| 2 | H2₹2.7 Cr+₹38.0 L (16.5%)Rejected-Finance 1ST FLOOR 239 8 KOTHAI HOUSE L J ROAD SHIVAJI PARK MAHIM MUMBAI 400 016 | MUMBAI | MUMBAI | MAHARASHTRA | 400016 | ₹2.7 Cr+₹38.0 L (16.5%) | H2 | Rejected-Finance H2 Bidder |
| 3 | H3₹2.6 Cr+₹29.5 L (12.8%)Rejected-Finance | ₹2.6 Cr+₹29.5 L (12.8%) | H3 | Rejected-Finance H3 Bidder |
Tender Value
Refer Docs
EMD Value
₹1 L
Closing Date
9 May 2022, 1:00 pmClosed
DIRECTOR
Nariman Bhavan, 156 157 15th Floor Nariman Point
Supply installation testing commissioning operation and maintenance for 5 years for the facade illumination of General Post Office
2022_TCADM_789567_1
dot/development/4/22
Open Tender
Electrical Works
Item Rate
365 days
Directorate of Tourism
Please refer Tender documents.
2 documents required · 2 mandatory
₹10,000
₹1 L
Online
16 Jun 2022
13 Apr 2022
12 May 2022
13 Apr 2022
9 May 2022
13 Apr 2022
20 Apr 2022
General Post Office LT Panel :Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/M.H/SLD/T6A).
Cubical : Supplying and erecting GI sheet 1.6 mm (16 SWG) to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint.
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete as per specification no. CP-BB
Supplying, erecting & marking FPMCB 40A to 63A B series in provided distribution board as per specification no. SWSWR/MCB
Supplying, erecting & marking TPN MCB 6A to 32A, B series in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting) in provided distribution board as per specification no. SW-SWR/MCB
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral as per specification no. CP-SPD
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver :
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable Tray : Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Cable :
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole as per specification no. CB-CE
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete. Specification no. EA-MOBI
Exterior Luminaires :
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen (Tolerence ±15%), the power consumption should not be more than 12 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen per meter (Tolerence ±15%), the power consumption should not be more than 12 watts per meter, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2000 lumen (Tolerence ±15%), the power consumption should not be more than 36 watts, 10° x 50° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen per meter (Tolerence ±15%), the power consumption should not be more than 15 watts per meter, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen (Tolerence ±15%), the power consumption should not be more than 10 watts, 10° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1500 lumen (Tolerence ±15%), the power consumption should not be more than 24 watts, 10° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen (Tolerence ±15%), the power consumption should not be more than 10 watts, 10°x30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen (Tolerence ±15%), the power consumption should not be more than 18 watts per meter, 10°x30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural pole/floor mounted IP66, flood light fixture complete with snoot and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 6500 lumen (Tolerence ±15%), the power consumption should not be more than 110 watts, 10° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be inbuilt non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural pole/floor mounted IP66, flood light fixture complete with snoot and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 6500 lumen (Tolerence ±15%), the power consumption should not be more than 110 watts, 40° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be inbuilt non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Royal Institute Of Science: LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/M.H/SLD/T3B).
Supply installation testing & commisioning of exterior rated architectural pole/floor mounted IP66, flood light fixture complete with snoot and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 6000 lumen (Tolerence ±15%), the power consumption should not be more than 100 watts, 60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be inbuilt non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural pole/floor mounted IP66, flood light fixture complete with snoot and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 6000 lumen (Tolerence ±15%), the power consumption should not be more than 100 watts, 4° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be inbuilt non dimmable with PF>0.9 & THD<20%. leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified & self declaration (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural pole/floor mounted IP66, flood light fixture complete with snoot and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 6000 lumen (Tolerence ±15%), the power consumption should not be more than 100 watts, 10° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be inbuilt non dimmable with PF>0.9 & THD<20%. leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified & self declaration (All the technical parameters of luminaire need approval from lighting consultant)
Supply and erection of 10 meter high pole of made in which pole pedstal should made of cast aluminium and pole should be GI in ribbed form. Thickness of the GI pole should be 3.2mm and aluminium pedstal thickness 6.5mm, Dia 150mm. Aluminum casted embalishments. Complete pole should be painted in PU paint and dark grey color. Base plate 450mm x 450mm x 10mm suitable to mount the pole on a concrete foundation. Pole must be connected to earthing.
Supply and erection of 4 meter high decorative pole of made in which pole pedstal should made of cast aluminium and pole should be GI in ribbed form. Thickness of the GI pole should be 3.2mm and aluminium pedstal thickness 6.5mm. Aluminum casted embalishments. Complete pole should be painted in PU paint and dark grey color. Base plate 300mm x 300mm x 10mm suitable to mount the pole on a concrete foundation. Pole must be connected to earthing.
Supply installation testing & commisioning of exterior rated posttop of system lumen output should not be less than 3500 lumen (Tolerence ±15%), the power consumption should not be more than 50 watts, 360° symmetrical optics, CCT 3000K. Single piece with circular shaped plant made of die cast aluminum using pressure die-casting process,with a decorative pineapple which is also made of die cast aluminum using pressure die-casting process, fixed on the top.Auxiliary and optical compartment can be accessed by tilting the top frame. Bottom frame in single piece, made of die cast aluminum using pressure die-casting process witha three curved uprights decorated which is also made of die cast aluminum using pressure die-casting process, fixed at the bottom with a hole (28 mm) for fixing to support. Frosted Screen made of polymethylmethacrylate (PMMA) moulded in a single piece using Injection moulding process. Screen's Impact resistance: IK06. Pure polyester powder coating in the same color as of the pole/as per the lighting consultant. Optical Compartment IP Rating - IP 66. Height – 700mm, Dia. - 470mm, Colour Rendering Index: Ra > 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection upto 4kv(an additional surge protection device of 10kV also provided in-built the fixture). Modular (2 X 2) refractive lens in PMMA with Type-II/III/IV photometric distribution options. protection screen in extra-clear tempered glass with impact resistance IK 08.LM80
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver :
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable Tray : Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Cable :
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole as per specification no. CB-CE
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete. Specification no. EA-MOBI
Exterior Luminaires :
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2000 lumen (Tolerence ±15%), the power consumption should not be more than 36 watts, 10° x 50° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1200mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2000 lumen (Tolerence ±15%), the power consumption should not be more than 40 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1100 lumen (Tolerence ±15%), the power consumption should not be more than 18 watts, 16° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1500 lumen (Tolerence ±15%), the power consumption should not be more than 18 watts, 10°x30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1500 lumen (Tolerence ±15%), the power consumption should not be more than 18 watts, 10°x30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen (Tolerence ±15%), the power consumption should not be more than 12 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen per meter (Tolerence ±15%), the power consumption should not be more than 12 watts per meter, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 700 lumen (Tolerence ±15%), the power consumption should not be more than 12 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2500 lumen (Tolerence ±15%), the power consumption should not be more than 36 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1200 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen per meter (Tolerence ±15%), the power consumption should not be more than 12 watts per meter, 10° x 60° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. IP65 driver boxes, leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply and erection of 4 meter high decorative pole of made in which pole pedstal should made of cast aluminium and pole should be GI in ribbed form. Thickness of the GI pole should be 3.2mm and aluminium pedstal thickness 6.5mm. Aluminum casted embalishments. Complete pole should be painted in PU paint and dark grey color. Base plate 300mm x 300mm x 10mm suitable to mount the pole on a concrete foundation. Pole must be connected to earthing.
Supply installation testing & commisioning of exterior rated posttop of system lumen output should not be less than 3500 lumen (Tolerence ±15%), the power consumption should not be more than 50 watts, 360° symmetrical optics, CCT 3000K. Single piece with circular shaped plant made of die cast aluminum using pressure die-casting process,with a decorative pineapple which is also made of die cast aluminum using pressure die-casting process, fixed on the top.Auxiliary and optical compartment can be accessed by tilting the top frame. Bottom frame in single piece, made of die cast aluminum using pressure die-casting process witha three curved uprights decorated which is also made of die cast aluminum using pressure die-casting process, fixed at the bottom with a hole (28 mm) for fixing to support. Frosted Screen made of polymethylmethacrylate (PMMA) moulded in a single piece using Injection moulding process. Screen's Impact resistance: IK06. Pure polyester powder coating in the same color as of the pole/as per the lighting consultant. Optical Compartment IP Rating - IP 66. Height – 700mm, Dia. - 470mm, Colour Rendering Index: Ra > 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection upto 4kv(an additional surge protection device of 10kV also provided in-built the fixture). Modular (2 X 2) refractive lens in PMMA with Type-II/III/IV photometric distribution options. protection screen in extra-clear tempered glass with impact resistance IK 08.LM80
National Gallery of Modern Art LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/M.H/SLD/T3B).
Cubical : Supplying and erecting GI sheet 1.6 mm (16 SWG) to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint.
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete as per specification no. CP-BB
Supplying, erecting & marking FPMCB 40A to 63A B series in provided distribution board as per specification no. SWSWR/MCB
Supplying, erecting & marking TPN MCB 6A to 32A, B series in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting) in provided distribution board as per specification no. SW-SWR/MCB
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral as per specification no. CP-SPD
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver :
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable Tray : Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Cable :
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole as per specification no. CB-CE
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete. Specification no. EA-MOBI
Exterior Luminaires :
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2000 lumen (Tolerence ±15%), the power consumption should not be more than 36 watts, 10° x 50° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1200mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2000 lumen (Tolerence ±15%), the power consumption should not be more than 40 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1100 lumen (Tolerence ±15%), the power consumption should not be more than 18 watts, 16° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1500 lumen (Tolerence ±15%), the power consumption should not be more than 18 watts, 10°x30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1500 lumen (Tolerence ±15%), the power consumption should not be more than 18 watts, 10°x30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen (Tolerence ±15%), the power consumption should not be more than 12 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 600 lumen per meter (Tolerence ±15%), the power consumption should not be more than 12 watts per meter, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 700 lumen (Tolerence ±15%), the power consumption should not be more than 12 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 2500 lumen (Tolerence ±15%), the power consumption should not be more than 36 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1200 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen (Tolerence ±15%), the power consumption should not be more than 15 watts, 10° x 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply installation testing & commisioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). system lumen output should not be less than 1000 lumen per meter (Tolerence ±15%), the power consumption should not be more than 12 watts per meter, 10° x 60° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. IP65 driver boxes, leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified (All the technical parameters of luminaire need approval from lighting consultant)
Supply and erection of 4 meter high decorative pole of made in which pole pedstal should made of cast aluminium and pole should be GI in ribbed form. Thickness of the GI pole should be 3.2mm and aluminium pedstal thickness 6.5mm. Aluminum casted embalishments. Complete pole should be painted in PU paint and dark grey color. Base plate 300mm x 300mm x 10mm suitable to mount the pole on a concrete foundation. Pole must be connected to earthing.
Supply installation testing & commisioning of exterior rated posttop of system lumen output should not be less than 3500 lumen (Tolerence ±15%), the power consumption should not be more than 50 watts, 360° symmetrical optics, CCT 3000K. Single piece with circular shaped plant made of die cast aluminum using pressure die-casting process,with a decorative pineapple which is also made of die cast aluminum using pressure die-casting process, fixed on the top.Auxiliary and optical compartment can be accessed by tilting the top frame. Bottom frame in single piece, made of die cast aluminum using pressure die-casting process witha three curved uprights decorated which is also made of die cast aluminum using pressure die-casting process, fixed at the bottom with a hole (28 mm) for fixing to support. Frosted Screen made of polymethylmethacrylate (PMMA) moulded in a single piece using Injection moulding process. Screen's Impact resistance: IK06. Pure polyester powder coating in the same color as of the pole/as per the lighting consultant. Optical Compartment IP Rating - IP 66. Height – 700mm, Dia. - 470mm, Colour Rendering Index: Ra > 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection upto 4kv(an additional surge protection device of 10kV also provided in-built the fixture). Modular (2 X 2) refractive lens in PMMA with Type-II/III/IV photometric distribution options. protection screen in extra-clear tempered glass with impact resistance IK 08.LM80
Maintaince charges for 1 yr
Maintaince charges for 2nd yr
Maintaince charges for 3rd yr
Maintaince charges for 4th yr
Maintaince charges for 5th yr
FRIENDS ELECTRICALS
ASC POWER PRIVATE LIMITED
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .