Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.0 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹26 L+₹7.1 L (37.3%)Rejected-Finance | L2 | Rejected-Finance Not being L1 | |
| 3 | Rejected-Technical | - | Rejected-Technical Due to non eligible category. |
Tender Value
₹29.6 L
EMD Value
₹59,500
Closing Date
6 Jul 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE, HQ 133 Works Engrs
HQ 133 Works Engrs PIN-914133 c/o 56 APO
SPECIAL REPAIR TO CHINAR COMN COMPLEX CENTRAL HEATING SYSTEM AND COOLING PLANT INSTALLED AT BLDG No. P-796 AT BB CANTT, SRINAGAR UNDER GE 864 EWS
2020_MES_350587_1
CWEK-24/2020-21
Open Tender
Support/Maintenance Service
Item Rate
180 days
GE 864 EWS
Class D Category c (i)
7 documents required · 7 mandatory
₹500
GE 864 EWS
₹59,500
Yes
HQ 133 Works Engrs
14 Aug 2020
6 Jun 2020
8 Jul 2020
6 Jun 2020
6 Jul 2020
22 Jun 2020
6 Jun 2020 - 16 Jun 2020
16 Jun 2020
60 days
Amount
Comprehensive repairs to central heating system (Thermal liquid/ horizontal glycol type) oil fired type as following:- Note: Spare/ parts required for the repairs shall be measured and paid separately under respective items
Dismanting the boiler coils from existing central heating plant by opening the boiler coil cover from the both sides and replacement of boiler coil of capacity 2 Lacs kCL/Hr with precision workmanship using tripod and chain pulley and inserting the coil inside combustion chamber including assembing the top cover plate and glycol tubing complete with electrical connections and testing the same complete all as specified and directed. Make: Rapid therm/ Thermax/ Alffatherm
Dismanting the burner assembly after disconnecting of all electrical and mechanical and oil connections replacement of burner assembly of capacity 200000 kCal/ hr as repair, refixing all the connections incl testing on load complete allas specified and directed.Make:-Eco flame/ relico
Descaling of boiler coils by opening of boiler coil cover from the both sides including disconnecting of inlet and outlet water connections of the boiler Removing the scale/ sludge precipitated in the boiler coil of capacity 2 Lacs kCL/ Hr. Closing the both sides of coils and circulating the the descaling compound solution in tubes of boiler through separate circulating pump and allow descaling solution to hold for 1 Hr for chemical reaction. After the duration of 1hr open the coil ends and clean with iron rod connected with nylon brush of suitable size as per tube size and ensuring that the coils has been descaled upto max clean range to the entire satisfaction of engr-in-charge, then closing both the ends of the coil and refixing the coil inside the chamber complete all as specified and directed.
Dismantling and isolating burnt blower motor from AHU (Air handling unit) by disconnecting all electrical and mechanical connection and reassembling, testing the same after carrying out rewinding of blower motor of capacity 10 HP 3 ph 415 volt 50 Hz with supper enamelled copper wire having same gauge after taking out old burnt winding including replacement of unserviceable bearing complete all as specified and directed
Disconnecting of suction, delivery lines and all electric connections of 3HP circulation pump motors for carrying out of repair/ replacement of wornout and defective parts, rewinding of burnout winding, replacement of bearing, impeller, pump assembly, shaft with fan and refixing the same after testing complete all as specified and directed.
MCCB 250 Amp, 3 pole 415 Volts, rupturing capacity 25 KA Adj thermal fixed magnetic MCCB including fixing arrangements complete and taking out old MCCB, complete all as specified and directed.
Repair/ overhauling of electrical control panel board including addition alteration in wiring system complete with replacement of defective parts such as voltmeter, Ammeter, frequency meter indicating lamps etc complete all as specified and directed.
Cleaning & painting of bulk oil tank of capacity 10 KL-01 Nos, day oil tank of Capacity 1KL- 02 Nos & pipe line system, chimney & allied accessories after draining out the existing glycol, all as directed by Engineer -in-charge.
Supply only glycol all as directed by Engineer -in-charge.
Repair to package type air condioning plant to cap 2X 15 tr complete with compressor , air cooled condensor after dismanting the plant as following all as directed by Engineer-in charge. Note: Spare/ parts required for the repairs shall be measured and paid separately under respective items.
Complete dismanting of package type airconditioner of capacity 2 X 15 Tr and taking out its compressor, drier filter, filter, humidifier humidistat, thermostat, pressure guage, mercury in glass industrial type thermometer etc and cleaning and complete servicing of package type aircondtioner of capacity 2 X 15 Tr including replacements of all filters (Drier and hepa) refilling of compressor oil, replacement of valves replacement of refregerant gas R-22 including replacement of other burnt/ unsv items and reinstalled the complete unit after complete sevicing as per specified and directed by Engineer-in-charge. Note: Regregerant Gas R-22 will be paid for separately in there respective items
Supply only refregerant gas R-22 in existing airconditioner as per specified and directed by Engineer -in-charge.
Dismanting of all electrical & mechanical connection of motor capacity 3 HP and rewinding with same gauge copper enemalled wire replacement of bearing, impeller and shaft with fan complete all as specified and directed.
Replacement of motor with fan of outer unit of existing package type air conditioner of capacity 2 X15 Tr as per given sample.
Supply & fixing compressor of capacity 7.5 Tr as per existing make & type incl taking out old unserviceable compressor all as specified and directed by Engineer-in-charge.
Supply in repair, installation, commissioning and testing of DX (direct Expansion) type package type airconditioning with all eqpts and accessories complete and comprising of:- Package Air Conditioning Plant :- (a) 1 Nos package type unit 11 Ton complete with compressors suitable electric motors, starters, air cooled condensers, flow switches as required, vibraton isolators, refigerant piping, insulation of pipings, wiring , accessories and controls as per specifications. The air handling unit for accessories and controls as per manufacturer specifications. The air handling unit for 100% packaged plant capacity with blower and blower motor and all accessories and controls comprising of:- (i) Refrigerant coils of copper tubes with aluminium fins (ii) Micro vee filters upto 10 micron particles and bypass dampers (iii) Humidification kit spray type with control spray handles, nozzles and spray pump (b) Ducting:- Supply air duct/ return duct made of aluminium sheet of 20/22 guage thick complete with dampers fixing and holding arrangements and insulation of same wherever required. The conditioned air obtained from the package units shall be fed to the required spaces through main duct as specified. (c) Isolation Louvers:- Louvers dampers with suitable length, lever and quadrants for manual controls to facilitate isolation during heating and vice versa, having interlocking arrangement to avoid simultaneous running of both the plants
(d) Instruments:-Control and instrument such as humidistat, thermostat, pressure guage, mercury in glass industrial type thermometer and other controls and instruments as required in normal application. (e) Electricals Control panel:- Main electrical panel board of suitable size made out of 1.6 mm thick CRCA sheet, cubical type duly painted with two coats of synthetic enamel paint over coat of paint over a coat of primer.Panel board shall consists of MCCBs, MCBs, Busbar DOL starter, etc of adequate capacity and as per manufacturer recommendation for various equipment like AHU, humidifiers etc including material required for electrical interlocking, sequence control and measuring equpment. (f) Cabling and Earthing: - (i) PVC insulated armoured conductor LT cable 1100 grade conforming to IS-1554(ISI marked) of suitable size from main panel to various eqiupment. (ii) cable will run on the wall with clamp/ cable tray/ in existing masonary ducts (iii) Aluminium strip as per IE and as per plate No 5 of SSR Part I shall be provided for all equipment and panel boards as per IS: 3043 all as directed. Note:- Ducting, Isolation Louvers, Earthing & LT cable shall be paid separately in respective items. (g) Civil Works:- (i) Rate deemed to be incl all civil works carpenters work including cutting chase , forming holes etc in walls ceiling, floors etc as required and making good to match with existing surfaces all as directed by engineer -in-charge required for installation of plant. Foundation for AC package plant will be as per Manufacturers instruction and incl in rate. Make: Blue star/ Voltas
Supply, installation, balacing and commissioning of fabricated at site Galvanised steel sheet thickness of 0.80mm rectangular ducting complete with neoprene rubber gasket, elbows, splitter dampers , vanes, hanger , supports etc duly applying two coats of rubber based adhesive CPRX compound on outer surface of duct and insulated with 13 mm thick elastromatic nitrile foam insulation of density 24 kg/ cubic metre cover with 400 microns polythene sheet with striking pin & finally finished with factory made laminated aluminium foil (vapour barrier) including sealing of all the overlaps, securing insulation with nylon/ steel strips of 12mm in a interval of 1.20 Mtrs as in existing/ new locations complete as all specified and directed.
Supply, installation, balacing and commissioning of fabricated at site Galvanised steel sheet thickness of 1.00mm rectangular ducting complete with neoprene rubber gasket, elbows, splitter dampers , vanes, hanger , supports etc duly applying two coats of rubber based adhesive CPRX compound on outer surface of duct and insulated with 13 mm thick elastromatic nitrile foam insulation of density 24 kg/ cubic metre cover with 400 microns polythene sheet with striking pin & finally finished with factory made laminated aluminium foil (vapour barrier) including sealing of all the overlaps, securing insulation with nylon/ steel strips of 12mm in a interval of 1.20 Mtrs as in existing/ new locations complete as all specified and directed. Note for Item No 10.00 & 11.00: width upto 750 mm of duct galvanised steel sheet of 0.80mm shall be provided & more than 750 mm but less than 1500mm galvanised steel sheet of 1.00mm shall be provided.
Supply and fixing of extruded aluminium supply grill/ diffusers dully powder coated with volume control dampers (size 300mmX 300 mm) complete as all specified and directed.
Supply and fixing of extruded aluminium supply grill/ diffusers dully powder coated with volume control dampers (size 375mm X 375 mm) complte as all specified and directed
Earthing complete with galvanised steel earth plate of size 60cmx60cmx6mm thick, burried directly in ground, earth pit not less than 2.25 m deep below normal ground level with top edge of the plate not less than 1.5m below normal ground level, connected to equipment by using GI strips of size 32x6mm as earthing lead by means of bolts,nuts,checknut & washers of galvanised iron all as shown in elect plate No.5 of MES schedule and connected to earthing test point all as specified and directed including earth pit of size 30cm x 30cm x 45cm made of PCC 1:3:6 and PCC 1:2:4 cover, funnel, GI tubing etc. & testing on completion, all as specified. Note : The units rate includes the cost of excavation & earth work in any type of soil charcoal & salt in altemate layers, 20mm GI Pipe (light grade) for watering 40mm GI protection pipe (light grade) funnel wire mesh PCC 1:2:4 type B1 chamber in cement concrete ,50 mm thick precast RCC M-25 ( Design mix) cover duly reinforced with XPM (weight not less than 3 kg /sqm ) and CI frame etc , and including provision of test point , connecting to test point and testing on completion etc, complete all as specified.
Surface levelling and excavation for PCC 1:2:4 platform of size 2mX 2m X 0.3m incl hard core, mild steel work post, trusse purlin rafter incl other work incl special shaped washer etc complete using EWR or induction butt welded of any section with 0.5 mm thick pre painted galvanised aluminium zinc coating GI based corrugated sheet having tensile strength of 550 mpa as in roof covering , shed of 3.0 X 3.0 mtr for packaged type airconditiner and equipment including steel structure for protection from rain and snow etc all as per site requirement and all as directed by Engr-in-charge.Please ref. Drg No CESZ/TD-1110/2011 Sheet 1/1 and 2/2 dated 01.12.11 for other details.
Supply, laying, testing and commissioning of cable LT XLPE insulated, PVC sheathed armoured, 1.1KV grade using stranded conductor aluminium of size 25 Sqmm 4 core confirming to IS specification on through wall with the MS clamp with nut & bolt of suitable size complete all as specified and as directed.
S &F TPN 63 Amp C series breaking capacity 10 kA incl TPN DB double door of 4 way all as specified and directed by Engineer-in charge.
Dismanting of wall and ceiling boards (fibre pulp, insulation etc) or insulation boards / slabs & Supply and fixing 4mm thick of size 600X600 mm HSPC (High pressure steam cured) pre-primetered self embossed, textured designer board E BOARD classic to be fixed & including GI based powder coated snap grid/ section (make: Armstrong) size 600mm X 600 mm with main runner 38X24X0.9 mm thick, cross tee 28.6X24X0.9 mm and wall 19X19X0.9 mm duly suspended with 4 mm dia GI bar hangers 1200 mm centre to centre both ways fixed with steel dash fasteners or from purlin from the roof with alignment clip including providing provision & fixing of existing light fixtures of any size complete all as specified and directed.
M/S SMA and SONS CONSTRUCTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .