Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹5.4 LAdmitted-Finance | +4.99% | ₹5.4 L | L1 | Admitted-Finance |
| 2 | L2₹6.1 LAdmitted-Finance | +18.00% | ₹6.1 L | L2 | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | - | - | - | Not Admitted-Fee/PreQual/Technical Others-DOCUMENTS ARE NOT AS PER NIT CONDITION |
Tender Value
₹5.1 L
EMD Value
₹10,257
Closing Date
14 Apr 2026, 12:00 pmClosed
EXCEUTIVE ENGINEER
BSNL ELECTRICAL DIVISION 1, EASTERN COURT, JANPATH, NEW DELHI-110001
Supply, Installation, Testing and commissioning of 2x5.5TR ductable type AC units at NIB switch room Kidwai Bhawan, Janpath, New Delhi
2026_BSNL_274308_1
03/NIT/E-TENDER/2026-27/ED-I
Open Tender
Electrical Works
30 days
KIDWAI BHAWAN JANPATH NEW DELHI
Please refer Tender documents.
4 documents required · 4 mandatory
₹590
Yes
A.O.(CASH) O/o CGM BSNL,NTR,NEW DELHI
₹10,257
Yes
15 Apr 2026
8 Apr 2026
15 Apr 2026
8 Apr 2026
14 Apr 2026
8 Apr 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, Installation, Testing and Commissioning of air cooled ducted split type air conditioning machine with each having a capacity and details as mentioned below suitable for operation on R 32/R-410A /R-407 Green refrigerant comprising of Scroll type compressor hermetically sealed complete with automatic capacity, safety switches, lubrication system with min 5 year(OEM) warranty for both compressor and Printed Circuit Board (PCB), Suitable capacity squirrel cage induction motor having class 'B' insulation suitable for operation on 415 + 10% volts, 50Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers, Microprocessor based control panel complete with accessories, machine Isolation /disconnect switch, valves and accessories to inter connect compressor and condenser including pressure testing, vacuum. Necessary starters suitable for Indoor & outdoor unit complete with O/L, U/V, phase reversal protection, single phase preventor i/c copper conductor control and power cable and drain pipe of suitable size and length etc. complete as required. The total cooling capacity/heating capacity of tested unit shall have a capacity as per relevant IS code. The lab testing reports as per IS: 8148 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL)accredited as per ISO/International Electro technical Commission (IEC) 17025 standards/ Central Power Research Institute (CPRI)/ Electrical Research and Development Association (ERDA) with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification as required. | |||||
| 1.01 | 5.5 TR (3.2 EER) | 2 | Nos. | - | - |
| 2SUB HEAD - II [Associated items] Providing/Fabricating and fixing M S Stand of suitable size for outdoor unit made out of 40x40x5 mm MS angle iron i/c cutting welding, painting, grouting etc complete with necessary MS angle support from the walls for Outdoor Unit mountings as required. | |||||
| 2.01 | 40 X 40 X 5 mm MS angle iron | 60 | Mtrs | 343 | ₹20,580 |
| 2.02 | 40 X 5 mm MS flat strip | 80 | Mtrs | 157 | ₹12,560 |
| 3Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft drawn copper refrigerant piping for AC system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications complete as required. (The item shall be measured from outside connection of indoor unit to outside of condenser unit). | |||||
| 3.01 | 9.5 mm dia with tube thickness 0.8 mm with insulation of suitable thickness | 30 | Mtrs | 423 | ₹12,690 |
| 3.02 | 15.87mm dia with tube thickness 0.8 mm with insulation of suitable thickness | 30 | Mtrs | 1,016 | ₹30,480 |
| 4Providing and fixing following size dia (nominal bore) FRLS, HMS (High Mechanical Stress), uPVC pipe from outlet socket of AC unit complete with uPVC fittings and clamps including cutting and making good the walls etc. complete as required. | |||||
| 4.01 | 40 mm dia. | 20 | Mtrs | 280 | ₹5,600 |
stage.html
html • 0.03 MB
technical_320224.pdf
techsummary_320224.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.73 MB
BOQ_320224.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid