Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹12.6 LAccepted-AOC 9 NAROTTAM KUNJ MADHU NAGAR AGRA CANTT 282001 | AGRA | UTTAR PRADESH | 282001 | 1 | Accepted-AOC Due to credit amount Rs 54708.00 | |
| 2 | 2₹13.4 L+₹25,910 (1.97%)Rejected-Finance | 2 | Rejected-Finance Being other than L-1 | |
| 3 | 3₹14.2 L+₹1.1 L (8.57%)Rejected-Finance NAGLA UDHA NEAR PRIMARY SCHOOL POST DHANOLI AGRA UP AGRA 282010 | AGRA | AGRA | UP | 282010 | 3 | Rejected-Finance Being other than L-1 | |
| 4 | 4₹16.7 L+₹3.6 L (27.6%)Rejected-Finance 38 49 D OLD IDGAH COLONY AGRA U P 282001 | AGRA | AGRA | UTTAR PRADESH | 282001 | 4 | Rejected-Finance Being other than L-1 |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
6 Oct 2022, 6:00 pmClosed
GE (AF) Adm Area Agra 282008
GE (AF) Adm Area Agra 282008
REPAIR REPLACEMENT OF LT UG CABLES LT CABLE END BOX MCCBS AND OTHER ALLIED WORKS IN 4 AREA UNDER GE AF ADM AREA AT AF STATION AGRA
2022_MES_551190_1
8000-1994/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AF Station Agra
Class E
cat b i
8 documents required · 8 mandatory
₹500
GE AF Adm Area Kheria Agra
₹30,000
Yes
2 Nov 2022
10 Sept 2022
8 Oct 2022
10 Sept 2022
6 Oct 2022
24 Sept 2022
10 Sept 2022 - 23 Sept 2022
Amount
Excavating in trenches n.exc 1.5 m wide and n.exc 1.5 m in depth for foundation etc or for laying for cables etc n.exc 10 sqm on plan and n.exc 1.5m in depth and getting out in any type of soil including removal of sand, bricks/PCC covers laid for cable proection complete all as specified and directed.
Returning, filling in, trenches including spreading, levelling, watering and well ramming in layers not exc. 25 cm in any type of soil complete all as specified and directed.
Removing surplus excavated material n.exc 50 m and depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and directed.
Supply & laying double walled corrugated (DWC) HDPE duct pipe conforming to IS 16205 Pt-24 of approved colour complete with fittings for cable protection of size 63 mm inner dia complete all as directed. Make :- Astral / JPC pipes Pvt Ltd./ Bhagwati Plastic & Agriculture Industries.
M&L for PCC 1:3:6 type C1 ( using 20mm graded stone aggregate) as in coping, plinth etc including necessary formwork and demolition of existing PCC complete all as specified and directed.
Material and labour for replacement of GI tubing light grade 50 mm bore for cable protection fixed on pole/wall or laid in floor/trenches/drain etc. complete with necessary clamp, nut, bolts, washers and socket for fixing the pipe and making good the disturbed surface of wall, floor or roof etc all as specified and directed.
Taking out old unserviceable LT UG cables of size 16 to 70 Sq mm 2/3.5/4 Core from trenches, poles/walls and floor for removing of fault or re-laying (Necessary earth work shall be measured and paid under respective item of Schedule) complete all as directed.
Taking out old unserviceable LT UG cables of size 95 to 150 Sqmm 3.5/4 Core from trenches, poles/walls and floor for removing of fault or re-laying (Necessary earth work shall be measured and paid under respective item of Schedule) complete all as directed.
Re-Laying XLPE LT UG cable PVC insulated, bedded armoured heavy duty electric cable 1100 volts grade with aluminium conductor of 16 to 70 Sqmm 2/3.5/4 Core (Item retreived from item 7 here-in-before) laid in trenches or fixed on wall/floor/poles after removing fault complete all as specified and directed.
Re-Laying XLPE LT UG cable PVC insulated, bedded armoured heavy duty electric cable 1100 volts grade with aluminium conductor of 95 to 150 Sqmm 3.5/4 Core (Item retreived from item 8 here-in-before) laid in trenches or fixed on wall/floor/poles after removing fault complete all as specified and directed.
Supply and Laying in floor/trenches or fixed on pole/wall XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor of 120 Sqmm 3.5 core complete all as specified and directed.
Supply and Laying in floor/trenches or fixed on pole/wall XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor of 95 Sqmm 3.5 core complete all as specified and directed.
Supply and Laying in floor/trenches or fixed on pole/wall XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor of 70 Sq mm 3.5 core complete all as specified and directed.
Supply and Laying in floor/trenches or fixed on pole/wall XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor of 50 Sq mm 3.5 core complete all as specified and directed.
Supply and Laying in floor/trenches or fixed on pole/wall XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor of 25 Sqmm 3.5 core complete all as specified and directed.
Supply and Laying in floor/trenches or fixed on pole/wall XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor of 16 Sqmm 4 core complete all as specified and directed.
M & L for drilling suitable dia horizontal bore holes for insertion / laying of 50/100 mm bore GI tubing of any description below/under road surface/floors etc. with using mechanical or manual devices as required at site including making good disturbed surface to match with the existing streta after laying pipes complete all as specified and directed
M&L for replacement of existing unsv Bus Bar Panel with new Bus Bar Panel of capacity 200 Amps copper bus bar 04 Nos with fixed on insulator welded with iron angle of size 40 x 40 x 6 mm thick grounting in floor, 0.45 mm depth grounting with PCC 1:3:6 upto ground level all as specified and directed. Cat Part No IHBC020004 of Make-Havells or equivalent in Legrand/L&T.
M&L for replacement of existing unsv Bus Bar Panel with new Bus Bar Panel of capacity 100 Amps copper bus bar 04 Nos with fixed on insulator welded with iron angle of size 40 x 40 x 6 mm thick grounting in floor, 0.45 mm depth grounting with PCC 1:3:6 upto ground level all as specified and directed. Cat Part No IHBC010004 of Make-Havells or equivalent in Legrand/L&T.
Clearing of bushes/small plants upto root level around and surroundings areas E/M installations (i.e. Two Pole/ Four structures, outdoor-substation yards & other Misc E/M installations etc.) soft and loose soil including surface dressing n.exc 15 cm deep and removing debris to a distance n.exc 50m complete all as directed
M&L in replacement of existing unsv MCCB 400 Amps current carrying capacity 36 KA, AC 415 Volts Ics= 100% Icu, four pole with magnetic/ thermal adjustable type setting complete all as specified and directed.
M&L in replacement of existing unsv MCCB 250 Amps current carrying capacity 25 KA, AC 415 Volts Ics= 100% Icu, four pole with magnetic/ thermal adjustable type setting complete all as specified and directed.
M&L in replacement of existing unsv MCCB 160 Amps current carrying capacity 25 KA, AC 415 Volts Ics= 100% Icu, four pole with magnetic/ thermal adjustable type setting complete all as specified and directed.
Cutting the existing road/ Hard standing for passing pipe/ cable and making good the disturbed surfaces by using 15 mm thick 1:4:8 in foundation type D-1 (using 20mm graded crushed stone aggregate) as in mass concrete complete all as specified exists complete all as specified.
M&L in replacament of existing old unsv earthing with steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earth lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full lenght of earth plate, 40 mm dia GI tubing light grade protection pipe upto test point, 20 mm dia GI watering pipe light grade with funnel and wire mesh, complete all as per SSR with PCC chamber, 50mm thick RCC cover in 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8mm dia TMT bar @ 80mm c/c both way, adequate qty of charcoal dust and salt layers all around the earth plate, including earth work in any type of soil, removal of surplus soil and returning filling in all as required at site including test point made out of steel plate of size 75x75x6mm fixed to wall all as shown on electric plate No 03 of SSR -2009 Part I complete all as specified and directed. (Note: Excavation and earth work is deemed to be included in the rates quoted).
Taking down existing old U/s panel board with all accessories and Supply, installing, erecting, testing and commissioning, factory made and tested LT Panel board, Out door type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated Aluminum busbars installed on porcelain/SMC insulators and all inter connection between main busbars as well as outgoing feeders shall be carried out with TPN Aluminum busbar of rating not less then 1.5 times rated capacity of individual out going feeders. The panel shall be dust and vermin proof, IP 56 class protection and made of 3 mm CRCA MS sheet and 50x50x6mm thick angle iron frame work, bottom channel of size: 70x40x5 mm powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front / back opening type, fixing 2 Nos. danger notice plate with letter, figures and conventional skull bones in signal red colour and fixed front & back door to LT panel etc with voltage and danger indicated in Hindi and English, with double door shutter and locking arrangement (including provn of 65mm Godrej(Freedom) stranded lock, internal wiring with PVC insulated, stranded copper conductor, FRLSH cables, IS-694 marked of adequate size but not less than 1.5 Sqmm. The platform shall be such that it is of a height 30 cm above the nearest ground level. complete all as specified and directed including connections of all out going/in coming existing cables of size 25 to 400Sqmm by drawing /digging out cable from loops in trenches/ ducts outside the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size Aluminum lugs for terminal connections of cables, necessary PCC foundation with plastering to the Panel board, All out going feeders shall be connected by cable through suitable size gland plate/ glands. The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and taking out of old Skelton type panel with control switches complete all as specified and directed. The scope of work includes the following Items:- NOTE:- Panel Builder should submit all Certificates before executing the job
Taking down existing old U/s panel board with all accessories and Supply, installing, erecting, testing and commissioning, factory made and tested LT Panel board, Out door type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated Aluminum busbars installed on porcelain/SMC insulators and all inter connection between main busbars as well as outgoing feeders shall be carried out with TPN Aluminum busbar of rating not less then 1.5 times rated capacity of individual out going feeders. The panel shall be dust and vermin proof, IP 56 class protection and made of 3 mm CRCA MS sheet and 50x50x6mm thick angle iron frame work, bottom channel of size: 70x40x5 mm powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front / back opening type, fixing 2 Nos. danger notice plate with letter, figures and conventional skull bones in signal red colour and fixed front & back door to LT panel etc with voltage and danger indicated in Hindi and English, with double door shutter and locking arrangement (including provn of 65mm Godrej(Freedom) stranded lock, internal wiring with PVC insulated, stranded copper conductor, FRLSH cables, IS-694 marked of adequate size but not less than 1.5 Sqmm. The platform shall be such that it is of a height 30 cm above the nearest ground level. complete all as specified and directed including connections of all out going/in coming existing cables of size 25 to 400Sqmm by drawing /digging out cable from loops in trenches/ ducts outside the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size Aluminum lugs for terminal connections of cables, necessary PCC foundation with plastering to the Panel board, All out going feeders shall be connected by cable through suitable size gland plate/ glands. The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and taking out of old Skelton type panel with control switches complete all as specified and directed. The scope of work includes the following Items:- NOTE:- Panel Builder should submit all Certificates before executing the job
M&L for dismantling the cable connections of four pole/ three pole Air circuit breaker of capacity upto 1000 Amps, 415 V, 50 Hz of Make Legrand/ CG/ L&T/ABB/ Havells/ C&S, strip opening the Air circuit breaker, inspecting the parts for serviceability/ overhauling complete and carrying out the following maintenance:- a) Cleaning the insulation parts including bushings with CTC solution. b) Checking the alignment and condition of movable and stationary contacts and adjust them all as per manufacturer's instructional manual. c) Check the bolts, nuts, washers, cotter pins and all terminal connections are in place and tights. Replace the worn-out parts. d) Check arc chutes for damage. e) Clean and lubricate the operating mechanism with a light machine oil for pins and bearings and with a non-hardening grease for the wearing surfaces. Adjust breaker operating mechanism all as per manufacturer's instructional manual. f) Checking / inspecting shunt trip coil for serviceability and replacing the same if required. g) Checking control device free for operation. j) Check after servicing the circuit breaker to verify the contacts move to the fully opened and fully closed positions, that there is an absence of friction and that the electrical operation is functional.
M&L for replacement of existing unsv cable straight through joints with straight through joints (heat shrinkable) any type suitable for XLPE 1100 Volts aluminium conductor cable of size 70- 150 Sqmm 3.5 core and testing after jointing. Note:- Rate quoted including necessary excavation, returning filling, removal etc for taking out loop/ cutting of burnt cable for required length for making end joint.
All as per item No. 31 but for cable size 185 - 300 Sqmm 3.5 core
Taking down existing MS articles and S&F new Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as directed.
S&F in replacement of Lithium based Energy Efficient integrated Solar street lights of 32 Watt in Single FRP Body with duly polylurethane coating (Camouflage color), encases with Monocrystalline solar PV Panel of 64/66 Wp, lithium battery 11.1/12.8V, 33.0 AH with inbuilt BMS, IP65, high brightness W-LED 160-180 lm/watt) lamp with Aluminium reflector for better light distribution, CRI>70, Colour Tempeture 5700K-6500K micro controller based charge controller curm driver automatic dimming function (first four hours at full brightness & rest of the time at lower light level with PIR Motion sensor), dust to dawn operation, suitable to working temperature; -100C to +550C, weight more than 16.18 Kg with adjustable MS clap suitable for pole/wall mounting etc s complete all as specified and directed. Protection : Short circuit over load reverse plolarity and battery protections. firm should provide Vital parameters test report from NABL accredited lab and should be of made in India CE & ROHS compliant. Make - Axxon (AXN-32)/Okaya power Pvt Ltd/Havells/Halonix
m/s Agra Builder
MUKTA AND COMPANY
GUPTA ENGINEERING WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .