Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.9 LAccepted-AOC | L1 | Accepted-AOC Being L1. | |
| 2 | L2₹18.9 L+₹1.0 L (5.72%)Rejected-Finance AZAD COLONY B 90 FEET ROAD SOURA SRINAGAR J K 190011 | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 190011 | L2 | Rejected-Finance Other than L1. | |
| 3 | L3₹20.6 L+₹2.7 L (15.2%)Rejected-Finance | L3 | Rejected-Finance Other than L1. | |
| 4 | L4₹20.7 L+₹2.8 L (15.8%)Rejected-Finance RAWALPORA WANABAL PATI YAYIL POST OFFICE SANAT NAGAR SRINAGAR 190005 J K | SRINAGAR | JAMMU AND KASHMIR | 190005 | L4 | Rejected-Finance Other than L1. |
Tender Value
₹20.3 L
EMD Value
₹40,500
Closing Date
28 Jan 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE, HQ 134 Wks Engr
HQ 134 Wks Engr PIN-914134 C/o 56 APO
PROVN OF 1 X 15 KVA AND 1 X 62.5 KVA GENERATOR SET AND HOT WATER PLANT AT VARIOUS LOCATIONS UNDER GE 861 EWS.
2022_MES_572383_1
134 WE-80(T)/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Srinagar
9 documents required · 9 mandatory
₹500
Yes
GE 861 EWS
₹40,500
Yes
15 Mar 2023
31 Dec 2022
30 Jan 2023
31 Dec 2022
28 Jan 2023
14 Jan 2023
31 Dec 2022 - 7 Jan 2023
Amount
Supply, installation, testing and commissioning of Diesel Engine driven generating set, water cooled of capacity 15 KVA, 415 Volts, 0.80 power factor at an altitude of 5515 feet above MSL with relay panel and switch gear for automatic starting, control panel having meters and sound proof canopy, mounted on common base plate with flexible coupling with and including of acoustic insulated chamber to maintain noise level as per CPCB norms for capacity of 15 KVA DG set complete inbuilt with all accessories and totally enclosed type with silencer pipe protected with asbestos rope from engine to outside the building, 0.50 mtr and independently supported AVM pads, battery starter type, DG Set should be capable of operating in temperature range (-)15º to (+) 39º Celcius with and including the following :- Note :- Cost of foudation of DG set as per manufacturer's size and specifications shall be deemed to be included in quoted rates.
(A) Diesel Driven Engine :- Vertical diesel engine of suitable capacity 15 KVA at an altitude of 5515 feet above MSL, water cooled type closed, circuit as per BS-649 or IS-10002, direct injection type turbo charged, battery starting system having rated speed 1500 RPM. The DG Set shall be capable of running 24 hours continuously with 10% over loading for one hour in every 12 hours run as per BS- 5514/BS-649. Engine shall be equipped with all standard fittings as per manufacturer’s recommendation & mounted common plate through flexible coupling with following fittings :- (i) RPM cum hour meter. (ii) Battery charging ammeter. (iii) Ignition key and starting with button switch. (iv) Lubricating oil pressure gauge. (v) Mechanical / electric governor controlling. (vi) Oil temperature gauge. (vii) Safety control with tripping facility for the following :- (a) Low lubricant oil pressure. (b) Over speed. (c ) High water temprature. (viii) Starting equipment comprising of following :- (a) Battery as per manufacturer's recommendation Make :- Exide / Luminus / Amron (b) Battery, charging alternator with inbuilt regulator. (c) Battery leads of copper cable of suitable size brass thimbles and terminals.
(D) Other fitting (i) Battery Charger - Battery charger having electric circuit consisting of triodes, rectifiers, capacitor and resistance etc. The battery charger should be able to charge the battery at all the time whenever electric supply is given to the battery. (ii) Fuel tank made up of MS Sheet of suitable capacity as per manufacturer’s instructions capable to store fuel for 12 hours running of DG set fixed as per manufacturer`s design and return fuel pipe with all pipes connecting upto fuel pump including oil level indicating gauge, drain plug for cleaning and air vent plug etc. (iii) Accousite enclosure with natural air circulation without loss of any power for ventilation fan. The enclosure shall be modular in construction with hinge bolted structure to provide easy dismantling and shall be made out of high quality CRCA sheet steel of 1.6mm thick with sufficient accessories for maint work, openable and locable door with air light rubber gasket, interior lighting arrangement. (iv) Emission control device should be filted to DG set as per present CPCB norms.
Supply, installation, testing and commissioning of Diesel Engine driven generating set, water cooled of capacity 62.5 KVA, 415 Volts, 0.80 power factor at an altitude of 6835 feet above MSL with relay panel and switch gear for automatic starting, control panel having meters and sound proof canopy, mounted on common base plate with flexible coupling with and including of acoustic insulated chamber to maintain noise level as per CPCB norms for capacity of 62.5 KVA DG set complete inbuilt with all accessories and totally enclosed type with silencer pipe protected with asbestos rope from engine to outside the building, 0.50 mtr and independently supported AVM pads, battery starter type, DG Set should be capable of operating in temperature range (-)15º to (+) 39º Celcius with and including the following :- Note :- Cost of foudation of DG set as per manufacturer's size and specifications shall be deemed to be included in quoted rates.
(A) Diesel Driven Engine :- Vertical diesel engine of suitable capacity 62.5 KVA at an altitude of 6835 feet above MSL, water cooled type closed, circuit as per BS-649 or IS-10002, direct injection type turbo charged, battery starting system having rated speed 1500 RPM. The DG Set shall be capable of running 24 hours continuously with 10% over loading for one hour in every 12 hours run as per BS- 5514/BS-649. Engine shall be equipped with all standard fittings as per manufacturer’s recommendation & mounted common plate through flexible coupling with following fittings :- (i) RPM cum hour meter. (ii) Battery charging ammeter. (iii) Ignition key and starting with button switch. (iv) Lubricating oil pressure gauge. (v) Mechanical / electric governor controlling. (vi) Oil temperature gauge. (vii) Safety control with tripping facility for the following :- (a) Low lubricant oil pressure. (b) Over speed. (c ) High water temprature. (viii) Starting equipment comprising of following :- (a) Battery as per manufacturer's recommendation Make :- Exide / Luminus / Amron (b) Battery, charging alternator with inbuilt regulator. (c) Battery leads of copper cable of suitable size brass thimbles and terminals.
(D) Other fitting (i) Battery Charger - Battery charger having electric circuit consisting of triodes, rectifiers, capacitor and resistance etc. The battery charger should be able to charge the battery at all the time whenever electric supply is given to the battery. (ii) Fuel tank made up of MS Sheet of suitable capacity as per manufacturer’s instructions capable to store fuel for 12 hours running of DG set fixed as per manufacturer`s design and return fuel pipe with all pipes connecting upto fuel pump including oil level indicating gauge, drain plug for cleaning and air vent plug etc. (iii) Accousite enclosure with natural air circulation without loss of any power for ventilation fan. The enclosure shall be modular in construction with hinge bolted structure to provide easy dismantling and shall be made out of high quality CRCA sheet steel of 1.6mm thick with sufficient accessories for maint work, open able and locable door with air light rubber gasket, interior lighting arrangement. (iv) Emission control device should be filted to DG set as per present CPCB norms.
Supply, laying, commissioning & testing XLPE LT cable, 1100 volts grade, PVC insulated, heavy duty, armoured, multistranded aluminium conductor cable of size 35 Sqmm 3.5 core, laid in trenches, fixing on wall/pole, under road crossing etc, complete all as specified and directed by Engr-in-Charge. Note :- Earth work, sand cushioning and brick covering shall be measured and paid separately under respective items of BOQ.
Supply, laying, commissioning & testing XLPE LT cable, 1100 volts grade, PVC insulated, heavy duty, armoured, multistranded aluminium conductor cable of size 95 Sqmm 3.5 core, laid in trenches, fixing on wall/pole, under road crossing etc, complete all as specified and directed by Engr-in-Charge. Note :- Earth work, sand cushioning and brick covering shall be measured and paid separately under respective items of BOQ.
M&L for earthing complete with GI steel earth plate electrode of size 600mm x 600mm x 6mm thick, burried directly in ground pit not less than 2.25 mtr deep below normal ground level with top edge of earth plate not less than 1.5 mtr below normal ground level, connected to the Galvanised iron strip of size 32x6mm by means of bolts, nuts, check nuts and washers of galvanised steel, connected to earthing test point with and including necessary excavation and earthwork and earth electrode, earthing lead from electrode to eqpt/sub stn, adequated quantity of charcoal dust and common salt, test point, PCC 1:3:6 type C-1 (using 20mm graded stone aggregate), 40mm thick RCC (type B-1) cover reinforced with 8mm dia TMT bar both ways with 12mm dia round bar handle and 20mm bore GI light grade watering pipe with funnel and wiremesh and 40mm bore GI pipe light grade for protection of earth lead upto equipments max length 7.5 mtr, complete all as shown on electrical plate No. 3 of MES SSR Part-I (2009) and directed by Engr-in-Charge. Note :- On testing after completion if the desired resistenance is not obtained, the contrator shall redo the earthing without any extra cost to the department.
S&F OFF LOAD change over switch 415 volt in sheet metal enlosures 4 pole of capacity 200 Amps, complete all as specified and directed.
Excavation in trenches, not exceeding 1.5 mtr wide and not exceeding 1.5 metre in depth for foundation for laying cables/pipes etc. including getting out any type of soil, complete all as specified and directed by Engr-in-Charge.
M&L for dry river sand, laid in trenches for cable protection, as 15cm thick below the cable and 8cm thick above the cable after laying, complete all as specified and directed. Note :- Punned thickness of sand shall be measured & paid.
M&L for sub class 'B' brick, old size, as in covering or protection of electric cable, laid dry flat transversally along the length of cable on sand cushioing with width equal to length of brick etc, complete all as specified and directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick, complete all as specified and directed.
Removing excavated material (soil) to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point, complete all as specified and directed.
M&L for 80mm bore GI pipe, light grade with all fittings, for protection of cable, laid in trenches, road crossing and fixed to pole/wall with MS clamps of suitable size, nuts and bolts and including two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer after preparation of surface, complete all as specified and directed by Engineer-in-Charge.
Supply, installation, testing and commissioning of Hot Water Generator Shell & Fire tube type (horizontal) of capacity 50,000 Kcal/Hr, oil fired, fully automatic, mono-block burner, minimum power, space and fuel requirement, excellent thermal efficiency level upto 90% on NCV, MS chimney 5"x 5", pressure gauge 2 Nos, thermostate sensor - 1 Pair, Oil tank 100 Ltr capacity & 1/2" ball valve, hot water mixing hopper with float, MS ERM heavy 2" pipe line and valve and suitable rating of digital control panel, PCC foundation with suitable size as per OEM recommendation, complete with all accessories, fittings and fixtures as required including with the following specifications :- (i) Heat Output (F&A 100 degree centigrade ) - 50,000 KCal/hr (ii) Furnance - Internal (iii) Fuel to be fired - Diesel / HSD (iv) Fuel NCV (HSD) - 10800 Kcal/Kg (v) Working pressure max - 1-3 Kg/cm2(g) (vi) Hydraulic test pressure - 10.5 Kg/cm2(g) (vii) Boiler tube - BS : 3059 PT-2, Gr-360, 51 OD, 3.66mm thick (viii) Outlet temperature max - 90 degree Centigrade (ix) Electricty supply - 3 Phase , 415 volts, 50 Hz, AC (x) Water Circulation Pump - 1 HP , H-47 & Q 55 LMP Max
S&F stainless steel (SS 304 Grade) 500 Ltrs capacity, 4mm thick tank for storage of hot water with legs, main Hole Nozzle with flange, complete all as specified and directed by Engineer-in-Charge.
M&L for 1000 Ltrs capacity rotational moulded polyethylene water storage tank (cylindrical vertical with closed top), hoisted and fixed in position including 25mm bore PVC float valve, complete all as specified and directed.
M&L for cross arms, bracings, supports, clamps and back plates, fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one coat of red oxide zinc chrome primer and one under & finishing coat of synthetic enamel paint for staging for water tanks etc, complete all as specified and directed.
M&L for 40mm bore GI water tube, medium grade with all fittings and fixtures, complete to laid in floors/trenches, complete all as specified and directed.
M&L for 25mm bore GI water tube, medium grade with all fittings and fixtures, complete to laid in floors/trenches, complete all as specified and directed.
M&L for 20mm bore GI water tube, medium grade with all fittings and fixtures, complete to laid in floors/trenches, complete all as specified and directed.
M&L for 15mm bore GI water tube, medium grade with all fittings and fixtures, complete to laid in floors/trenches or fixed to walls, complete all as specified and directed.
S&F 40mm bore gun-metal, globe or gate valve, with iron wheel head, screwed both end for iron pipe and fixed, complete all as specified and directed.
S&F 25mm bore gun-metal, globe or gate valve, with iron wheel head, screwed both end for iron pipe and fixed, complete all as specified and directed.
S&F 20mm bore gun-metal, globe or gate valve, with iron wheel head, screwed both end for iron pipe and fixed, complete all as specified and directed.
S&F 15mm bore bib tap, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for rass ferrule and fixed,complete all as specified and directed.
M&L for lagging to 20mm bore GI pipes used in external water supply or plumbing all round with, 25min thick bonded mineral wool preformed ‘SNAP ON’ pipe sections of density 144 Kg/cum conforming to IS-9842 and including chicken wire mesh netting 25 gauge, 20mm meshing & Plaster Of Paris (POP) 3-5mm thick all around the mesh, complete all as specified and directed by Engineer-in-Charge.
M&L for lagging to 15mm bore GI pipes used in external water supply or plumbing all round with, 25min thick bonded mineral wool preformed ‘SNAP ON’ pipe sections of density 144 Kg/cum conforming to IS-9842 and including chicken wire mesh netting 25 gauge, 20mm meshing & Plaster Of Paris (POP) 3-5mm thick all around the mesh, complete all as specified and directed by Engineer-in-Charge.
FG CONSTRUCTION
M/S AKMAL CONSTRUCTIONS
FIRDOUS AHMAD BABA
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .