Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.6 LAccepted-AOC NEAR SVN UNIVERSITY NARSINGHPUR ROAD SIRONJA SAUGOR MP 470228 | SAUGOR | SAGAR | MP | 470228 | L1 | Accepted-AOC lowest and reasonable | |
| 2 | L2₹12.1 L+₹1.0 L (9.30%)Rejected-Finance | L2 | Rejected-Finance not lowest | |
| 3 | L3₹12.6 L+₹1.6 L (14.2%)Rejected-Finance 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | L3 | Rejected-Finance not lowest |
Tender Value
Refer Docs
EMD Value
₹30,000
Closing Date
1 Jan 2021, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE AF NAGPUR
OFFICE OF GARRISON ENGINEER AIR FORCE VAYUSENA NAGAR NAGPUR- 440007
REPAIR MAINTENANCE REPLACEMENT OF LT DISTRIBUTION SYSTEM AT VSN NAGPUR
2020_MES_400618_1
GE/NAG/20-21/8405/52
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF NAGPUR
As per NIT
8 documents required · 8 mandatory
₹500
GE AF NAGPUR
₹30,000
9 Mar 2021
4 Dec 2020
2 Jan 2021
4 Dec 2020
1 Jan 2021
18 Dec 2020
60 days
Amount
Taking down the unserviceable LT cable of any size from trenches/ walls /floor etc complete all as specified and as directed by engineer in charge . Note :- laying of cable route is same as old cable route
Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 10 sq mm 2 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed.
Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 16 sq mm 4 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed.
Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 25 sq mm 4 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed.
Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 35 sq mm 3.5 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed.
Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 50 sq mm 3.5 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed.
Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 120 sq mm 3.5 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed.
Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 240 sq mm 3.5 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed.
Excavation in trenches in hard/dense soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of cables and getting out of excavated material complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the pipes have been laid and tested complete all as specified and directed.
Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed.
M & L for Low density polyethylene pipes (LDPE) of pressure rating 6 kgf/cm2 of size 40 mm dia laid in trenches for passing of LT cable complete all as specified and directed.
M & L for Low density polyethylene pipes (LDPE) of pressure rating 6 kgf/cm2 of size 50 mm dia laid in trenches for passing of LT cable complete all as specified and directed.
M & L for Low density polyethylene pipes (LDPE) of pressure rating 6 kgf/cm2 of size 100 mm dia laid in trenches for passing of LT cable complete all as specified and directed.
Excavation of road cutting by manually including making good to disturb surface after the completion of work with PCC 1:2:4 type B2 on top not less than 150 mm thick including levelling and cambering according to existing road surface, refilling, watering, ramming etc all as specefied and as directed. Note : Depth of excavation shall be 0.6 Mtr and width 0.45 Mtr complete all as specified and directed.
Supply and fixing GI pipe light grade with necessary fittings in floor /piller/fixed on pole of size 80 mm dia complete all as specified
Supply and fixing GI pipe light grade with necessary fittings in floor /pillar/fixed on pole of size 40 mm dia complete all as specified
M & L for Straight through joint kit Heat shrinkable type suitable for 1.1 KV XLPE under ground cable of size 25-35 sqmm 3.5 core all as directed. Make :Densan/3M
M & L for Straight through joint kit Heat shrinkable type suitable for 1.1 KV XLPE under ground cable of size 50-95 sqmm 3.5 core all as directed. Make :Densan/3M
M & L for Straight through joint kit Heat shrinkable type suitable for 1.1 KV XLPE under ground cable of size 120-185 sqmm 3.5 core all as directed. Make :Densan/3M
Material & Labour for MCCB 63 Amps 16 KA, 4 Pole including dismantling of old one MCCB testing and commissioning complete all as specified and directed by Engineer-in-Charge. Make:- Legrand,Siemens, Schneider
Material & Labour for MCCB 100 Amps 16 KA, 4 Pole including dismentling of old one MCCB testing and commissioning complete all as specified and directed by Engineer-in-Charge. Make:- Legrand,Siemens, Schneider
Material & Labour for MCCB 125 Amps 16 KA, 4 Pole including dismentling of old one MCCB testing and commissioning complete all as specified and directed by Engineer-in-Charge. Make:- Legrand,Siemens, Schneider
Material & Labour for MCCB 160 Amps 16 KA, 4 Pole including dismentling of old one MCCB testing and commissioning complete all as specified and directed by Engineer-in-Charge. Make:- Legrand,Siemens, Schneider
Material & Labour for MCCB 250 Amps 25 KA, 4 Pole including dismentling of old one MCCB testing and commissioning complete all as specified and directed by Engineer-in-Charge. Make:- Legrand,Siemens, Schneider
Supply & fixing MCB TPN 63 amps of 10 KA in existing panel with incoming and outgoing connection complete all as directed. Make:- Legrand,Siemens, Schneider
Supply & fixing MCB TPN 32 amps of 10 KA in existing panel with incoming and outgoing connection complete all as directed.Make:- Legrand,Siemens, Schneider
Supply and fix thermoplastic cable junction boxes IP 65 with metric knockout for cable entry with terminal of size 200 x 160 x 98 mm on pole with MS clamps, nut bolts, washers and glands suitable for 16 sq mm 04 core cable and all as specified and directed . Make- HANSEL,Neptune,Rittal.
M&L for roughing old painting from the LT panels by paint removers, cleaning with scrapes and preparing the surface and applying one coats Painting complete to LT panel with synthetic enameled paint of existing colour and writing work for incoming and outgoing complete all as specified and directed.
Cutting / trimming of tree branches which are touching of street light/ peremeter pole and disposal of branches to nearest dumping area complete all as directed.
Supply and fix 2 core 2.5 sqmm PVC insulated PVC sheathed weather proof multistranded copper conductor cable 1100 volts grade drawn through in GI conduit, pole etc with MS clamps from junction box to street light fitting all as specified and directed.
Supply and fix heat shrinkable straight through cable jointing kit for 11 KV grade cable joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sq mm complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV grade cable for indoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sq mm complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sq mm complete all as specified and directed.
S & F in replacement of danger notice plate of 1.6mm thick mild steel sheet vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with M S Clamps, bolt and nut approved size for HT Panels, 25x20cm size including taking out old unserviceable danger notice plate complete all as specified and directed.
Cutting of vegetation/grasses earth hips etc, cleaning and levelling of cutting areas in various electrical installation areas, surrounding of HT/LT poles complete all as specified and directed.
Material & Labour for Cement concrete in foundation, filling and mass concrete type B2 1:2:4 (40mm graded aggregate) not exceeding 15 cm in deapth for plinth protaction for path including Nesessary excavation, form work and dismantling of old surface complete all as specified and directed.
M & L for PCC cable route indicator in mix of 1:2:4 type B1 of size 450x200x75mm with oval shape and writing the letter HT/LT cable with synthetic enamel paint and embedded with PCC foundation type D2 1:4:8 of size minimum 250 mm depth including necessary earth work complete all as specified and directed.
Supply & fixing MCB TP 32 amps of 10 KA in existing panel with incoming and outgoing connection complete all as directed Make:- Legrand,Siemens, Schneider
S & F 3 phase 440 v operating coil voltage 240 volts,32 Amps Capacitor duty contactor for APFC pannel complete with taking down old unserviceable contactor all as specified.
Material & Labour for replacement of capacitor bank long life 3 phase 440 volts of capacity 10 KVAr and fixing at APFC panel in sub station including necessary copper lead connection of suitable size all as directed.
Material & Labour for replacement of capacitor bank long life 3 phase 440 volts of capacity 5 KVAr and fixing at APFC panel in sub station including necessary copper lead connection of suitable size all as directed.
Supply & fixing for replacement power factor controller relay 8 step 415 Volts, AC,50 Hz to automation to power capacitor including replacement of control wring as required at site including addition/alteration if required.
Supply and fix aluminium lugs for 10 sqmm to 16 sqmm 4 core cable complete all as specified and as directed
Supply and fix aluminium lugs for 25 sqmm to 35 sqmm 4 core cable complete all as specified and as directed
Supply and fix aluminium lugs for 50 sqmm to 70 sqmm 3.5 core cable complete all as specified and as directed
Supply and fix aluminium lugs for 95 sqmm to 120 sqmm 3.5 core cable complete all as specified and as directed
Supply and fix aluminium lugs for 240 sqmm to 300 sqmm 3.5 core cable complete all as specified and as directed
Supply & fixing in replacement Driver for 45 Watts LED street light luminaries complete. Make : CG S0DQL-65-700-45W
Dismantling and Taking out old unserviceable Garden/Pathway Light fittings and Supply, Installation, Testing and Commissioning of Integral LED Ground mounted Bollard 10W, Inverted pyramid tripod led bollard with soft 360 degree light with a system lumen output of 300 lumens and a minimum system efficency of 35 lm/W. The luminaire shall have a rated system lifetime of 25,000 burning hours at L70. The luminare should have a color temperature of 3000K and CRI>75. The luminaire shall meet IP65 & IK10 rating with THD < 20% and PF > 0.9. The luminaire housing should made of pressure die cast aluminium with polycarbonate diffuser. The power consumption should not exceed 10W (including driver). Make:- CG, Philips, Wipro
Dismantling and Taking out old unserviceable street Light fittings and Supply, Installation, Testing and Commissioning of Integral LED street light luminarie 45 Watt die cast aluminium housing designed to act as heat sink for efficient dissipation of heat. Electrochemically brightened and anodized aluminium reflector. Heat resistant toughened glass is provided with die cast aluminium frame. (IK 08) luminarie provided with a mounting bracket for aiming adjustment. Driver is provided with input voltage surge (10kV), open and short circuit protection. system wattage 45 W and power factor 0.90. Make CG LSTP-45-CDL or equivalant in Philips, GE
Dismantling and Taking out old unserviceable flood Light fittings and Supply, Installation, Testing and Commissioning of Integral LED flood light luminarie 50 Watt die cast aluminium housing designed to act as heat sink for efficient dissipation of heat. Elecrochemically brightened and anodized aluminium reflector. Heat resistant toughened glass is provided with die cast aluminium frame. (IK 08) luminarie provided with a mounting bracket for aiming adjustment. Driver is provided with input voltage surge (10kV), open and short circuit protection. system wattage 60 W and power factor 0.90. Make CG LFLE-50-CDL or equivalant in Philips, GE
Dismantling and Taking out old unserviceable flood Light fittings and Supply, Installation, Testing and Commissioning of Integral LED flood light luminarie 135 Watt die cast aluminium housing designed to act as heat sink for efficient dissipation of heat. Elecrochemically brightened and anodized aluminium reflector. Heat resistant toughened glass is provided with die cast aluminium frame. (IK 08) luminarie provided with a mounting bracket for aiming adjustment. Driver is provided with input voltage surge (10kV), open and short circuit protection. system wattage 135 W and power factor 0.90. Make CG LFLN-135-CDL/60 or equivalant in Philips, GE
M & L for switching on and off the street lights based on analog time controlling switch box for automatic controller of street light on 2.0 mm thick sheet metal enclosure consist of 230 Volt Astronomical Time Switch, 40 Amp MCB internally pre wired, terminal blocks mounting brackets, cable glands and openable door with lock and key and manual setting features complete all as specefied and directed. Make Indo Asian Cat No TL040AS0 or Bajaj/Havells/ Crompton.
Dismantling and Taking out old unserviceable time switch and Supply and fix Analog time switch for controll street light 3P module,24 hours program,with battrey back up of 100 hours complete all as specified and as directed. Legrand,L&T,Indo asian
Disconnecting and dismantling & complete overhauling of 11/0.433 KV Transformer capacity up to 315 KVA, after disconnecting of electric supply and earth connections including transportation to work shop, drained out transformer oil, lifting/removing of top cover of transformer & cores with chain pully blocks/crane, cleaning of sludge and washed down with the help of spray of clean oil and re-assembling of transformer with S&F of new gasket set assembly, replacement of nuts, bolts and washers as required, re filling of Transformer oil after centrifuging at satifactory dielectric strength complete after electric connections and testing all as specified and directed.
M&L for Filling of new transformer oil having dielectric strength not less than 60 KV complete including centrifuging of oil (if required) up to getting dielectric strength near 60 KV all as specified and directed.
M&L for replacement of HV copper coil and insulation complete
M&L for replacement of LV copper coil and insulation complete
M&L for reinsulation of existing HV copper coil complete
M&L for reinsulation of existing LV copper coil complete
M&L for insulation of core,bushing,Tap changer and etc
M&L for Ovan Drying complete
Repair/Maintenance and complete over hauling of 11 KV HT VCB’s including disassembling of operating mechanism parts, well cleaning with petrol CRC 226, replacing unserviceable parts and accessories like spring, gasket, coils, nuts, bolts and washers etc, oiling and greasing of moving parts, re-assembling, fine setting of mechanism, well cleaning and de-carbonizing of arc control pot, fixed and moving contact including checking testing, tripping check of HT VCB’s making perfect operational in manual and electric mode including maintenance and well cleaning the complete, replacing unserviceable parts and components etc complete all as directed.
SUPPLY ONLY SPARES FOR SER ITEM NO 64
(a) Digital ammeter flush type 96 sqmm with suitable fixing arrangement for easily fixing in existing LT panel including necessary wiring. Make L&T, Cat No WDS301OCA00, Legrand, Schneider
(b ) Digital voltmeter flush type 96 sqmm with suitable fixing arrangement for easily fixing in existing LT panel including necessary wiring. Make L&T, Cat No WDV303FC000, Legrand, Schneider
(c) Indicator lamp assembly LED type (RYB) in existing LT panel with suitable wiring and volts.
(d) Indicator lamp assembly LED type (RYB) in existing HT panel with suitable wiring and volts.
(e) Spring Bushing for VCB breakar ON and OFF mechanisum in existing VCB panel complete all as specefied and directed.
(f) HRC Fuse of 10 Amps rated capacity suitable for HT VCB Panel complete all as specefied and directed.
(g) Heater suitable for HT VCB Panel complete all as specefied and directed.
(h) Name plate suitable for Incoming and Out going HT VCB Panel complete all as specefied and directed.
Disconnecting/dismantiling/taking down old 33 KV HT VCB control panel any size/capacity and disconnecting of Control cables connection and Shifting from power Old room to New room including necessary New Control Cables, PCC work ,installation,connections,commissioning and testing etc complete all as directed.
Repair/Maintenance and complete over hauling of 33 KV HT VCB control panel any size/capacity, well cleaning and de-carbonizing, including checking testing, tripping check of HT VCB’s making perfect operational in manual and electric mode etc complete all as directed.
Maintenance and complete calibration and setting as per fault level of HT VCB’s relay 33 KV and 11 KV with suitable instrument including T&P etc complete all as directed.
Supply, installation, testing and commissioning of CT 11 KV epoxy type ratio 50/5+5 Amps accuracy Class-I 1 3 .1 K A for 1 sec for CT ratio = 50/5 A (including 50/5 A) single pole (Three core type) fixing on existing 11 KV panel including necessary connections, any modification required, addition/alteration required for fixing CT in existing 11 KV panel complete all as directed by Engineer-in-Charge.
Supply & fixing in replacement of 100 AH, 12V Maintanance free battery including replacement connecting materials such as terminals,lead, thimbles, lugs, nuts, bolts and washers as required at site all as specified and directed. Make:- Exide, Amco.
Matrial and labour for replacement of service cable of PVC insulated, unsheathed aluminium multistranded conductor twin core 4 Sqmm size including dismantling of existing unserviceable cable complete all as directed
Matrial and labour for replacement of service cable of PVC insulated, unsheathed aluminium multistranded conductor twin core 6 Sqmm size including dismantling of existing unserviceable cable complete all as directed
Matrial and labour for replacement of service cable of PVC insulated, unsheathed aluminium multistranded conductor twin core 10 Sqmm size including dismantling of existing unserviceable cable complete all as directed
Chinmaya Enteprises
Paragon Electrotechnics
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .