Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.7 LAccepted-AOC | ₹34.7 L | L1 | Accepted-AOC BEING L-1 BIDDER |
| 2 | L2₹35.8 L+₹1.1 L (3.15%)Rejected-Finance FLAT NO 164 SHAKTISHIKHA GANDHI NAGAR SIGRA VARANASI UP 221003 | VARANASI | VARANASI | UP | 221003 | ₹35.8 L+₹1.1 L (3.15%) | L2 | Rejected-Finance Being Other than L-1 Bidder |
| 3 | Rejected-Technical | - | - | Rejected-Technical Not Recommended as not enlisted in reqd category |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not Recommended as the firm not enlisted in reqd Category |
| 5 | Rejected-Technical | - | - | Rejected-Technical Not Recommended as not enlisted in reqd category |
| Sl No | Description | Qty | Unit | R K Traders L1 | Ray Enterprises L2 |
|---|---|---|---|---|---|
| 1.00 | Supply,Install,Testing and Commissioning of step down 11 KV transformer,level-3,Voltage rating 11KV/0.433 Volts,out door type of capacity 315 KVA,,3 Phase,4 Wire,50 Hz, oil cooled, core type, floor mounted, Delta&star connected maximum losses as defined in vector group DYN 11,Double copper wound ONAN manual type off load tap changing facility on HT side to vary secondary voltage from +/- 7.5 % in steps of 2.5 % continuous rating of capacity 315 KVA incl cable end box on both HT & LT side .The transformer shall be completed with all standard fittings and accessories, guages and including providing first fill transformer oil as per indication level etc and confirming to IS :1180 and fittings and accessories of transformers shall confirm to IS 3639,335-1996 as amended and duly mounted on rollers as per load bearing capacity of transformer and the transformer shall have the following fittings/accessories fitted as per IS and complete all as specified and directed.
(i) HV Primary side consisting of 03 Nos porcelain insulated bushing with brass bushing rods and nuts, bolts and washersand 01 No cable end box as per OEM gauge.
(ii) LV Secondary side consisting of 04 Nos porcelain insulated bushing with brass bushing rods and nuts, bolts and washers and 01 No cable end box as per OEM gauge.
(iii) Rating plate and terminal marking plate of HT/LT sides
(iv) Two earthing terminals for body earthing and two additional for neutral brought out on a bushing
(v) One number Thermometer dail type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature gauge :max reading painted terminal ,(vi) Lifting lugs, (vii) Dehydrating silicagel breather
(viii) oil level indicator with minimum and maximum marking, (ix) Cooling Radiator, (x) Thermometer pocket , (xi) Drain valve with plug or cover plate, (xii) Conservator tank, (xiii) Oil filling hole with cover including funnel, (xiv) Air release device / plug, | 1 | Each | 19,45,000 ₹19,45,000 Lowest | 22,78,000 ₹22,78,000 |
| 1.10(xv) Thermometer 100 mm dia/ stem type with metal guard having maximum temperature indication with resetting devices for transformer, (xvi) winding temperature indicator, (xvii) Air release device for transformer (xviii) First fill of suitable grade tranformer oil confirming to IS and tested upto 60Kv die electric strength Note : 1:- Information plate /Technical data plate as laid down in para 15.2 and 15.3 as per IS. 2:- Including making PCC foundation for transformer of size of 2.5 mtr X 2.5 mtr X 1.30 mtr (below ground level 0.3 mtr and above ground level 01 mtr and incl providing GI cattle fencing up to 1.50 mtr height all-around up to 2.5 mtr width from the transformer foundation corner to fence and suitable GI gate and locking arrangements complete all as directed by Engr-in-Charge. 3:- Exc,RFR,PCC & GI metal fencing with gate items will be measured & paid separately in relavent items (4) Precommissioning test shall be done by SEI in presence of Contractor`s rep. Any defects noticed to be rectified with full satisfaction of SEI & meeting the requirements. All arrangement shall be done by contractor at his own cost. | |||||
| 2.00 | Supply, Install, Testing and Commissioning of 11/12 KV, Load Break Switch (LBS) , 3 Pole, incl providig dropout fuse units assembly with suitable fuses,Rating capacity 630 Amps,50 Hz which confirms to IEC 62271-1 standards Outdoor type in CRCA powder coated steel enclosure, 3 mm thick and the main frame is welded in steel structures fabricated load break switche Panel.The unique arc quenching mechanism makes it capable of breaking normal loads and fault loads.This can be operated on loads up to 1 MVA with epoxy insulators suitable rating, HT three pole busbar of rating 1.5 times capacity of LBS , double switch blades,forged contacts with arc quenching chamber, lagging pin and loop less current path. The nylon/FRP insulaton makes the switch light weight with greater electrical safety and mechanical strength load break switch panel and the contacts are mounted on epoxy insulators and operated the switch is also provided with stored energy tripping device and tripping intiantion by means of fuses rated short circuit making capacity upto 20 KA (RMS) 50 KA (PEAK) and make/break upto 630 Amps and mechanically interlocked earth switch and manually operated mechanical system and incoming and outgoing cable entries with necessarybase foundation in PCC 1:2:4 and the Manufactured shall be CPRI norms followed and drawings/circuit layout approval by Engr-in-Charge | 1 | Each Job | 2,48,000 ₹2,48,000 | 2,30,000 ₹2,30,000 Lowest |
| 3.00 | M&L for galvanised iron metal fencing for 11 KV substation and including providing necessary fabrication work,welding, & drilling work,bending,cutting,nuts,bolts and washers etc for transformer fencing and gate with locking arrangements and necessary galavanised 100mm GI channels of length 2 meters heigh incl errection of channels 1.0 mtr below ground level and 1.5 mtr above ground level with proper foundation and coping two coats of red oxide primer and two coats of anti-corrosive silver paint complete all as specified and directed. | 5 | Per Qtl | 12,500 ₹62,500 | 12,000 ₹60,000 Lowest |
| 4.00 | Supply, laying & testing 11 KV grade cable XLPE/PVC insulated, screened, PVC bedded,galvanized steel strip or wire armoured, electric power cables (heavy duty ) with stranded aluminium conductor,11000 volts (Earthed) grade, of cross sectional area 95 sqmm,3 core complete all as specified and directed.Make:-Havells india Ltd/Polycab wires Pvt Ltd/Gloster cables Ltd
(Note:-(i) Excavation,Earth work,sand cushioning,cable covers and cable protection pipes shall be measured and paid separately.)
(ii) The cable shall be in one length unless otherwise directed by GE. | 20 | RM | 4,000 ₹80,000 Lowest | 4,300 ₹86,000 |
| 5.00 | Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 to 120 sqmm complete all as specified and directed. | 1 | Each | 12,000 ₹12,000 | 8,000 ₹8,000 Lowest |
| 6.00 | Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 to 185 sqmm complete all as specified and directed. | 1 | Each | 9,000 ₹9,000 Lowest | 9,000 ₹9,000 Lowest |
| 7.00 | Supply, install, testing and commissinoning LT panel board outdoor type of size 1400 mm long X1200 mm width X 600mm thickness(depth) with double door type suitable for working on 3 phase ,4 wire ,415 volts, AC ,50Hz, ,cubicle and shall have air ventilation arrangement,IP-54 Protection, floor mounted, free standing, dust and vermin proof, made out of 3.15 mm thick at outer sheet and 2.0 mm thick at internal compartments CRCA sheet and necessary angle/flat irons duly powder coated, hinged doors with rubber gasket, handles.Panel shall have front and rear opening,locking arrangement,cable alleys,cable entry holes for incoming and out going cables busbar chamber and switch gear compartment,see through glass for indicator lamps, control copper wiring & safety fuses,earthing terminals,affix danger notice plate,aluminium busbar fixed on DMC/SMC insulators and all incoming and outgoing internal connection should be connected suitable rating aluminium bus bars only with RYB color code leeves/taps, and the panel will be mounted on 50mmX50mmX6mm GI angle iron base frame of height 45 CM above GL as per site requirement and below GL 45 CM and including connecting up of existing incoming and out going cables by using new aluminium lugs and cable gland and connecting of earth strip and providing civil work/PCC foundation (1:2:4) type B1 with studs,bolts,nuts & washers as per site requirement. And complete all as specified and directed and including comprising of following:- | 1 | Each Job | 3,49,000 ₹3,49,000 Lowest | 4,30,000 ₹4,30,000 |
| 7.10Note:- (i) LT panel board manufactured by any manufacturer should be followed by CPRI norms/certified. (ii)The contractor shall be arranged General (SLD), circuit lay out drawings & Switch gear items makes submitted for prior approval by the Accepting Officer/Engineer -in-charge before procurement/ordering. (i) MCCB 500 Amps,4 pole, 35/36KA, 415 Volts thermal magnetic based-01 Nos I/C incl spreader links of suitable ratings Make:-ABB/ Siemens/Schneider/Havells (ii) MCCB 400 Amps,4 pole, 36KA, 415 Volts thermal magnetic based-01Nos O/G incl spreader links of suitable ratings Make:-ABB/siemens/Schneider/Havells (iii) MCCB 160 Amps,4 pole, 25KA, 415 Volts thermal magnetic based-01 Nos incl spreader links of suitable ratings Make:-ABB/ Siemens/Schneider/Havells (iv) MCCB 100 Amps,4 pole, 16KA, 415 Volts thermal magnetic based-01 Nos and 01 X spare compartments for MCCB incl spreader links of suitable ratings Make:-ABB/ Siemens/Schneider/Havells (v) MCCB 63 Amps,4 pole, 16KA, 415 Volts thermal magnetic based-01 Nos 01 X spare compartments for MCCB incl spreader links of suitable ratingsMake:-ABB/ Siemens/Schneider/Havells (vi) MCB 32 Amps,SPN, 10KA, 240 Volts thermal magnetic based-03 Nos Make:-ABB/ Siemens/Schneider/Havells (vii) R,Y,B Phase indicating lamp -01 Set Make:- Jigo/L&T (viii) Digital Ammeter (0 amps to 500 Amps) selector switch -01 No.Make:-AE/Selec (ix) Ammeter Selector switch -01 No.Make:-AE/Kaycee (x) 400/5A current transformer -03 No's Make:-Kappa (xi) Digital Voltmeter( 0Volts to 500Volts)-01 No with ASS, Make:-AE/Kaycee (xii) Volmeter selector switch -01 No with VSS Make:-AE /Kaycee (xiii) Protection fuses& controll wiring -03 Nos Make:-Nippon (xiv) Busbar aluminium TPN 800 amps rating suitable size -01 Set ( 04 Nos) | |||||
| 8.00 | M&L for danger notice plate of size 250 x 250mm and 1.6 mm thick galvanised steel plate,vitreous enammelled white, with letters,figures and conventional skull and bones in signal red colour and fixed with GI clamps,bolts and nuts of above size, for HT, 11000 volts grade complete all as specified and directed | 1 | Each | 150 ₹150 Lowest | 1,300 ₹1,300 |
Tender Value
Refer Docs
EMD Value
₹68,000
Closing Date
24 Jul 2026, 6:00 pmClosed
GARRISION ENGINEER I GOS
GARRISON ENGINEER I GOPALPUR MILITARY STATION PO GOLABANDHA DIST GANJAM ODISHA 761052
PROVN OF INFRA FOR INSTALLATION OF 240 KW ELECTRIC FAST CHARGING STATION ALONGWITH CONNECTED FITTINGS FOR ELECTRIC VEHS AT AAD CENTRE UNDER GE (I) GOS
2026_MES_774190_1
GE/GOS/TOK/67 OF 2026-27
Open Tender
Civil Works
Item Rate
180 days
GOS
AS PER TENDER DOCUMENTS
6 documents required · 6 mandatory
₹500
GARRISION ENGINEER I GOS
₹68,000
22 Sept 2026
23 Jun 2026
30 Jul 2026
23 Jun 2026
24 Jul 2026
10 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1E/M | |||||
| 2 | Supply,Install,Testing and Commissioning of step down 11 KV transformer,level-3,Voltage rating 11KV/0.433 Volts,out door type of capacity 315 KVA,,3 Phase,4 Wire,50 Hz, oil cooled, core type, floor mounted, Delta&star connected maximum losses as defined in vector group DYN 11,Double copper wound ONAN manual type off load tap changing facility on HT side to vary secondary voltage from +/- 7.5 % in steps of 2.5 % continuous rating of capacity 315 KVA incl cable end box on both HT & LT side .The transformer shall be completed with all standard fittings and accessories, guages and including providing first fill transformer oil as per indication level etc and confirming to IS :1180 and fittings and accessories of transformers shall confirm to IS 3639,335-1996 as amended and duly mounted on rollers as per load bearing capacity of transformer and the transformer shall have the following fittings/accessories fitted as per IS and complete all as specified and directed. | 1 | Each | - | - |
| 2.01 | (i) HV Primary side consisting of 03 Nos porcelain insulated bushing with brass bushing rods and nuts, bolts and washersand 01 No cable end box as per OEM gauge.
(ii) LV Secondary side consisting of 04 Nos porcelain insulated bushing with brass bushing rods and nuts, bolts and washers and 01 No cable end box as per OEM gauge.
(iii) Rating plate and terminal marking plate of HT/LT sides
(iv) Two earthing terminals for body earthing and two additional for neutral brought out on a bushing
(v) One number Thermometer dail type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature gauge :max reading painted terminal ,(vi) Lifting lugs, (vii) Dehydrating silicagel breather
(viii) oil level indicator with minimum and maximum marking, (ix) Cooling Radiator, (x) Thermometer pocket , (xi) Drain valve with plug or cover plate, (xii) Conservator tank, (xiii) Oil filling hole with cover including funnel, (xiv) Air release device / plug, (xv) Thermometer 100 mm dia/ stem type with metal guard having maximum temperature indication with resetting devices for transformer, (xvi) winding temperature indicator, (xvii) Air release device for transformer, (xviii) First fill of suitable grade tranformer oil confirming to IS and tested upto 60Kv die electric strength | - | - | - | - |
| 3 | Supply, install, testing and commissinoning LT panel board outdoor type of size 1400 mm long X1200 mm width X 600mm thickness(depth) with double door type suitable for working on 3 phase ,4 wire ,415 volts, AC ,50Hz, ,cubicle and shall have air ventilation arrangement,IP-54 Protection, floor mounted, free standing, dust and vermin proof, made out of 3.15 mm thick at outer sheet and 2.0 mm thick at internal compartments CRCA sheet and necessary angle/flat irons duly powder coated, hinged doors with rubber gasket, handles.Panel shall have front and rear opening,locking arrangement,cable alleys,cable entry holes for incoming and out going cables busbar chamber and switch gear compartment,see through glass for indicator lamps, control copper wiring & safety fuses,earthing terminals,affix danger notice plate,aluminium busbar fixed on DMC/SMC insulators and all incoming and outgoing internal connection should be connected suitable rating aluminium bus bars only with RYB color code leeves/taps, and the panel will be mounted on 50mmX50mmX6mm GI angle iron base frame of height 45 CM above GL as per site requirement and below GL 45 CM and including connecting up of existing incoming and out going cables by using new aluminium lugs and cable gland and connecting of earth strip and providing civil work/PCC foundation (1:2:4) type B1 with studs,bolts,nuts & washers as per site requirement. And complete all as specified and directed and including comprising of following:- | 1 | Each Job | - | - |
| 4 | M&L for galvanised iron metal fencing for 11 KV substation and including providing necessary fabrication work,welding, & drilling work,bending,cutting,nuts,bolts and washers etc for transformer fencing and gate with locking arrangements and necessary galavanised 100mm GI channels of length 2 meters heigh incl errection of channels 1.0 mtr below ground level and 1.5 mtr above ground level with proper foundation and coping two coats of red oxide primer and two coats of anti-corrosive silver paint complete all as specified and directed. | 5 | Per Qtl | - | - |
| 5 | Supply, laying & testing 11 KV grade cable XLPE/PVC insulated, screened, PVC bedded,galvanized steel strip or wire armoured, electric power cables (heavy duty ) with stranded aluminium conductor,11000 volts (Earthed) grade, of cross sectional area 95 sqmm,3 core complete all as specified and directed.Make:-Havells india Ltd/Polycab wires Pvt Ltd/Gloster cables Ltd
(Note:-(i) Excavation,Earth work,sand cushioning,cable covers and cable protection pipes shall be measured and paid separately.)
(ii) The cable shall be in one length unless otherwise directed by GE. | 20 | RM | - | - |
| 6 | Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 to 120 sqmm complete all as specified and directed.Make: Raychem/M-Seal/Denson | 1 | Each | - | - |
| 7 | Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 to 185 sqmm complete all as specified and directed.Make: Raychem/M-Seal/Denson | 1 | Each | - | - |
| 8 | Supply, install, testing and commissinoning LT panel board outdoor type of size 1400 mm long X1200 mm width X 600mm thickness(depth) with double door type suitable for working on 3 phase ,4 wire ,415 volts, AC ,50Hz, ,cubicle and shall have air ventilation arrangement,IP-54 Protection, floor mounted, free standing, dust and vermin proof, made out of 3.15 mm thick at outer sheet and 2.0 mm thick at internal compartments CRCA sheet and necessary angle/flat irons duly powder coated, hinged doors with rubber gasket, handles.Panel shall have front and rear opening,locking arrangement,cable alleys,cable entry holes for incoming and out going cables busbar chamber and switch gear compartment,see through glass for indicator lamps, control copper wiring & safety fuses,earthing terminals,affix danger notice plate,aluminium busbar fixed on DMC/SMC insulators and all incoming and outgoing internal connection should be connected suitable rating aluminium bus bars only with RYB color code leeves/taps, and the panel will be mounted on 50mmX50mmX6mm GI angle iron base frame of height 45 CM above GL as per site requirement and below GL 45 CM and including connecting up of existing incoming and out going cables by using new aluminium lugs and cable gland and connecting of earth strip and providing civil work/PCC foundation (1:2:4) type B1 with studs,bolts,nuts & washers as per site requirement. And complete all as specified and directed and including comprising of following:- | 1 | Each Job | - | - |
| 9 | M&L for danger notice plate of size 250 x 250mm and 1.6 mm thick galvanised steel plate,vitreous enammelled white, with letters,figures and conventional skull and bones in signal red colour and fixed with GI clamps,bolts and nuts of above size, for HT, 11000 volts grade complete all as specified and directed | 1 | Each | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.44 MB
tender_docs.pdf
Tender Documents • 1.12 MB
BOQ_867054.xls
BOQ • 2.31 MB
Corr_3_67_R.pdf
PDF • 0.38 MB
corrigendum.pdf
PDF • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .