| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.0 CrAccepted-AOC JAMMU AND KASHMIR JAMMU AND KASHMIR | JAMMU | JAMMU AND KASHMIR | 181122 | ₹1.0 Cr | L1 | Accepted-AOC LOWEST BIDDER |
| 2 | L2₹1.1 Cr+₹2.9 L (2.83%)Rejected-Finance | ₹1.1 Cr+₹2.9 L (2.83%) | L2 | Rejected-Finance BEING NOT LOWEST BIDDER |
| 3 | L3₹1.1 Cr+₹8.8 L (8.56%)Rejected-Finance 24 A RAGHBIR MARG NEAR 22 NO PHATAK PATIALA 147001 PB | PATIALA | PATIALA | PUNJAB | 147001 | ₹1.1 Cr+₹8.8 L (8.56%) | L3 | Rejected-Finance BEING NOT LOWEST BIDDER |
| 4 | L4₹1.2 Cr+₹15.7 L (15.3%)Rejected-Finance 1630 SECTOR 7C CHANDIGARH 160019 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160019 | ₹1.2 Cr+₹15.7 L (15.3%) | L4 | Rejected-Finance BEING NOT LOWEST BIDDER |
| 5 | L5₹1.2 Cr+₹16.6 L (16.2%)Rejected-Finance 135 CHAKRANA TIWARI CHAKA NAINI PRAYAGRAJ 211008 UTTAR PRADESH | PRAYAGRAJ | UTTAR PRADESH | 211008 | ₹1.2 Cr+₹16.6 L (16.2%) | L5 | Rejected-Finance BEING NOT LOWEST BIDDER |
Tender Value
₹1.1 Cr
EMD Value
₹1.8 L
Closing Date
12 Apr 2025, 6:00 pmClosed
Col Neelima CWE
Military Engineer Services, Commander Works Engineer, Udhampur, PO - Garhi, Udhampur-182121
SPL REPAIRS REPLACEMENT OF ELECTRICAL INFRASTRUCTURE AT ASHOK VIHAR FEEDER AND DEPENDENT UNIT AND PROVN OF 33KV RING MAIN SYSTEM AT MULTI-STORY MODERN HOSPITAL COMPLEX UNDER GE (UTILITIES) UDHAMPUR
2025_MES_700724_1
CWE/U(U)-88/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
210 days
UDHAMPUR
AS PER NIT
6 documents required · 6 mandatory
₹1,000
GE(UTILITIES) UDHAMPUR
₹1.8 L
28 May 2025
8 Mar 2025
19 Apr 2025
8 Mar 2025
12 Apr 2025
30 Mar 2025
Amount
Excavating in trenches, n exc 1.5 m wide and n.exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, and for laying of cable or pipes etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any type of soil, complete all as specified and as directed.
Description all as above but depth exceeding 1.5 mtr but not exceeding 3.0 mtr complete all as specified & directed.
Returning, filling in (soil) including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick in any type of soil, complete all as specified and as directed.
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point, complete all as specified and as directed.
Dry coarse sand as cushioning to under ground cable provided with layer of 8 cms deep before laying the cable and 15 cms deep after laying and stretching the cable, punned to 18 cm thick complete all as specified and as directed. NOTE Only punned thickness shall be measured for payment purpose.
Precast in reinforced Concrete cable covers Class HV, type B-1 flat of size 300mm x 180mm x 40 mm for HT cable, complete all as specified and as directed.
Supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 33000 volts grade, of size 3 core 300 sq mm, complete all as specified and directed.
Supply,installation,testing & commissioning of 33 KV Outdoor type Non-Extensible floor mounted Gas Insulated Switchgear with internal copper bus bars, consisting of with 3 nos motorised Vacuum Circuit Breaker as 2 INCOMER & 1 OUTGOING. All live parts, bus bars,VCBs connections, ON-OFF offload switch, Earth switch of of feeder should be enclosed in one tank sealed for life robotically welded non magnetic and non ferrite grade stainless steel tank Grade 304 of minimum 2 mm thick having IP67 degree of protection filled with SF6 gas as insulation with leakage rate less than 0.1% per year tested as per IEC 62271-200.The unit shall have front cable entry for ease of installation and shall have site replaceable bushings for ease of troubleshooting during breakdown.The Gas Insulated switchgear should be complete with all accessories such as Terminal kits suitable for 1Cx300sqmm Cable, VPIS, cable supports, all front cable terminations, mechanical indications for VCB, OFF load switch & Earth switch , Manometer as per with IEC standards 62271-1, 100, 200. Altitude of installation up to 1000m as per IEC 60120.Cable termination Kit must be screen seperable touchproof type.The unit shall include the following with all necessary standard fitting required at site.License partnar / Authorized Integrators are not accepted. Complete commissioning must be supervised by OEM only.
Cont..... item No 8.00:- VACUM CIRCUIT BREAKER feeder 630A VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity-1 Nos. Motor operated 630 A Vacuum circuit breaker having spring stored mechanism. ON-OFF off load switch and earthing switch downstream vacuum circuit-breaker. Menometer per tank per feeder. “Live Cable” LED Indicators through Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 25KA/ 3 sec Making Capacity - 62.5KA VCB must confirm operating sequence O-0.3sec-CO-3Min-CO and 10000 mechanical operation. Power frequency withstand voltage - 70KV & Impulse withstand voltage - 170KV Minimum operating gas pressure - 1.2 Bar abs. Front cover mechanism - IP2X and VPIS to be given. Green(ON)/Red(OFF) push buttons to operate VCB. Indication Lamp for ON, OFF, TCS, TRIP, SPRING CHARGE etc. Auxiliary powered numerical protection relay having Over Current, erath fault protection. Auxiliary relays are required for Transformer feeder for OTI, WTI, BUCHLOZ Alarm & Trip.
Cont..... item No 8.00:- Sutable Ammeter with ASS and Multifunction meter 6/8 window Annunciator with Hooter scheme. RMU Gas Tank and cable chamber should be tested for an internal arc fault of 25kA for 1 sec with AFLR classification Resin cast ring core CT on cables 50/1-1A, Class: 0.5 & 5P10 , 2.5 VA - 3 Nos Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. RMU, VCB, Vaccum Interrupter must be of same make. Interlock to be provided between 2 nos Incomer so that only one Incomer can be made ON at a time. Mechanical Interlock to be provided for followings: - Earthswitch can be operated in CB OFF codition. - Earthswitch Can not be operated when Cable is Chared.
Cont..... item No 8.00:- One Bus Connected equipment / metering cubical consisting of following 3 nos. Single Phase PTs - 33kV/V3/110/V3 ,Cl-0.5 & 3 P ,50VA 1 Nos Single Phase Auxiliary PT- 33kV/V3/230V, 500 VA Space Heater with thermostat Sutable Analog Voltmeter with VSS. Bus Under Voltage & Over Voltage Relay- 1Nos. 2X12V, 26AH Battary with 7 Amps Charger - 1set
PCC 1:3:6 type C-1 (using 20 mm graded stone aggregate for sub base) for foundation of RMU and PCC 1:4:8 type B-0 (using 12.5 mm grade stone aggregrate in foundation for mass concrate) of Size 2mtr X 2mtr X 0.70 Mtr including necessary form work and finishing the surface of PCC above ground level with cement mortar 1:4, 5mm thick complete all as specified and directed. Note: Size & Shape of Plinth will be change as per OEM recommendation.
HT gang operated air break switch 33 KV, 3 pole horizontaly mounted type, mechanically operated, mounted on insulators and steel frame with operating mechanism, worked from ground level for current rating 200 Amps switch having 100 MVA rating at 33 KV and 9 insulators suitable for 33 KV, 50 C/s including mounting on steel structure and necessary electrical connections and including Gl pipe handle, clamps bolls, nuts, jumper wire connecting with stranded conductors with locking arrangement, complete all as specified and as directed.
Plain cement concrete (1:4:8) type D2 using 40mm graded stone aggregate as in foudation, filling, sub base and mass concrete all as specified and as directed.
PCC 1:2:4 (nominal mix) type B-2, using 40 mm graded crushed stone aggregate as in coping and the like including weathering, slightly rounded or chemfered angles and throating including necessary from work and finishing the exposed surfaces in cement mortar 1:4, 5mm thick, complete all as specified and as directed.
Earthing with GI earth plate electrode 600 X 600 X 6.3mm buried directly in ground (earth pit not less than 2.25M deep below ground level ) with top edge of the earth plate not less than 1.5M below ground level connected to GI strip 32 x 4 mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate NO 3 of SSR1996 part 1 ,including necessary excavation and earth work in any strata of soil,comman salt, charcoal dust, 40 mm dia light grade GI pipe for protection to earth lead, GI water pipe 20mm dia with funnel &wire mesh , PCC pit with CI cover and frame etc all as specified and directed by Engineer-in-charge. Note:- All the joints shall be made with welding to get proper conductivity. Note: On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge
Mild Steel work as in heavy sizes such as trusses built up gates, door frames, record racks, roof work gates etc wrought to required form including holes rivetting or welding where necessary and also fixing in proper position and alignment including supply of steel bolts nuts, wastage etc. and their fixing required for proper completion of the work, complete all as specified and as directed.
Supply and fixing cable jointing kit for 33 KV (Earthed) grade cable for End joint Heat shrinkable type joint complete with jointing material and acessories suitable for 3 core XLPE armoured aluminium conductor cable 240-400 sq.mm, complete all as specified and as directed.
Supply and fix HT overhead lines on 11 meter steel poles with XLPE insulated AB cable 3-core X 95 sq mm + 1 x 70 sq mm.11 KV including clamp, nuts alongwith complete accessories all as specified and directed.
Supply and Fixing Steel tubular swaged pole erected to truly vertical or planted as strut complete with 6 mm thick MS Base plate,welded to pole,finial taper cap, bolts, nuts, screws,11 Mtr long, type 410 SP - 55,including drilling of holes of required size for fixing of cross arms,painting the exposed surfaces of pole with two coats of aluminium paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint on the portion embedded in concrete, and marking pole no. with black paint at suitable height all as specified and directed by Engineer-in-Charge.Note:- The earthwork, PCC foundation, steel clamps, MS Cross arms & bracing of angle iron etc will be measured and paid separately under relevant items.
Supply and Fix cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint , complete all as specified and as directed.
Blank
Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 m below normal ground level, connected to and including 4mm dia galvanized iron wire lead by means of bolts, nuts, check nuts and washers of galvanized standard iron or steel all as specified or indicated in electrical plate No 3 of MES Part-I, including testing on completion including the material and labour and taking out old unserviceable earthing of the following :- (a) Excavation and earth work for drilling hole for electrode in any type of soil. (b) PCC pit in cement concrete 1:2:4 type B-1. (c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm. (d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified.
Srl item No 20 Contd … (e) 15 mm nominal bore light grade GI protection pipe 7.5 mtr long for protection of earthing lead from mechanical injury or tempering. (f) Requisite quantity of common salt and charcoal. (g) Testing of earthing. Note : On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size120-185 sqmm complete, all as specified and directed.
Supply, installation, testing & commissioning of Indoor (IP54) 11kV 630Amps 21KA/3 sec. One side Extensible Ring Main Unit Compact switchgear consisting of 2 Nos. Fixed motorized Vacuum Circuit Breaker Module and 2 Nos. fixed morotized Load break switch module and Copper Busbar in SF6 insulated stainless steel enclosure (2.5mm thick, SS304 grade), (comprising 2Nos incomming VCB & 2 Nos outgoing SF6 in such a manner all are having interconnecting arrangement. The complete RMU must be type tested for Internal arc 21KA for 1 sec with AFLR Classification for Gas tank & Cable Chamber. HT RMU shall preferably have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works. The Vaccum Interrupter must RMU manufacturer's own make. Make of RMU shall be limited to : Siemens Limited/Schneider Electric Infrastructure Limited/ABB India Limited. [Channel partner / System Integrator / Authourized Partner/ License partner make RMU shall not be accepted.The complete RMU shall be consisting of followings:
Srl item No 22 Contd … Microprocessor based IDMT Relay for Circuit Breakers - Self Powered along with series trip coil (Modbus RS485 complaint) for each VCB Module. Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder. SF6 Gas pressure indicator on the gas tank. Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO.and suitable for 10000 mechanical operation. CT shall be minimum 100-50/1A ,2.5VA , 5P20 - 3 nos. for protection. CT shall be minimum 100-50/1A ,2.5VA , Class 0.5 - 3 nos. for metering. Manometer for each Tank. Right angle boot to be provided in each module. 2X12V, 26AH Battary with Charger - 1 Set
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 150 sq mm complete all as directed.
Blank
S&F double walled corrugated (DWC) pipe of size 200 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of HT cable in under ground complete all as spd and directed. Make: REX/Tirupati Plastomatics Pvt Ltd
Supplying, Installation, Testing & Commissioning Outdoor type panels shall be constructed from CRCA sheet of 2 mm thickness, floor mounted metal enclosed, 11 KV VCB panel, totally enclosed and fully interlocked, horizontal draw out, horizontal isolation type breaker as per IEC-62271-1,100,200, as amended up to date and additional Specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and manually closing breaker suitable for use on 11 KV, 3 phase, 50 Hz A.C. supply with short circuit fault level of 25kA for 3 sec compete with self contained, fully interlocked, rack in and rack out mechanism, air insulated, sleeved copper bus bars of 630 amps capacity, breaker featured with mechanical ON/ OFF indicator with hand trip coil and auxiliary switch and equipped with following switchgears and accessories. Make of Vacuum interrupter, circuit breaker, relays shall be same make. Cable compartment suitable for 2RX3C x 240 sq. mm XLPE 11 KV cable (Cable entry from bottom) end termination with heat shrinkable jointing material etc as reqd. The basic insulation level of entire panel shall be 28KV(RMS) / 75KV(Peak). Make of Panel shall be limited to Siemens Limited/ Schneider Electric infrastructure limited/ ABB India limited/ BHEL, (Channel Partner/ System integrator/Authourized partner / Licence Partner make shall not be accepted.)
Srl item No 26 Contd … f) Dual core /single core;separate sets, dual ratio 3 Nos. CTs 400/1 A of 5 VA burden and accuracy class 0.5 for metering and class 5P10 for protection comply with IS 2705 - 1 Set. g) Trip super vision Relay - 1 Nos. h) R,Y,B ON, OFF, Trip Indication with Control MCB - 1 Set. i) Annunciator -8 Window- 1Set . j)Power panel pack with 220 Volt AC input & 110V Volt DC continuous output suitable for closing / tripping / indication etc.
Supply and fix Air break gang operated switches Horizontal/Vertical type 09 instulators type with drop out fuses assembly mounted on MS Channel with operating mechanism works from ground level suitable for 11000 volts, 400 Amps, including Gl pipe handle, clamps bolls, nuts, jumper wire connecting with stranded conductors with locking arrangement, complete all as specified and as directed.
M/s Trade Linker Associates (BID ID -3276991)
MAHESH KUMAR SINGLA CONTRACTOR (BID ID -3277134)
SAGGI ELECTRIC COMPANY (BID ID -3274087)
vijay builders (BID ID -3276961)
PROACH ASSOCIATES BUILDERS & ENGINEERS (BID ID -3276222)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .