Office of the Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
Renovation of Kanyapur MLW Centre, Electrical works including Air Conditioning System---- Supply and installation of A.C (IVRF) system for Auditorium
2017_WBPWD_99623_1
WBPWD/SEWEC/BED /NIQ-87/2016-17 (2nd Call)
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Kanyapur
Please refer Tender documents.
4 documents required · 4 mandatory
₹60,000
Yes
5 Aug 2025
27 Jan 2017
7 Feb 2017
27 Jan 2017
6 Feb 2017
27 Jan 2017
Amount
Supply of Air Cooled Inverter technology Scroll Unit (IVRF-B) each comprising of at least one variable speed inverter controlled compressor, air cooled condenser with protective coated fins, mounting frame, micro processor panel and other standard accessories as per specification. The unit shall be suitable for operation with R-410A refrigerant. Minimum capacity of outdoor unit are as follows.(make Bluestar/Mitsubishi/ O- General)
Supply of variable refrigerant flow Large Cassettes units comprising of coil section, filter section. The unit shall be ceiling suspended /Wall mounted type and complete with all standard accessories as follows.
Supply of variable refrigerant flow High wall Split unit comprising of coil section, filter section. The unit shall be ceiling suspended /Wall mounted type and complete with all standard accessories as follows.
Cordless Remote Control for Indoor Unit
Receiver Kit for Remotes
Supply, installation, testing and commissioning of the following sizes Cu. refrigerant pipes including all fittings e.g sockets, elbows duly insulated with 19mm/13mm close cell elastomeric nitrite rubber insulation between each set of outdoor and indoor units (VRF).
41.3mm outer dia with 19 mm thick insulation
34.9mm outer dia with 19 mm thick insulation
28.6mm outer dia with 19 mm thick insulation.
25.1mm outer dia with 19 mm thick insulation.
22.2mm outer dia with 13 mm thick insulation.
19.1mm outer dia with 13 mm thick insulation.
15.9mm outer dia with 13 mm thick insulation.
12.7mm outer dia with 13 mm thick insulation.
9.5mm outer dia with 13 mm thick insulation.
6.4mm outer dia with 13 mm thick insulation.
Supply, erection, testing & commissioning of refrigerant distribution joints complete with insulation per set for taking branches between outdoor and various indoor units as required
Supply, installation, testing and commissioning of PVC pipe medium class (For drainage of water from IDU) with 9 mm thick Nitrile Rubber insulation.
Providing and fixing of M.S. angle iron frame work ( 75x50, 65x40 ) with 65x50mm MS flat strip for outdoor unit's platform and railing
M.S. angle with platform for ODU's
Supply, erection, testing & commissioning of communication cabling between outdoor and indoor units as per OEM Specification. Cabling shall be bundled properly and shall be neatly aligned with the refrigerant piping. Cabling shall be well supported at specific intervals with anchor fasteners
Installation, testing and commissioning of the following VRF outdoor units with R410A refrigerant, controls, electricals, necessary accessories of minimum capacity
22 HP OUTDOOR UNIT
12 HP OUTDOOR UNIT
Installation, testing and commissioning of the following VRF indoor units with refrigerant, controls, electricals, necessary accessories etc of following type
3.2 TR large Cassettes unit
2 TR High wall Split unit
Lifting & shifting of machines & minor civil work of wall cutting for pipe routing etc
Necessary Scaffolding arrangement for external work of the building
Add Service Tax as applicable
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .