Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.0 LAccepted-AOC NEAR SVN UNIVERSITY NARSINGHPUR ROAD SIRONJA SAUGOR MP 470228 | SAUGOR | SAGAR | MP | 470228 | ₹21.0 L Quoted ₹21.5 L | L1 | Accepted-AOC ELIGIBLE |
| 2 | L2₹21.8 L+₹30,174 (1.41%)Rejected-AOC 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | ₹21.8 L+₹30,174 (1.41%) | L2 | Rejected-AOC ELIGIBLE |
| 3 | L3₹24.0 L+₹2.5 L (11.7%)Rejected-AOC C 40 BHAGAT SINGH NAGAR BHIND ROAD GWALIOR MP 474005 | NA | NA | 474005 | ₹24.0 L+₹2.5 L (11.7%) | L3 | Rejected-AOC ELIGIBLE |
Tender Value
₹22 L
EMD Value
₹44,000
Closing Date
17 Jul 2023, 6:00 pmClosed
CWE AF NAGPUR
HQ CWE AF NAGPUR VAYUSENA NAGAR, NAGPUR 440007 MILITARY ENGINEER SERVICES
SPECIAL REPAIR OF RMU TO VCB TRIPPING SYSTEM AT SUBSTATION NO 4 AT VSN NAGPUR
2023_MES_602924_1
80576
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF Nagpur
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF NAGPUR
₹44,000
23 Aug 2023
13 Jun 2023
24 Jul 2023
13 Jun 2023
17 Jul 2023
3 Jul 2023
Amount
Supply, laying and testing HT UG cable XLPE insulated, screened, PVC bedded, galvanized wire armoured, electric power cables (heavy duty) 11000 Volts grade (Earthed) with stranded aluminium conductor of size 120 sq mm 3 core complete all as specified and directed. Make : POLYCAB/HAVELLS/GLOSTER
Supply, laying and testing HT UG cable XLPE insulated, screened, PVC bedded, galvanized wire armoured, electric power cables (heavy duty) 11000 Volts grade (Earthed) with stranded aluminium conductor of size 185 sq mm 3 core complete all as specified and directed. Make : POLYCAB/HAVELLS/GLOSTER
Excavation in trenches not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for laying of cables and getting out in hard/dense soil complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, with excavated soil in trenches after the cables have been laid and tested complete all as specified and directed.
Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed .
Supplying and laying un-reinforced precast concrete cable cover, class HV, Type 1, flat, size 300mm x 180mm x 40mm complete all as specified and directed
Supply and lay dry river sand below and around cable in trenches as in cable cushioning to cables complete all as specified and directed. Note : Punned thickness only shall be measured
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm all as directed. Make : 3M/Dension
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 120 Sqmm to 185 sqmm all as directed. Make : 3M/Dension
Material & labour for earthing complete with galvanised steel plate earth electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25 meter below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to GI strip of size 25 x 4mm at two points by means of bolts and nut, check nut and washers including charcoal dust, common salt, necessary excavation in any type of soil, returning filling in and removal of surplus soil to a distance up to 50metres, PCC pit in 1:3:6 type C1 (using 20mm grade stone aggregate) RCC 1:2:4 type B-1 (using 20mm grade stone aggregate ) 50mm thick pit cover, reinforced with 8mm dia TMT bars 75mm c/c, both ways MS handle 12mm dia, GI funnel, wire mesh and GI watering pipe of 20mm bore (medium grade) and earth lead protection pipe 40mm bore (light grade) all as specified, directed and shown in electrical plate No 3 of SSR Part-I including testing complete all as specified and directed. Note : GI strip and protection pipes 40 mm GI light grade up to 7.5 metre is included in unit rate.
Supply, installation, testing and commissioning 11 KV, 630 Amps, 21 KA Motor Operated compact outdoor both side extensible Non drawout type +CCVVV+( 2 Nos Load Break Switch (OD)) Incomer with Castle Key interlock (In such a way that only one should operate at a time both electrical and mechanical ) and 3 Nos compact switch gear Ring Main unit Main Copper Bus bar SF6 Insulation are inside SF6 Gas tank, Nominal operating gas pressure 1.4 Bar abs, Extensible type, having 02 Nos Load Break Switches at Incoming and 03 Nos fixed type motor operated Vacuum Circuit Breaker (VL) outgoing) SAFEPLUS compact gas insulated Ring Main Unit. All live parts enclosed in a robotically welded stainless steel tank of IP-67 class of protection. with battery and Battery charger, 5 way with IP class as IP 67, for outer door separately, inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X along with bottom cable entry and front cable termination complete all as specified and as directed with following accessories & specification RMU switchgear shall be capable of withstanding the specified currents without damage in accordance with the latest versions of IEC 60694 specified including metering module complete. Make : CG/ABB/siemens/Schnieder
(A) (i) 630A manual Load Break Switch module for making of fault current along with Earth Switch of full making capacity - 2 Nos. (ii) Short time withstand current - 21KA/ 3 sec (iii) Making Capacity - 50 KA Peak at rated voltage (iv) Auxiliary contacts - 1NO + 1NC (v) Power frequency withstand voltage - 28kVrms (vi) Impulse withstand voltage - 75Kvpeak (vii) Front cover mechanism - IP2X (viii) Cable covers - 3X (ix) Snap action mechanism for manual operation (x) Cable box for front termination of the cable suitable up to 3 core 300 Sqmm, 11 KV XLPE cable (xi) Right angle non-touch proof Termination boots - 1 Set (R,Y,B) (xii) Set of 03 Nos. Ring Core Metering CTs 40-80/1A as per feeder load, 2.5VA, Class 1.0 The degree of protection required against prevailing environmental conditions, including splashing water and dust, shall be not less than IP 54 as per IS12063
(B) (i) 630A Motor operated VCB module for making & breaking of fault current along with Earth Switch of full making capacity -3 No Motor operated 630 A Vacuum circuit breaker having spring stored mechanism. (ii)Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. (iii) Short time breaking current - 21KA/ 3 sec (iv) Making Capacity - 50 KApeak at rated Voltage (v) Auxiliary contacts - 1NO + 1NC (vi) Power frequency withstand voltage to Earth between Poles & Across opening span - 28KVrms (vii) Impulse withstand voltage Phase to Phase & Phase to Earth - 75kVp (viii) Front cover mechanism - IP2X (ix) Cable covers - 3X (x) Green(ON)/Red(OFF) push buttons to operate VCB. LED indicator for ON, OFF etc. (xi) 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. Provision of Power Pack of suitable specification. (xii) Mechanical ON/OFF/EARTH/Spring charge Indication (xiii) Cable boxes should be Arc Proof interlocked with respective Earthing Switches. (xiv) Right angle non-touch proof Termination boots - 1 Set (R,Y,B) The degree of protection required against prevailing environmental conditions, including splashing water and dust, shall be not less than IP 54 as per IS12063
Min no. of operations of Circuit breakers at rated current (as per IEC 62271-100) shall be guaranteed with Mechanical Endurance – Class M1 (2000 operations). Stored energy mech. for manual operation - 01 No Set of 03nos. Ring Core Protection CTs of ratio 40-80A/1A as per feeder load, 2.5VA, 10P10 - 01 Set Capacitive voltage indication fixed type VPIS 6-12 kV - 01 No - R-Y-B Phase Indication Set of Coupling bus bars along with suitable coupling kit.- 01 No Manometer- 01 No Operating handle - 01 No Material: Epoxy resin cast/ Tape wound - Burden: 2.5VA - Ratio: 200-100-50 /1A. Potential Transformer 11 KV/R3/110/R3/-ACC Class -1 50 VA - Accuracy Class:0.5
NOTES (a) RMU Tank shall be IAC AFL 20kA/1s tested to ensure utmost operator safety. Test report (from an STL member Lab) shall be submitted along with drawings of the RMUs. In case the test report is not found suitable, the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU tank shall be of 304 grade, Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (e) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (f) Bus bar to be copper material. (g) Insulation of bus bar to be epoxy or PVC Sleeved insulation to be provided. (h) The Quoted rate for RMU shall be inclusive of making Platform as per OEM instructions, made with bricks and necessary PCC at Bottom and Top and plastering complete all as directed. (j) Metering Module including power pack/battery with battery charging unit.
Dismantling/Taking down carefully existing old HT cable of any size complete all as specified.
Note : The amount against Schedule of Credit on Page No. 25 shall be deducted from the total amount quoted against Sch 'A' while deriving Contract Sum for Acceptance.
Paragon Electrotechnics
SHRI HARI CONSTRUCTION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .