Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.6 LAdmitted-Finance | ₹9.6 L | L1 | Admitted-Finance |
| 2 | L2₹13.6 LAdmitted-Finance | ₹13.6 L | L2 | Admitted-Finance |
| 3 | L3₹13.9 LAdmitted-Finance | ₹13.9 L | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Puri Engineering Electricals L3 | mrr electricals and contractors pvt. ltd. L1 | POWER GEN ENGG CO L2 |
|---|---|---|---|---|---|---|
| 1.00 | Supply & Fixing of Distribution Transformers structure including R.S.Joist & other steel item as per approved drawing as per JVVNL specification 2 Pole DT Structure. | 25 | Each | 54,500 ₹13.6 L | 35,000 ₹8.8 L | 47,500 ₹11.9 L |
| 2.00 | Dismentling of materials from site safely deposite in Dis.Com. store (11 K.V. ). | 1 | Job | 15,000 ₹15,000 | 70,000 ₹70,000 | 90,000 ₹90,000 |
| 3.00 | To maintain Height of Overhead LT line on existing poles using all needful accessories | 1 | Nos | 14,500 ₹14,500 | 14,000 ₹14,000 | 85,000 ₹85,000 |
Tender Value
₹2.8 Cr
EMD Value
₹5.6 L
Closing Date
30 Dec 2025, 5:00 pmClosed
Unit Office RIICO Malviya Jaipur (South) Ind. area
Unit Office RIICO Malviya Jaipur (South) Ind. area Jaipur
Shifting of existing overhead line by using Underground cable at Ind. area, Mansarovar, Jaipur.
2025_RIICO_518842_1
34/2025-2026/2212
Open Tender
Electrical Works
365 days
Ind. area Mansarovar
Scanned copy of tenderers registration in appropriate class according this tender and as per technical bid according this tender
5 documents required · 5 mandatory
₹5,900
RIICO
₹5.6 L
Power cell Udyog Bhawan, Tilak marg, Jaipur.
29 Jan 2026
8 Dec 2025
31 Dec 2025
12 Dec 2025
30 Dec 2025
12 Dec 2025
11 Dec 2025
Supply & Fixing of Distribution Transformers structure including R.S.Joist & other steel item as per approved drawing as per JVVNL specification 2 Pole DT Structure.
Dismentling of materials from site safely deposite in Dis.Com. store (11 K.V. ).
To maintain Height of Overhead LT line on existing poles using all needful accessories
BoQ_Ver3.0
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
NUMBER #
Supply and erection of P.C.C. pole as per REC manual no 15/1979 (ammended upto date) and as per latest Discom specifications with factor of safety 2.5 including excavation of pit upto pole planting depth 1/6th of pole length. and back filling with stone aggregate/boulders and soil by ramming and watering etc complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR, 9.0 Mtr long PCC pole of 400 Kg Working Load
Supply and fixing of V type cross arms with top hamper and clamps as per latest Discom specifications made of MS angle on the existing poles complete including all necessary nut and bolt, clamps with two coats of Red oxide and two coats of Aluminium paint etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure A attached with this BSR
Supply and fixing of 11 kV pin insulator confirming to IS:731:1971 with latest ammendment on existing bracket including all accessories like MS forged hot dipped GI Pin confirming to IS 2486(Part-I)/1993 & IS:2486 (Part-II)/1989 with latest amendment, and as per latest Discom specs. etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
Supply and erection of GI stay set confirming to pattern-1 of BS:16/1974 and as per latest Discom Specifications complete with stay rod with anchor plate fitted with cast iron cross head and steel bow, in cement concrete 1:3:6 including excavation of pit-re-filling etc complete as reqd. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR, Stay set of dia 20mm, 2.4m long stay rod and anchor plate 380 x 380 x 4.0 mm
Supplying and drawing overhead steel core Aluminium conductor (ACSR) ISI marked(IS 398 part II-1996) on existing cross arms through insulator with all necessary T&P required including binding and twisting etc. complete in all respect as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR, 100 sqmm of (6/4.72 mm+1/1.57 mm) (Dog)
SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make. Each feeder of RMU should have voltage presence indicator. . and compring of followings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder Modules All the type test certificates as per IEC from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR, Non Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch
Supplying and laying of Hot dip galvanized steel stay wire of 550-900 N/mm Quality confirming to IS-2141/2000 in all respect Including chemical composition (Heavily coated Hard quality) of dia 7/3.15 mm(7/10 SWG) and as per latest Discom specs. etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR ., 3 core 185.0 Sq.mm
Add Extra in item no. 11.1 to 11.4 for Laying Charges for cable through Vermeer machine by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required.
Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. including testing etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR ., 11 KV End Termination Kit Outdoor type, 3 core 240/300 Sq.mm
Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. including testing etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR ., 11 KV End Termination Kit Indoor type, 3 core 120/150/185 Sq.mm
Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. including testing etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR ., 11 KV Straight Through Joint Kit, 3 core 240/300 Sq.mm
Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR, 185.0 Sq. mm, 3.5 core
Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR ., 3.5 x 185.0 sq.mm
Supply and fixing of LT Distribution Kiosk confirming to IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per DISCOM specifications made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including Incoming Switch Disconnector Fuse unit, Aluminium Busbar with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS Channel frame of 75 mm x 40 mm grouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for required no. outgoing. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR, 400 Amp. LT Distribution Kiosk for 250/315 KVA Transformer
Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR ., 20mm x 3mm Alum. Strip
Supply and installation of high tensile low carbon steel rod molecularly bonded with 99.9 % Copper thickness (250 microns) and confirming to UL 467, IS/IEC 62561-2 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-, 25 mm thick and 3 Mtr. Long
Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. All as per pre approved by Engineer in charge. (Earth Excavation will be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annex ure "A" attached with this BSR ., 100 mm dia.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.28 MB
special_terms.pdf
Other Document • 6.07 MB
bd.pdf
Tender Documents • 0.53 MB
BOQ_925870.xls
BOQ • 0.56 MB
Download all tender documents and submit your bid