Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L- 1₹19.9 LAccepted-AOC | L- 1 | Accepted-AOC BEING L- 1 | |
| 2 | L- 2₹19.9 L+₹1,243 (0.06%)Rejected-Finance PLOT NO 1235 JLPL SECTOR 82 SAS NAGAR MOHALI MOHALI PUNJAB 160055 | S A S NAGAR | PUNJAB | 160055 | L- 2 | Rejected-Finance BEING L- 2 | |
| 3 | Not Admitted-Fee/PreQual/Technical 145 A HSIDC HSIDC SECTOR 31 FARIDABAD FARIDABAD HARYANA 121003 | FARIDABAD | HARYANA | 121003 | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification | |
| 4 | Not Admitted-Fee/PreQual/Technical D S 185 186 SECTOR D LDA COLONY KANPUR ROAD LUCKNOW LUCKNOW UTTAR PRADESH 226012 | LUCKNOW | UTTAR PRADESH | 226012 | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification | |
| 5 | Not Admitted-Fee/PreQual/Technical 218 2ND FLOOR U S COMPLEX 120 MATHURA ROAD NEW DELHI 110076 | SOUTH | DELHI | 110076 | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹45,300
Closing Date
20 Oct 2020, 6:00 pmClosed
AGM (ENGG. ELECT.)
AGM (ENGG. ELECT.), Chandigarh International Airport, Project Engineering office, Village- Jhurheri, Mohali (Punjab)- 1403006
SITC of Refrigeration units for Perishable Cargo building at Chandigarh International Airport, Mohali.
2020_AAI_59637_1
SITC of Refrigeration units for Perishable Cargo
Open Tender
Electrical Works
Item Rate
90 days
Chandigarh International Airport, Mohali.
AS PER NIT.
2 documents required · 2 mandatory
₹1,180
Yes
Chandigarh International Airport Ltd
₹45,300
Yes
29 Dec 2020
13 Oct 2020
27 Oct 2020
13 Oct 2020
20 Oct 2020
13 Oct 2020
13 Oct 2020 - 19 Oct 2020
Amount
SITC of refrigeration units suitable for maintaining Indoor temperature range from 10 Deg. C to 18 Deg. C for prefabricated Walk in Store Room (10m x 12m x 3.3m) of newly constructed Cargo, complete as required as per technical specification. The refrigeration units are inclusive of : i) Outdoor unit- Minimum refrigeration capacity of 8.55KW. Hermatic scroll type compressor. Refrigerant R-134a / R- 404a Power supply 415 V, 3 phase 50 Hz ii) Indoor Unit: Minimum refrigeration capacity of 9.75KW. Power supply 230 V, 1 phase 50 Hz or 415 V, 3 phase 50 Hz iii) All associated work like interconnected insulated copper piping upto 06 mtr., Drain piping, Electrical (power&control) cabling, Digital display of temperature at entrance, Gas charging with R134a, Pressure testing & vacuuming with Nitrogen with all adjunct work and supporting material/accessories for installation of Indoor and Outdoor units as per site conditions.
SITC of refrigeration units suitable for maintaining Indoor temperature range from 10 Deg. C to 22 Deg. C for prefabricated Walk Perishable Room (12m x 20m x 3.3m) of newly constructed Cargo, complete as required as per technical specification. The refrigeration units are inclusive of : i) Outdoor unit- Minimum refrigeration capacity of 10.25 KW. Hermatic scroll type compressor. Refrigerant R-134a/ R- 404a Power supply 415 V, 3 phase 50 Hz ii) Indoor Unit: Minimum refrigeration capacity of 10.16 KW. Power supply 230 V, 1 phase 50 Hz or 415 V, 3 phase 50 Hz iii) All associated work like interconnected insulated copper piping upto 06 mtr., Drain piping, Electrical (power&control) cabling, Digital display of temperature at entrance, Gas charging with R134a, Pressure testing & vacuuming with Nitrogen with all adjunct work and supporting material/accessories for installation of Indoor and Outdoor units as per site conditions.
SITC of refrigeration units suitable for maintaining Indoor temperature range from -5 Deg. C to 20 Deg. C for prefabricated Chiller cum freezer Rooms (5m x 4m x 3.3m)- 03 Rooms, of newly constructed Cargo, complete as required as per technical specification. The refrigeration units are inclusive of : i) Outdoor unit- Minimum refrigeration capacity of 5.60 KW. Hermatic scroll type compressor. Refrigerant R-134a / R- 404a Power supply 415 V, 3 phase 50 Hz ii) Indoor Unit: Minimum refrigeration capacity of 5.30 KW. Power supply 230 V, 1 phase 50 Hz or 415 V, 3 phase 50 Hz iii) All associated work like interconnected insulated copper piping upto 06 mtr., Drain piping, Electrical (power&control) cabling, Digital display of temperature at entrance, Gas charging with R134a, Pressure testing & vacuuming with Nitrogen with all adjunct work and supporting material/accessories for installation of Indoor and Outdoor units as per site conditions.
Supplying and connecting additional copper pipe with insulation between the indoor and outdoor units installed in newly constructed cargo rooms (Suitable for item 1, 2 & 3) as required.
Ace Cooling Solutions
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .