Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.0 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹46.0 L+₹8.0 L (21.2%)Rejected-AOC | L2 | Rejected-AOC Rejected |
Tender Value
₹38.8 L
EMD Value
₹77,600
Closing Date
24 Nov 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE JHANSI
HQ CWE JHANSI
PROVN OF 01X150 KVA TRANSFORMER WITH CONNECTING ITEMS FOR SIMULATORS AT 54 ARMD REGT TRG COMPLEX AND PROVN OF WIRING AND ELECT CONNECTION ALONG WITH ALLIED ACCESSORIES FOR OFFRS MD ACCN AS AUTH INCL AC POINT UNDER GE BABINA
2021_MES_475533_2
CWE/JHA/BAB/TOKEN/67 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
BABINA
As per tender documents
8 documents required · 8 mandatory
₹500
GE BABINA
₹77,600
Yes
22 Jan 2022
28 Oct 2021
29 Nov 2021
28 Oct 2021
24 Nov 2021
12 Nov 2021
60 days
Amount
Supplying, installation, connecting, testing and commissioning of outdoor type distribution transformer of 160 KVA, 11/0.433 KV, 3 phase, 50 Hz, ONAN cooled oil immersed copper wound step down energy saving ( level 2) floor mounted complete with first filling ISI marked filtered & dehydrated transformer oil and other standard fittings / accessories and 7 position off circuit tap changer (tapping range +/- 7.5% in steps of 2.5% each) with vector group DYN -11 complete all as specified and as directed by the Engineer in Charge. Note - (i) The ambient temprature shall be 48 degree Centigrade when measured by the resistance method after continuous full load run . (ii) The transformer shall be complete with standard fittings all as specified and conforming to IS:335 of 1993 for oil and IS: 1180 Part -I of 2014 for transformer and comprising of followings:- (i) One No cable box on LV side (secondary side) consisting of 04 Nos of porcelain bushing with bushing rods and another cable box on HV side (primary side) consisting of 03 Nos of porcelain bushing with bushing rods etc complete with nut, washers, cable gland etc. (ii) Oil conservator tank with filter type drain valve and oil level gauge. (iii) Oil level indicator with minimum and maximum marking (iv) Dehydration silica gel breather assembly with first fill of dehydrating agent and oil seal. (v) Explosion vent with diaphragm complete. (vi) Thermometer pocket on tank cover. (vii) Dial type thermometer vapour pressure having range 0-120 degree C with max reading pointer max temp indicator and resetting device. (viii) Rating plate with terminal marking.
(ix) 02 Nos earthing terminal on tank and cover for fixing earth strip of size 32 x 6 mm. (x) Oil level gauge and oil drain filter valve. (xi) Lifting hook. (xii) Oil filler hole with cap /plug with connection complete. (xiii) Air relief valve plug. (xiv) Detachable rollers - 04 Nos (xv) Extra bushing for Neutral out side the cable box for independent earthing for neutral earth. (xvi) First fill of fresh transformer oil confirming to relevant IS and tested up to 40 KV die electric strength. Make :- ITE Gurgon/ Rajastan Transformers/voltlamp ltd/Crompton/Schnider/Alstom/Indo Asian
M&L for switch air break gang operated triple pole mechanically operated mounted on HT insulators (12 insulator type) with DO fuse unit insulator barrel type fuse of suitable rating and MS galvanised steel frame with operating mechanism worked from ground level incl operating rod and operating handle with 11 KV insulation for current rating up to 200 Amp 11000 volts complete all as specified and directed.
M&L SMX type lightning arrestors confirming to IS-3070 (Part-1) having voltage rating 12 KV, rated frequency 50 Hz, nominal discharge current 65 KA (heavy duty) expulsion type transmission class complete with all fittings suitable for 11 KV, 3 phase earthed distribution system complete all as specified and directed. Make :- Pactil/BHEL/GEC-ELPRO/ATLAS
Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP-55), 11 mtr long, complete with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided with one coat of red oxide primer and two coats of aluminium paint complete all as specified and directed. (Numbering of the poles shall be done with synthetic enameled painted letter of shape & size as directed.) Note :- Excavation including earth work and PCC foundation will be measured and paid separately.
Supplying laying jointing, testing & commissioning in trenches, fixed on poles/ drawing through pipes HT XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cables, heavy duty with stranded aluminium conductor, 11000 volts grade (Earthed) crossectional area 95 Sqmm 3 core complete all as specified and directed. Make:- M/s KEI INDUSTRIES/HAVELLS INDIA LTD/ASIAN CABLE/UNIVERSAL CABLES
S&F of cable jointing Kit 11 KV (earthed) grade cable for end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 95 sqmm complete all as specified and as directed. Make - M- seal/Denson/3M-Birla/Raychem
M&L for mild steel cross arms, bracings supports, clamps and back plates fabricated from structural steel sections, channel including nuts, bolts, washers welding, bending cold or not, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and as directed.
Supplying laying jointing, testing & commissioning in trenches, fixed on poles/ drawing through pipes LT XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cables, heavy duty with stranded aluminium conductor, 1100 volts grade (Earthed) crossectional area size single core 150 sqmm complete all as specified and directed. Make:- M/s KEI INDUSTRIES/HAVELLS INDIA LTD/ASIAN CABLE/UNIVERSAL CABLES
All as per item no 8 but of size 70 sqmm 3.5 Core complete all as specified and directed.
All as per item no 8 but of size 35 sqmm 3.5 Core. complete all as specified and directed.
Aall as per item no 8 but of size 25 sqmm 4 Core .complete all as specified and directed.
All as per item no 8 but of size 16 sqmm 4 Core complete all as specified and directed.
M & L for earthing complete with galvanized steel earth plate electrode 60 x 60cm x 6 mm thick burried directly in ground vertically to a depth not less than 3.0 mtr deep below GL with top edge of the plate not less than 2.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to earth lead of GI wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvd iron or steel and thimbles and other end of the earth lead connected to equipments and watering pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and testing of earthing complete and all as shown in electrical plate No 3 of MES schedule Pt I of 2009 . Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. 2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . 3. On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms.
M & L for earthing complete with galvanized steel earth plate electrode 60 x 60cm x 6 mm thick burried directly in ground vertically to a depth not less than 3.0 mtr deep below GL with top edge of the plate not less than 2.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to earth lead of GI strip 32x6 mm by means of bolts, nuts, check nuts and washers of galvd iron or steel and thimbles and other end of the earth lead connected to equipments and watering pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and testing of earthing complete and all as shown in electrical plate No 3 of MES schedule Pt I of 2009 . Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. 2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . 3. On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms.
Excavation in trenches n. exc 1.5 mtr wide and n. exc 1.5 mtr depth for pole / cable / foundation etc including getting out in soft /loose soil complete all as specified and directed.
Excavation in trenches in any type of soil not exc 1.5 mtrs wide and exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed.
Returning, filling in, approved earth including spreading, levelling, watering and well ramming in layers n.exc 25 Cm thick after cable are laid and tested complete all as specified and directed.
Removing excavated material / surplus soil to a distance not exc. 50 mtrs & deposited where directed at a level not exc.1.5 mtr above the ground level complete all as specified & directed.
M&L for PCC cable cover class LV type 1 flat size 250 mm x 150 mm x 40 mm, ISI marked across the cable for protection of cable after sand cushioning complete all as specified & directed. Make :- MEHTAB TILES INDORE/M/S NAVYA TILES JODHPUR, SAP PAVERS JODHPUR
M&L for PCC cable cover class HV type 1 flat size 300 mm x 180 mm x 40 mm, ISI marked across the cable for protection of cable after sand cushioning complete all as specified and directed. Make : MEHTAB TILES INDORE/M/S NAVYA TILES JODHPUR, SAP PAVERS JODHPUR
Supply and laying dry river sand for cable cushioning in trenches to required width at bottom and top of cable incl spreading, levelling, watering and consiolidation complete all as specified and directed.
M&L for PCC 1:4:8 type D-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete for poles all as specified and directed by Engr-in-Charge.
M&L for PCC 1:3:6 type C-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete including form work for poles complete all as specified and directed.
M&L for PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) as in coping etc including form work for poles complete all as specified and directed.
M&L for steel tubing galvanised, light grade complete with fittings laid in trenches/ fixed along with poles etc as protection to cables of size 50 mm dia bore complete all as specified and as directed.
M&L for steel tubing galvanised, light grade complete with fittings laid in trenches/ fixed along with poles etc as protection to cables of size 80 mm dia bore complete all as specified and as directed.
M & L for road cutting incl excavation in trenches for laying HT/LT UG cable in pipe not exc 45 cm wide and n.exc 90 cm depth or as per site requirement making good the disturbed surfaces with cement concrete (1:3:6) type C-1 and top surface neatly finished as per existing to match with the existing complete all as specified .
M&L for brick work with fly ash bricks, straight or curved on plan exc 6 m mean radius built in CM (1:4) as in foundation of equipment, platform, ramp, supporting pillars of pipes incl demolistion of existing brick work built in cement mortar complete all as specified and directed.
M&L for plastering in CM (1:4) 10 mm thick on fair faces of brick work or concrete surface/cable duct/floor complete all as specified and directed.
M&L MS angles as fencing port, struct cutting tops in shape incl all necessary drilling, notching and reveting etc and similar work confirming fe 310-0 pr fe 4120-0 including prepration of steel Surface of one coat of red oxide and two coat of synthetic enamel paint complete all as specified and directed.
M&L for structural MS frame work half round or other stock section including securing posts and stuts in fencing, frame work for gates of substations, base frame for equipments including securing bolts, posts and sturts in fencing including cutting and makeing shapes as desired, drilling holes, notching for wire cut to size and made to the exisitng shape suitable for fixing MS chequred duct covers / door panels, including nuts, bolts and washers, welding / bracing works, bending cold or hot drilling holes for bolts in any shapeetc flat iron fillets (for securing wire mesh etc) all necessary drilling, bolting or riveting etc and similar work confirming to Fe-290 Gde E-165 including one coat of primer and two coats of synthetic enamel paint to the entire steel surfaces complete all as specified and directed.
M&L for chain link MS galvanised fencing including lines wires, dia of chain link n less than 3.5 mm any mesh any size any type to any type strands rails, straining bolts etc complete all as specified and directed.
S&F mild steel screw bolt (mechine made) with hexagonal or square, head, n.exc 5 cm but n.ecx 10 cm dia complete all as specified and directed.
M&L TMT bars 10 mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and includingmild steel wire (annealed) not less than 0.9 mm dia or securing with clips complete all as specified and directed.
S&F galvanised 2 strand steel barbed wire 2.24 mm dia barbed with 2 mm dia barbs at 75 mm spacing and straining and fixing to any type of standard rails straining bolts including securing or tying at crossing with and provision of galvanised mild steel wire staples or steel pins etc complete all as specified and directed. Note - Each line of horizontal/vertical/diagonal wire to be measured for purpose of payment.
M&L for laying 40 mm graded stone aggregate & stone dust in substations insuch a way that after removing of unwanted grass from substations and then levelling at zero level and laying of stone dust of 50 mm thick at an initial layer and then laying of 25 mm gaded stone aggregate 100 mm thick over the stone dust. The quoted rate also includes cleaning and levelling and filling of sub station before laying aggregate complete all as specified and directed.
Supply & fixing of TPN Kit kat type rewireable switch fuse unit of 415 Volt 50 Hz three phase of capacity 63 Amp including MS box with backelite fuse fittings with HBC fuse, operating insulated handle, top cover necessary locking arrangemnts etc including necessary wall mounting fitting as directed of make Havells Cat part No. IHSBTE4063 or equivalent including taking down the existing all as specified and directed
S & F of change over switch with advanced neutral, ON LOAD, 100 Amps, 4 pole, AC 415 Volt, manual Change over insheet metal enclosure including operating handle conforming to IS:13947 (Part-3) complete all as specified and directed. Make : L&T cat part No CO11000OSOO/Havells/Indo Asian or equivalent approved make
Supply, installing, testing and commissioning, factory made and tested ,CPRI type tested LT feeder pillar , outdoor type floor mounted , suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and LT panel shall bemounted on angular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hight and fixed with PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door shutter and locking arrangement and consisting of the following all as specified including taking out old feeder pillar and taking out LT cable from loop for connecting in new panel and necessary excavation etc and consisting of the following
S&F & testing commissioning of outdoor type bus bar panel pedestal type weather proof CPRI approved MS cubical panel board outdoor type of size 110 cm x 80 cm x 40 cm, 4 Nos of bus bar of 200 Amp capacity & MCCB 160 Amp capacity 4 pole (Ics = Icu = 100%) including one coat of red oxide and two coat of enamel paint powder coated, mounted on channels and PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator complete all as specified and directed. Make :- MCLAYERS-BHOPAL/NATIONAL ENGG WORKS/UNIVERSAL SWITCH GEAR/ SHALABH/ALSTONE
Supplying laying jointing, testing & commissioning in trenches, fixed on poles/ drawing through pipes LT XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cables, heavy duty with stranded aluminium conductor, 1100 volts grade (Earthed) crossectional area size single core 630 sq mm complete all as specified and directed. Make:- M/s KEI INDUSTRIES/HAVELLS INDIA LTD/ASIAN CABLE/UNIVERSAL CABLES
All as per item no 41 but of size 3.5 core 150 sq mm complete all as specified and directed.
Supplying, installation, connecting, testing and commissioning of outdoor type distribution transformer of 400 KVA, 11/0.433 KV, 3 phase, 50 Hz, ONAN cooled oil immersed copper wound step down energy saving ( level 2) floor mounted complete with first filling ISI marked filtered & dehydrated transformer oil and other standard fittings / accessories and 7 position off circuit tap changer (tapping range +/- 7.5% in steps of 2.5% each) with vector group DYN -11 complete all as specified and as directed by the Engineer in Charge. Note - (i) The ambient temprature shall be 48 degree Centigrade when measured by the resistance method after continuous full load run . (ii) The transformer shall be complete with standard fittings all as specified and conforming to IS:335 of 1993 for oil and IS: 1180 Part -I of 2014 for transformer and comprising of followings:- (i) One No cable box on LV side (secondary side) consisting of 04 Nos of porcelain bushing with bushing rods and another cable box on HV side (primary side) consisting of 03 Nos of porcelain bushing with bushing rods etc complete with nut, washers, cable gland etc. (ii) Oil conservator tank with filter type drain valve and oil level gauge. (iii) Oil level indicator with minimum and maximum marking (iv) Dehydration silica gel breather assembly with first fill of dehydrating agent and oil seal. (v) Explosion vent with diaphragm complete. (vi) Thermometer pocket on tank cover. (vii) Dial type thermometer vapour pressure having range 0-120 degree C with max reading pointer max temp indicator and resetting device. (viii) Rating plate with terminal marking.
(ix) 02 Nos earthing terminal on tank and cover for fixing earth strip of size 32 x 6 mm. (x) Oil level gauge and oil drain filter valve. (xi) Lifting hook. (xii) Oil filler hole with cap /plug with connection complete. (xiii) Air relief valve plug. (xiv) Detachable rollers - 04 Nos (xv) Extra bushing for Neutral out side the cable box for independent earthing for neutral earth. (xvi) First fill of fresh transformer oil confirming to relevant IS and tested up to 40 KV die electric strength. Make :- ITE Gurgon/ Voltamp ltd / Crompton/ Schnider/Alstom
M&L for demolition of PCC floor/brick wall of any type any size for laying UG cable/GI pipe any ize & making good the disturbed area to match with the existing level with cement mortar including removing the surplus soil to a distance upto 50 mtr making good the disturbed surfaces with cement concrete (1:3:6) type C-1 and top surface neatly finished as per existing to match with the existing complete all as specified and directed
S&F for sub main wiring with PVC insulated, unsheathed flame retradent low smoke (FRLS) 2 single core cable 1100 volts grade with copper conductor of size 4.0 sq mm (Nominal area) multi stranded drawn into new PVC conduit on surface mounting with and including 2.5 sqmm green stranded copper conductor as contineous earthwire terminated with copper lugs in complete all as specified and as directed. Note: New conduit and conduit accossories shall be measured & paid separately. Make :- Havells/polycab/ RR Cables.
S&F for sub main wiring with PVC insulated, unsheathed flame retradent low smoke (FRLS) 2 single core cable 1100 volts grade with copper conductor of size 10.0 sq mm (Nominal area) multi stranded drawn into new PVC conduit on surface mounting with and including 6 sqmm green stranded copper conductor as contineous earthwire terminated with copper lugs in complete all as specified and as directed. Note: New conduit and conduit accossories shall be measured & paid separately. Make :- Havells/polycab/ RR Cables.
S & F Regid non-metallic PVC conduit not less than 20 dia (external) ISI marked (on surface) incl of all accessories and all fittings such as Tees,bends, elbows,junction boxs any type reducers, bell mouth, tube ends and fixing accossories such as couplers,lock nuts, saddles, pipe hook etc complete all as specified and as directed
S&F MCB single pole and neutral 40 Amp 240 V ,10KA , 'C' series, complete all as specified and as directed with copper lugs complete all as specified and as directed. Make :- ABB/ Schneider/ L&T
S&F sheet metal enclosure double door concealed suitable for distribution boards when MCBs to be used having 200 Amp rated bus bar 4 ways 240 V IP 54 complete all as specified and as directed . Make :- ABB/ Schneider/ L&T/Indoasian
S&F MCB single pole 25 Amp 240 V ,10KA , 'C' series, complete all as specified and as directed with copper lugs complete all as specified and as directed. Make :- ABB/ Schneider/ L&T
Supply & fix pre wired power unit with 25 Amp MCB & 16 Amp 3 pin plug indicator type (for connecting AC) with MS terminal boxes (not less than 1.0 mm thick) and painted with one coat of red oxide primer all around and two coats of black bituminous paint from out side and two coat of aluminum paint from in side suitable for fluh mounting conforming to IS 8623-1 & 3 IES 61439-1 & 3 complete all as specofid and directed. Make :- ABB/ Schneider/ L&T/Havells
M/s SIYA ENGINEERING CO
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .