| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹41.9 LAccepted-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L1 | Accepted-AOC L1 QUOTED | |
| 2 | L2₹42.7 L+₹83,575 (1.99%)Rejected-AOC 59 NEW MARKET CLOCK TOWER DEHRADUN UK PIN 248001 | DEHRADUN | UTTARAKHAND | 248001 | L2 | Rejected-AOC L2 QUOTED | |
| 3 | L3₹44.8 L+₹2.9 L (6.90%)Rejected-AOC 5021 1 CAT III MODERN HOUSING COMPLEX MANIMAJRA CHANDIGARH | CHANDIGARH | CHANDIGARH | 160001 | L3 | Rejected-AOC L3 QUOTED | |
| 4 | L4₹45.3 L+₹3.4 L (8.09%)Rejected-AOC | L4 | Rejected-AOC L4 QUOTED | |
| 5 | L5₹47.6 L+₹5.7 L (13.6%)Rejected-AOC 901 GH 83 SECTOR 20 PANCHKULA 134116 | PANCHKULA | HARYANA | 134116 | L5 | Rejected-AOC L5 QUOTED |
Tender Value
₹48.4 L
EMD Value
₹96,860
Closing Date
27 Dec 2024, 6:00 pmClosed
GE AF Chandigarh
GE AF Chandigarh, Air Force Station Chandigarh-160003
PROVN OF CERTAIN B/R AND E/M WORK SERVICES AND AIR CONDITIONERS ( 2 TON CAPACITY) ALONGWITH ASSOCIATED WORK SERVICES AT AF STN CHANDIGARH UNDER GE (AF) CHANDIGARH.
2024_MES_685129_1
GE(AF)/CHD/T-48/2024-25
Open Tender
Civil Works
Item Rate
183 days
Chandigarh
Please refer Tender documents.
10 documents required · 10 mandatory
₹500
GE AF Chandigarh
₹96,860
Yes
15 Feb 2025
22 Nov 2024
31 Dec 2024
22 Nov 2024
27 Dec 2024
6 Dec 2024
22 Nov 2024 - 29 Nov 2024
Amount
Note :The unit rate quoted by the tenderer under Col No (13) of Sch `A’ (BOQ) unless specifically mentioned otherwise such as labour only/fixing only, for all items of works shall be deemed to be including cost of all materials, labour, tools and plants, testing and commissioning of work in position complete as required for entire completion of work.
Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out in soft/loosec soil including removing excavated soil to a distance exceeding 250 metre but not exceeding 500 metre and depositing where directed at a level not exceeding 1.50 meter above the starting point , complete all as specified and directed by Engineer-in-Charge.
Excavating in trenches in soft/loosec soil , not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out, complete all as specified and directed by Engrineer-in-Charge.
Excavating in trenches in soft/loosec soil , exceeding 1.5 m not exceeding 3.0 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out, complete all as specified and directed by Engrineer-in-Charge.
Excavating in (soft/ loose soil) post holes (or similar holes) each n. exc. 0.5 cum, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, including leveling and spreading, , complete all as specified and directed by Engrineer-in-Charge.
Hardcore of gauge exceeding 63 mm but not exceeding 100 mm of broken stone or boulders , deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface , complete all as specified and directed by Engineer-in-Charge.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches , complete all as specified and directed by Engineer-in-Charge.
Removing excavated soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.50 meter above the starting point , complete all as specified and directed by Engineer-in-Charge.
Demolition of cement concrete (un-reinforced) of any description and in any position not otherwise specifically provided for and removal or debries outside MoD land, complete all as specified and directed by Engineer-in-Charge.
Plain cement concrete (1:4:8), type D-2, using 40 mm graded mechanically crushed stone aggregates and finished the surface rough to provide adequate bond for the topping as in sub base ,foundations, filling and mass concrete,path and hardstanding etc, complete all as specified and directed by Engineer-in-Charge.
Plain cement concrete type C-2 (1:3:6) using 40mm graded mechanically crushed stone aggregates as in embedding the fencing post / struts , complete all as specified and directed by Engineer-in-Charge.
Plain cement concrete (1:2:4) type B-0 using 12.5 mm graded mechanically crushed stone aggregates as in mud stop ,sides of intetlocking paver block and the like including rounded or chamfered on edges including necessary form work , complete all as specified and directed by Engineer-in-Charge.
Providing Precast plain cement concrete 1:2;4 type B-1 usinng 20mm graded mechanically crushed stone aggregatesas in kerb stone machine made of size as approved by GE made to shape slightey rounded or chamfered as directed set & pointed in CM 1:6 as in road side kerb stone , complete all as specified and directed by Engineer-in-Charge.
Plain cement concrete ,50 mm thick (1:2:4) type B-1, using 20 mm graded mechanically crushed stone aggregates as in flooring finished even & smooth using extra cement @1.20 Kg /Sqm including necessary form work , complete all as specified and directed by Engineer-in-Charge. Note : Use and waste of form work/screed strips and to divide the area in panels shall be included in the quoted rate .
Plain cement concrete ,100 mm thick (1:2:4) type B-1, using 40 mm graded mechanically crushed stone aggregates as in flooring laid in approved size panels finished even & smooth using extra cement @1.20 Kg /Sqm including necessary form work , complete all as specified and directed by Engineer-in-Charge. Note : Use and waste of form work/screed strips and to divide the area in panels shall be included in the quoted rate .
Use & waste of form work to sides of concrete foundations, footings, bases of columns, raft and raft beams,sides and soffits (if any) of foundation and plinth beams;and similar work; vertical or to batte etc of rough finished flat surfaces, complete all as specified and directed by the Engineer in Charge.
Use & waste of form work to sides of pillars,posts, struts, piers, columns and stanchions etc; with r rough finished flat surfaces of concrete, complete all as specified and directed by the Engineer in Charge.
Mild steel TMT bars 10mm dia and over as in reinforcement cut to length , bent to shape required, including cranking, bending spirally for hooping ends for columns, hooking ends and binding with and including mild steel wire annealed not less than 0.90mm dia, complete all as specified and directed by the Engineer in Charge.
Mild steel TMT bars 5mm dia and over and upto and including 10mm dia as in stirrups, spacers and binders cut to length, bent to shape required, including cranking, bending spirally for hooping for columns , hooking ends and binding with and including mild steel wire ( annealed) not less than 0.90mm dia. Or securing with clips , complete all as specified and directed by the Engineer in Charge.
Reinforced Cement concrete 1:1.5:3 , type A-1 using 20mm graded mechanically crushed stone aggregates as in foundations, including rafts, footings, foundation beams; plinth beams; bases for columns, etc; basement slabs, under reamed piles and mass concrete, complete all as specified and directed by Engineer-in-Charge. Note: Steel reinforcement shall be measured and paid for separetely.
Reinforced Cement concrete 1:1.5:3 , type A-1 using 20 mm graded mechanically crushed stone aggregates as in Columns, pillars, piers,posts and struts, complete all as specified and directed by Engineer-in-Charge. Note: Steel reinforcement shall be measured and paid for separetely.
Brick work with sub-class `B' bricks, straight or curved on plan exceeding 6 M mean radius built in cement sand mortar 1:6 complete in and including demolition of brickwork or stone boulder masonary built in cement mortar including all quoins, arches, pillars etc for the area where unservicable bricks retrived and removal of rubbish outside MoD land , complete all as specified and directed by Engineer-in-Charge.
Granite 20mm thick (of any type) tiles machine cut, in skirting/ dado laid over 15mm thick screed bed in cement mortar (1:4) and jointed with grey cement slurry, and pointed with white cement with admixture of pigment to match the shade of granite stone including grinding and polishing including grinding and polishing ,complete all as specified and as directed by Engineer -in-Charge.
Providing and laying 60mm thick factory made machine pressed interlocking paver block of M-35 grade of any shape and size confirming to IS 15658-2006 with grey cement and pigment (In top layer) laid over and including 25 mm thick compacted bed of fine sand, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra ,complete all as specified and as directed by Engineer -in-Charge. Note : Quoted rates are inclusive of fine sand and nothing extra shall be admissible on this account.
Rendering 15 mm thick plaster on other than fair faces of brick work or concrete surfaces in cement mortar (1:4) finished even and smooth without using extra cement, complete all as specified and directed by Engineer-in-Charge.
Rendering 5 mm thick plaster in cement mortar (1:3), as on concrete surfaces of ceiling and finished the surfcae even and smooth without using extra cement, complete all as specified and directed by Engineer-in-Charge.
Preparation of new plastered or unplastered surfaces of walls and applying two coats of Cement base paint over over a coat of primer , complete all as specified and directed by Engineer-in-Charge.
Steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I. S.1161-1979 grade St.-240 including all fittings , complete all as specified and directed by the Engineer-in-Charge.
Mild steel work such as wind ties for for roof including securing bolts etc and similar works including all necessary drilling, bolting or riveting, etc., conforming to Fe-290 Gde E-165 , complete all as specified and directed by the Engineer-in-Charge.
Bands, straps, supports or stays for rainwater, plain angle cleat for securing purlin, knee piece inserts, two way and three way straps, plate washer and similar small articles, confirming to Fe-290 Gde E-165 , complete all as specified and directed by the Engineer-in-Charge.
Plates (plain or chequered) Channels, square, cut or notched (ordinary and counter sunk) forming holes without any attachment of Fe-410-W (Grade E-250) quality B, complete all as specified and directed by the Engineer-in-Charge.
Mild steel screw bolts(machine made)11 to 15mm dia of shank with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or squarae nut, exc 5cm but n.exc 10cm long , complete all as specified and directed by the Engineer-in-Charge.
M S work as Framed works such as grills, gratings etc with ends of bars shouldered and/or riveted, or forged into spikes,framed guard bars barred iron doors ladders, framed balusters walk ways railing, framed work of water tanks, framed and hung as gates including pintle hinges, stops, hand made sliding sliding bolts etc ,drilling bolting or reveting etc and similar work conforming Fe-290 Gde E-165, complete all as specified and directed by Engineer-in- Charge.
Tie bars with screwed ends, nuts, washers and mild steel plates for walls, chimneys, roofs, arches, etc. king rods and straining bolts conforming to Fe- 290 Gde-E-165 , complete all as specified and directed by Engineer-in- Charge.
Mild steel, plain, black sheet of 1mm thick in hearths in wall cladding,steel gates and similar work, cut to size, holes punched; including round headed screws, clout nails or rivets and fixed to wood or steel framing with plain 40 mm lap joints with riveted or welded seams, including bending or turning up, mitred angles, etc. as required., complete all as specified and directed by the Engineer-in-Charge.
Pre-colour coated high tensile strength galvalume corrugated sheet roofing with yield strength (550 MPA) prepainted with aluminium (55%) and zinc (45%) alloy coating applied through continous hot dip process having total coated thickness (TCT) of 0.50mm as in roof covering/cladding to wall, fixed with self tapping screws , complete all as specified and directed by Engineer-in-Charge.
Pre-colour coated high tensile strength galvalume plain sheet roofing with yield strength (550 MPA) prepainted with aluminium (55%) and zinc (45%) alloy coating applied through continous hot dip process having total coated thickness (TCT) of 0.50mm as in roof covering/cladding to wall, fixed with self tapping screws , complete all as specified and directed by Engineer-in-Charge.
Plain mild steel 4mm dia of wire,galvanised class 3, in detached work such as for mosquito nets and fixing to straining bolts, hooks, eyes, etc. including straining and fixing to wood, concrete or steel posts and/or to straining bolts, including securing with and provision of galvanised iron tying wire, galvanised iron staples or steel pins, etc , complete all as specified and directed by Engineer-in-Charge. Note :Each line wire shall be measured.
Preparation of new or previously untreated steel surfaces of any description , not otherwise described over 10 cm width or girth and applying two coats of synthetic enamells paint over one coat of red oxide primer,complete all as specified and directed by the Engineer in Charge.
Point wiring complete with single core multi stranded copper conductor cable of size 1.5 sqmm PVC insulated sheathed FRLS 1100 volts grade drawn through in and including concealed non-metallic PVC rigid conduits medium grade with all standard fitting such as tee,junction boxes,bends,including new sunken terminal boxes duly epoxy painted with 3mm thick hylam sheet for mounting switch/sockets etc and incl 1.5 sqmm multi stranded copper conductor PVC insulated sheathed FRLS colour code cable 1100 volts grade for earth continuity for one light point/fan point controlled by one switch one way, complete all as specified and directed by Engineer-in-Charge. Note : Wiring shall be done by using proper colour coding.
All as per srl item No. 40 here-in-before but for 06 Amp socket outlet on independent board, complete all as specified and directed by Engineer-in-Charge. Note : Wiring shall be done by using proper colour coding.
Point wiring complete with single core multi stranded copper conductor cable of size 2.5 sqmm PVC insulated sheathed FRLS 1100 volts grade drawn through in and including concealed non-metallic PVC rigid conduits medium grade with all standard fitting such as tee,junction boxes,bends,including new sunken terminal boxes duly epoxy painted with 3mm thick hylam sheet for mounting switch/sockets etc and incl 2.5 sqmm multi stranded copper conductor PVC insulated sheathed FRLS colour code cable 1100 volts grade for earth continuity for one 15 amps socket outlet on independent board, complete all as specified and directed by Engineer-in-Charge. Note : Wiring shall be done by using proper colour coding.
Switch piano, flush type single pole, one way 6 Amp , complete all as specified and directed by Engineer-in-Charge.
Switch piano, flush type single pole, one way 16 Amp complete all as specified and directed by Engineer-in-Charge.
Socket outlet 2 in1, 3 pin, 5 Amp, complete all as specified and directed by Engineer-in-Charge.
Socket outlet 6/16 Amp - 2/3 pin combined piano type, complete all as specified and directed by Engineer-in-Charge.
Ceiling Rose, 3 Phase/ PVC/ Polycarbonate, isolated body, complete all as specified and directed by Engineer-in-Charge.
Ceiling Fan step regulator ,120 W for 1200/ 1400 mm sweep ceiling fan, complete all as specified and directed by Engineer-in-Charge.
Removing existing switches/sockets of any type along with mounting sheet, fixing insulation tape on cable ends and supply and fixing 3 mm thick hylam sheet cut to required size on existing sunken terminal boxes/junction boxes etc , complete all as specified and directed by Engineer-in-Charge.
MCB SP, 6 to 32 Amps, ,240 Volts ,10 KA 'B' curve type to be housed in DBs of Proper and suitable size cable lugs to be fixed with MCBs ,complete all as specified and directed by Engineer-in- Charge.
MCB SP, 63 Amps, ,240 Volts ,10 KA 'B' curve type to be housed in DBs of Proper and suitable size cable lugs to be fixed with MCBs ,complete all as specified and directed by Engineer-in- Charge.
MCB SPN, 32 to 40 Amps, ,415 Volts ,10 KA 'B' curve type to be housed in DBs of Proper and suitable size cable lugs to be fixed with MCBs ,complete all as specified and directed by Engineer-in- Charge.
MCB TP 240 volts 20 to 40 Amps ‘10 KA 'B' curve type to be housed in DBs of Proper and suitable size cable lugs to be fixed with MCBs ,complete all as specified and directed by Engineer-in- Charge.
Distribution box Double door type , SPN 8 way,with 200 amps rated bus bar, 240 Volts for MCBs, grouted flush to walls complete with IP 42 and metal double door ,epoxy powder coated ,complete all as specified and as directed by Engineer-in- Charge.
Distribution box Double door type , SPN 12 way,with 200 amps rated bus bar, 240 Volts for MCBs, grouted flush to walls complete with IP 42 and metal double door ,epoxy powder coated ,complete all as specified and as directed by Engineer-in- Charge.
Sheet metal enclosure for incoming MCCB and outgoing MCBs factory made double door, VTPN 415 volts 4 ways with 200 Amp bus bar with IP43 protection ,complete all as specified and as directed by Engineer-in- Charge.
Sheet metal enclosure single pole and neutral with a two pin & earth plug and socket etc complete with on SP MCB 6 to 32 Amps, 'B' curve, 240 volts 10 KA, complete all as specified and as directed by Engineer-in- Charge.
MCCB, 4 pole, 100 Amps, 16 KA, 50Hz, 415 volts with adjustable thermal & adjustable magnetic type relays , complete all as specified and as directed by Engineer-in- Charge.
LED tube light fittings 1x20W,220V,AC decorative box batten type with driver, 4 feet long and connecting, complete all as specified and as directed by Engineer-in- Charge.
LED tube light fittings 1x10W,220V,AC decorative box batten type with driver, 2 feet long and connecting, complete all as specified and as directed by Engineer-in- Charge.
Sub main wiring along with earth wire with two single core 4 Sqmm(nominal area) PVC insulated and sheathed cables with stranded copper FRLS conductor in and including concealed non-metallic rigid PVC conduits including one run of continuous PVC insulated FRLS multi stranded copper cable of size 1x4.0 Sqmm earth wire for earth continuity conductor, complete all as specified and as directed by Engineer-in- Charge. Note- 02 runs of 4.0 sqmm cables, 01 runs of 4.0 sqmm earth wire and 01 run of PVC conduit will be measured as one unit.
Sub main wiring along with earth wire with two single core 6 Sqmm(nominal area) PVC insulated and sheathed cables with stranded copper FRLS conductor in and including concealed non-metallic rigid PVC conduits including one run of continuous PVC insulated FRLS multi stranded copper cable of size 1x6.0 Sqmm earth wire for earth continuity conductor, complete all as specified and as directed by Engineer-in- Charge. Note- 02 runs of 6.0 sqmm cables, 01 runs of 6.0 sqmm earth wire and 01 run of PVC conduit will be measured as one unit.
Sub main wiring along with earth wire with four single core 6 Sqmm(nominal area) PVC insulated and sheathed cables with stranded copper FRLS conductor in and including concealed non-metallic rigid PVC conduits including one run of continuous PVC insulated FRLS multi stranded copper cable of size 1x6.0 Sqmm earth wire for earth continuity conductor, complete all as specified and as directed by Engineer-in- Charge. Note- 04 runs of 6.0 sqmm cables, 01 runs of 6.0 sqmm earth wire and 01 run of PVC conduit will be measured as one unit.
LT under ground electric power cable crossed linked polyethylene ( XLPE) insulated, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 35 sqmm cross sectional area, 3.5 core ,laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers including jointing and testing , complete all as specified and directed by Engineer-in- Charge. Note: Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items.
All as per item No 64 here-in-before but size 50 sqmm 3.5 core , complete all as specified and as directed by Engineer-in- Charge.
All as per item No 64 here-in-before but size 70 sqmm 3.5 core , complete all as specified and as directed by Engineer-in- Charge.
All as per item No 64 here-in-before but size 95 sqmm 3.5 core , complete all as specified and as directed by Engineer-in- Charge.
All as per item No 64 here-in-before but size 120 sqmm 3.5 core , complete all as specified and as directed by Engineer-in- Charge.
HT electric power cable crossed linked polyethylene XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, (heavy duty) with aluminium conductor, 11000 volts Earthed, grade of size 95 sqmm cross sectional area, 3.0 core ,laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers including jointing and testing , complete all as specified and directed by Engineer-in- Charge. Note: Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items.
HT electric power cable crossed linked polyethylene XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, (heavy duty) with aluminium conductor, 11000 volts Earthed, grade of size 120 sqmm cross sectional area, 3.0 core ,laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers including jointing and testing , complete all as specified and directed by Engineer-in- Charge. Note: Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items.
Sand cushioning to under ground cable with clean dry river sand in layer of sand 8cm thick before laying of cable and 15 cm after laying of cable, complete all as specified and directed by Engineer-in-Charge. Note- For payment purpose punned thickness of 18 cm shall be measured against spread thickness of 23 cm as mentioned in para 19.75 of SSR Part-I.
Protection of cable with one layer of bricks laid flat butting to each other in such a way that the length of the bricks is at right angle to the central axis of the cable using old size sub-class ‘B’ bricks, complete all as specified and as directed by Engineer-in-Charge.
Steel tubing, 80 mm bore light grade ISI marked galvanized with all fittings laid in trenches / road crossing/ fixed to pole /walls/path/drain /floor etc,compllete all as specified and as directed by Engineer-in-Charge.
Suppy, installing, connecting, commissioning and testing of energy effficient transformer (level 3 of IS 1180 as per latest amendments of 2014) of capacity 250 KVA outddoor type, mounted on four pole structure, step down 11/0.433 KV, core type oil immersed, copper wound, natural oil cooled with external cooling tubes/radiators, having 3 phase 50 Hz AC supply, DYn-11 design, off load tap changer on HT side to vary secondary voltage ±7.5% in steps of 2.5% as per IS 1180 (Pt-I to III) with all standerd accessories including bushing on HT side, cable box on LT side, including first filling of new transformer oil (of di-electric strength not less than 60 KV) upto required level in conservator tank , complete all as specified and directed by Engineer-in-Charge. with and including the following :- (a) One No 100 mm dia, dial type thermometer with resetting device vapour pressure type having range 0 to 120 degree centigrade. (b) Rating plate and terminal marking plate. (c) Two earthing terminals for body earthing and two additional for neutral brought out on a bushing. (d) Oil level gauge with max & min level marking. (e) Oil filter valve. (f) Oil drain valve.
(g) Lifting hooks. (h) Oil conservator with filling hole and cap. (j) Air relief valve plug. (l) Earth bushing for neutral outside the LT cable box for providing independent earthing for neutral. (m) Clear view type silica gel breather with first fill of fresh bluish color silica gel. Note :- [1] The transformer should be as per level 3 of IS 1180(2014) and energy conservation (Energy conservation Binary Corps) for which necessasry test certificate to be produced by contractor from manufacturer of the transformer. [2] Four pole structure and related items shall be measured and paid separately under respective items. [3] Pre dispatch inspection of transformer shall be carried out by the Rep of Accepting officer. All factory inspeection arrangments will be co-ordinated by the contractor. [4] Transformer shall be tested and commissioned by SEI after installing at site.All the T&P,testing equipments required for the same shall be arranged by the contractor and unit rate quoted will be deemed to included the cost of the same.
Switch air break, triple pole, gang operated (GOD), complete with 12 insulators, drop out fuse unit mechanically operated, mounted on insulators and steel frame, non-ferrous knife and spring loaded contacts, arcing horns of adequate sections to break magnitising current of the transformer, with operating mechanism worked from ground level, for current rating upto 200 Amps, suitable for 11000 volts grade AC supply,complete all as specified and directed by Engineer-in-Charge. Note: All ferrous parts shall be hot dipped galvanised and non-ferrous parts shall be heavily dipped to withstand weather.
Cross arms, bracing, supports, clamps and back plates, fabricated from structural steel section Fe-290 grade E-165 quality including nuts, bolts, washers, and welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of alminium paint over a coat red oxide primer, complete all as specified and directed by Engineer-in-Charge.
Jumpers in red/yellow/blue colour for HT lines/connections made from aluminium conductor single core PVC insulated cable of suitable dia and 1.2 to 2 mtr long complete including winding wires, aluminium tapes etc, complete all as specified and directed by Engineer-in-Charge.
Steel tubular swaged poles complete with mild steel base plate,closed at top as specified, type 410 SP-55(11 metre long) including painting with two coated of black bituminuous paint externally up to the planted depth and internally through out and remaining external portion with two coats of aluminium paint,over a coat of red oxide primer including necessary earth work and PCC 1:4:8 type D-2 in foundation below base plate,PCC1:3:6 type C-1 as in foundation & plinth block incl all type of form work, complete all as specified and as directed by Engineer in charge. Notes : (i) Cost of Transportation of Pole at location shall deemed to be included in the rate quoted by contractor against this item and nothing extra shall be admissible on this account . (ii) Quoted rate of this item is deemed to inclusive cost of all the itmes mentioned therein such as earth work, PCC ,Form work ,finishes including painting etc and nothing extra shall be admissible on this account.
Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole ,complete all as specified and as directed by Engineer in charge.
Lightning arresters expulsion type complete with all fittings, distribution class, discharge capacity 65 Kilo Amps, long duration current impulse to withstand 250AP/2000Seconds & energy dissipation capacity 2KJ/KV, suitable for 11000 volts grade system, fixed in position & tested ,complete all as specified and as directed by Engineer in charge.
Pin type insulator porcelain, vitreous white/brown including one galvanised MS spindle nut and two GI washers of size 150 mm height, 150 mm dia for 11000 volts ,complete all as specified and as directed by Engineer in charge.
Single disc porcelain, vitreous white/brown insulator 255 mm dia and 145 mm height assembly for tension with tension clamps for conductor working pressure 11000 volts,complete all as specified and as directed by Engineer in charge.
Outdoor end termination joint kit (heat shrinkable) complete with jointing material and accessories suitable for 3wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 95 Sqmm size cable in and including jointing & testing ,complete all as specified and as directed by Engineer in charge.
Outdoor end termination joint kit (heat shrinkable) complete with jointing material and accessories suitable for 3 wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 120 Sqmm size cable in and including jointing & testing ,complete all as specified and as directed by Engineer in charge.
Indoor end termination joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 3 wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 95 Sqmm size cable in and including jointing & testing ,complete all as specified and as directed by Engineer in charge.
Cutting chases pinning in, making good to facings where required and pointing in cement mortar 1:2 to ends of edges of landings, steps, cills sunshades, sheleves, lintels, etc; and cutting chases for concealed conduit woiring, etc and making good, cutting not exceeding 10 cm girth in brick walls ,complete all as specified and as directed by Engineer in charge.
Tower type vertical split AC with indoor unit floor mounted and outdoor unit mounted on and including suitable frame operating on single phase 230 volts 50Hz AC supply,rotary type compressor,Eco friendly refrigerent R-32,indoor unit noise level not more than 43 dB, complete with cordless remote control unit and with inbuilt air ioniser and plasma filter for better indoor air quality with max star rating as per manufacture rating and EER 3:2 of capacity 2 TR in and including installation & testing etc ,complete all as specified and as directed by Engineer in charge. Make: Bluestar/ Hitachi/ Daikin/ Voltas.
Earthing complete with Galvanised steel earth plate electrode 600 mm x 600 mm x 6 mm burried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to G I earth strip 4 dia G I wire by means of brass bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 15 mm bore (light grade) connected to main switch board or any other electrical equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 20 mm bore medium grade GI pipe for watering, MS funnel with wire mesh, PCC (1:3:6), type C-1 chamber, with 80 mm thick pit cover of precast RCC (1:2:4), type B-1,reinforced with 8 mm dia TMT bars @ 150mm c/c, both ways with lifting hooks made out of 12 dia ms bar MS handle 12mm dia reinforced XPM of weight not less than 4 kg/ Sqm, complete all as specified and as directed by Engineer-in-Charge. Note :- (i) The unit rate includes earth lead and protection pipe up to maximum 7.5 metre from earth plate to earth point/test point. (ii) Earth pit shall be constructed minimum 0.5 metre away from earth. (iii) Quoted rate of this item is deemed to inclusive cost of all the itmes mentioned therein such as earth work, PCC ,Form work etc and nothing extra shall be admissible on this account .
Earthing complete with galvanised steel plate earth electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25 meter below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to GI strip 25x4mm at two points by means of bolts and nut, check nut and washers including charcoal dust, common salt, necessary excavation in hard/dense soil, returning filling in and removal of surplus soil to a distance up to 50metres, PCC pit in 1:3:6 type CI (using 20mm grade stone aggregate) RCC 1:2:4 type B-1 (using 20mm grade stone aggregate ) 80mm thick pit cover, reinforced XPM of weight not less than 4 kg/ Sqm, complete all as specified and as directed by Engineer-in-Charge, both ways MS handle 12mm dia, GI funnel, wire mesh and GI watering pipe of 20mm bore GI (light grade) and earth lead protection pipe 40mm bore (light grade) all as specified, directed and shown in electrical plate No 3 of SSR Part-I and testing , complete all as specified and as directed by Engineer-in-Charge. Note :- (i) The unit rate includes earth lead and protection pipe up to maximum 7.5 metre from earth plate to earth point/test point. (ii) Earth pit shall be constructed minimum 0.5 metre away from earth. (iii) Quoted rate of this item is deemed to inclusive cost of all the itmes mentioned therein such as earth work, PCC ,Form work etc and nothing extra shall be admissible on this account .
Earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick burried directly in ground vertically (depth of pit not less than 2.25 m below normal ground level), with top edge of earth plate not less than 1.5 m below normal ground level, earth plate surrounded from all sides by 15cm thick packed alternate layers of charcoal dust and common salt, electrode connections using galvanized iron strip of size 32mmx6mm thick (upto body of equipment) by means of nuts, bolts, check nuts & GI washers, connected to main switch board or main control board or test point, protected by galvanized iron pipe light grade 40mm dia bore, and watering pipe 20 mm bore GI light grade pipe with funnel & wire mesh, including all necessary excavation & earth work, PCC chamber in PCC (1:2:4) type B-1 & RCC cover, all as shown in electrical plate No 3 of MES Schedule Part-I (2009), testing on completion, ,complete all as specified and as directed by Engineer in charge. Note(s) :- (i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm. (ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit. (iii) Rate shall include GI strip and protection pipe of length 7.5m, GI pipe beyond 7.5m length required at site shall be measured and paid separately. (iv) Earth resistance should be less than 3 Ohm. In case the test results are not found below 3 Ohm, complete earthing will be redone without any extra cost to Govt.
Supply, installation, testing and commissioning of LT panel board (CPRI Approved) of suitable size factory made, compartment type, dust, water and vermin proof duly powder coated, indoor type suitable for 1100 volts grade, 3 phase, 4 wire supply, floor mounted fabricated out 2 mm thick CRCA Sheet on 50mm X 50mm X 6mm angle iron frame, angle iron legs 04 Nos of suitable length for grouting in floor with cement concrete PCC foundation of suitable size in 1:2:4 and with provision of all incoming/outgoing cable entries along with suitable size of double compression type cable gland for incomming & out going cable all as specified and comprising the following:-
Note :Schedule of credit to be deducted on acceptances of bid.Details of Schedule of credit is given in tender documentse.
M/s badrinath Traders (BID ID -3193851)
M/s APEX ENTERPRISES (BID ID -3194124)
BANSAL ENGINEERING (BID ID -3199883)
HARISH SALES CORPORATION (BID ID -3200155)
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .