| Sl No | Description | Qty | Unit | M/s Luxmi Constructions L6 | M/s BHUPINDRA ENGINEERING WORKS L1 | R.J.Enterprises L2 | Truly Technos LLP L3 | ANANT ENTERPRISES L4 | Rasvinderpalandco L5 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches not exc. 1.5 m wide and not exceeding 1.5m depth for foundation of poles/laying of cables/ stay/ strut etc not exceeding 10 Sq m on plan and getting out in soft/loose soil, complete all as specified and directed by Engineer in charge. | 621.81 | CUBIC METRE | 99 ₹61,559.19 | 80 ₹49,744.8 Lowest | 150 ₹93,271.5 | 90 ₹55,962.9 | 120 ₹74,617.2 | 80 ₹49,744.8 Lowest |
| 2.00 | Returning, filling including spreading, leveling watering and well ramming in layers not exceeding 25 cm, complete all as specified and directed by Engineer in charge. | 284.72 | CUBIC METRE | 45 ₹12,812.4 | 15 ₹4,270.8 Lowest | 80 ₹22,777.6 | 25 ₹7,118 | 30 ₹8,541.6 | 40 ₹11,388.8 |
| 3.00 | Removing excavated material (soil) n.exc 50m and depositing where directed at a level not exceeding 1.5 mtr above the starting point, complete all as specified and directed by Engineer in charge. | 337.09 | CUBIC METRE | 54 ₹18,202.86 | 15 ₹5,056.35 Lowest | 80 ₹26,967.2 | 35 ₹11,798.15 | 30 ₹10,112.7 | 40 ₹13,483.6 |
| 4.00 | M&L for river sand as in sand cushioning to under ground cable including punning down of thickness 180mm sand in layers, complete all as specified and directed by Engineer in charge. | 238.36 | CUBIC METRE | 630 ₹1,50,166.8 | 320 ₹76,275.2 Lowest | 1,000 ₹2,38,360 | 700 ₹1,66,852 | 350 ₹83,426 | 435 ₹1,03,686.6 |
| 5.00 | M&L for brick protection cover of UG cable by old size bricks common burnt clay building bricks sub class `B’ laid dry and flat abutting each other with width equal to length of brick and gap between adjacent brick not exceeding 10mm, complete all as specified and directed by Engineer in charge. | 17.38 | 1000 NOS | 4,860 ₹84,466.8 | 2,800 ₹48,664 Lowest | 4,500 ₹78,210 | 8,800 ₹1,52,944 | 4,500 ₹78,210 | 5,200 ₹90,376 |
| 6.00 | M&L for making bore below the road for crossing the GI pipe light grade 50 mm dia for cable protection and fill the putty on both sides of the GI pipe after crossing the armoured cable to avoid the water inside, complete all as specified and directed by Engineer in charge. | 48 | RUNNING METRE | 198 ₹9,504 | 200 ₹9,600 | 100 ₹4,800 Lowest | 250 ₹12,000 | 100 ₹4,800 Lowest | 230 ₹11,040 |
| 7.00 | M&L for making bore below the road for crossing the GI pipe light grade 80 mm dia for cable protection and fill the putty on both sides of the GI pipe after crossing the armoured cable to avoid the water inside, complete all as specified and directed by Engineer in charge. | 18 | RUNNING METRE | 243 ₹4,374 | 200 ₹3,600 | 100 ₹1,800 Lowest | 300 ₹5,400 | 130 ₹2,340 | 230 ₹4,140 |
| 8.00 | M&L for GI pipe 80 mm dia, 'light grade', galvanised, with all fitting; laid in trenches, complete all as specified and directed by Engineer in charge. | 18 | RUNNING METRE | 495 ₹8,910 | 500 ₹9,000 | 500 ₹9,000 | 730 ₹13,140 | 800 ₹14,400 | 475 ₹8,550 Lowest |
| 9.00 | M&L for GI pipe 50 mm dia, 'light grade', galvanised, with all fitting laid in trenches including taking out of old rusted GI pipe, complete all as specified and directed by Engineer in charge. | 48 | RUNNING METRE | 396 ₹19,008 | 400 ₹19,200 | 400 ₹19,200 | 480 ₹23,040 | 1,000 ₹48,000 | 275 ₹13,200 Lowest |
| 10.00 | M&L for taking down unserviceable LT UG cable any type from trenches and removing the fault and relaying of LT UG cable after rectifying the fault and making cable in serviceable condition of 1100 V grade UG cable of size from 185 to 240 sq mm, 3½ core including relaying of bricks and sand, complete all as specified and directed by Engineer in charge.
Note:-
(a) straight through joints measure and paid separately )
(b) Excavation, Returning, filling, removal, will be measured and paid separately. | 500 | RUNNING METRE | 45 ₹22,500 | 30 ₹15,000 Lowest | 60 ₹30,000 | 40 ₹20,000 | 50 ₹25,000 | 35 ₹17,500 |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
6 Aug 2025, 6:00 pmClosed
GE (AF) BHISIANA
GE (AF) BHISIANA PIN - 151201
REPAIR/ REPLACEMENT/ MAINT OF LT DISTRIBUTION SYSTEM ALONGWITH ALLIED WORK IN DOMESTIC AREA AND E/M ITEMS INCLUDING EOT CRANE IN WSA AT AF STN BHISIANA
2025_MES_718967_1
GE/BHI/T-89/2025-26
Open Tender
Civil Works
Item Rate
273 days
GE (AF) BHISIANA
Please refer Tender documents.
10 documents required · 10 mandatory
₹500
GE (AF) BHISIANA
₹90,000
Yes
18 Sept 2025
7 Jul 2025
8 Aug 2025
7 Jul 2025
6 Aug 2025
23 Jul 2025
7 Jul 2025 - 14 Jul 2025
Amount
Excavation in trenches not exc. 1.5 m wide and not exceeding 1.5m depth for foundation of poles/laying of cables/ stay/ strut etc not exceeding 10 Sq m on plan and getting out in soft/loose soil, complete all as specified and directed by Engineer in charge.
Returning, filling including spreading, leveling watering and well ramming in layers not exceeding 25 cm, complete all as specified and directed by Engineer in charge.
Removing excavated material (soil) n.exc 50m and depositing where directed at a level not exceeding 1.5 mtr above the starting point, complete all as specified and directed by Engineer in charge.
M&L for river sand as in sand cushioning to under ground cable including punning down of thickness 180mm sand in layers, complete all as specified and directed by Engineer in charge.
M&L for brick protection cover of UG cable by old size bricks common burnt clay building bricks sub class `B’ laid dry and flat abutting each other with width equal to length of brick and gap between adjacent brick not exceeding 10mm, complete all as specified and directed by Engineer in charge.
M&L for making bore below the road for crossing the GI pipe light grade 50 mm dia for cable protection and fill the putty on both sides of the GI pipe after crossing the armoured cable to avoid the water inside, complete all as specified and directed by Engineer in charge.
M&L for making bore below the road for crossing the GI pipe light grade 80 mm dia for cable protection and fill the putty on both sides of the GI pipe after crossing the armoured cable to avoid the water inside, complete all as specified and directed by Engineer in charge.
M&L for GI pipe 80 mm dia, 'light grade', galvanised, with all fitting; laid in trenches, complete all as specified and directed by Engineer in charge.
M&L for GI pipe 50 mm dia, 'light grade', galvanised, with all fitting laid in trenches including taking out of old rusted GI pipe, complete all as specified and directed by Engineer in charge.
M&L for taking down unserviceable LT UG cable any type from trenches and removing the fault and relaying of LT UG cable after rectifying the fault and making cable in serviceable condition of 1100 V grade UG cable of size from 185 to 240 sq mm, 3½ core including relaying of bricks and sand, complete all as specified and directed by Engineer in charge. Note:- (a) straight through joints measure and paid separately ) (b) Excavation, Returning, filling, removal, will be measured and paid separately.
M&L for taking down unserviceable LT UG cable any type from trenches and removing the fault and relaying of LT UG cable after rectifying the fault and making cable in serviceable condition of 1100 V grade UG cable of size from 70 to120 sq mm, 3½ core including relaying of bricks and sand, complete all as specified and directed by Engineer in charge. Note:- (a) Straight through joints measure and paid separately (b) Excavation, Returning, filling, removal, will be measured and paid separately.
M&L for taking down unserviceable LT UG cable any type from trenches and removing the fault and relaying of LT UG cable after rectifying the fault and making cable in serviceable condition of 1100 V grade UG cable of size from10 to 50 sq mm, 2 to 4 core including relaying of bricks and sand, complete all as specified and directed by Engineer in charge. Note:- (a) Straight through joints measure and paid separately (b) Excavation, Returning, filling, removal, will be measured and paid separately.
Taking down LT cable 1100 Volts grade heavy duty UG cable XLPE/PVC of size from 185 to 240 sq mm, 3½ core, complete all as specified and directed by Engineer in charge.
Taking down LT cable 1100 Volts grade heavy duty UG cable XLPE/PVC of size from 70 to 150 sq mm, 3½ core, complete all as specified and directed by Engineer in charge.
Taking down LT cable 1100 Volts grade heavy duty UG cable XLPE/PVC of size from 10 to 50 sq mm, 2 to 4 core, complete all as specified and directed by Engineer in charge.
Supply, laying, jointing and testing in replacement XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 240 Sq mm 3.5 Core with aluminium thimble of same size, complete all as specified and directed by Engineer in charge.
Supply, laying , jointing and testing in replacement XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 185 Sq mm 3.5 Core with aluminium thimble of same size, complete all as specified and directed by Engineer in charge.
Supply, laying ,jointing and testing in replacement XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 120 Sq mm 3.5 Core with aluminium thimble of same size, complete all as specified and directed by Engineer in charge.
Supply, laying , jointing and testing in replacement XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 95 Sq mm 3.5 Core with aluminium thimble of same size, complete all as specified and directed by Engineer in charge.
Laying, jointing and testing in replacement XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 70 Sq mm 3.5 Core with aluminium thimble of same size, complete all as specified and directed by Engineer in charge.
Supply, laying , jointing and testing in replacement XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 50 Sq mm 3.5 Core with aluminium thimble of same size, complete all as specified and directed by Engineer in charge.
Supply, laying , jointing and testing in replacement XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 35 Sq mm 3.5 Core with aluminium thimble of same size, complete all as specified and directed by Engineer in charge.
Supply, laying , jointing and testing in replacement XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 25 Sq mm 3.5 Core with aluminium thimble of same size, complete all as specified and directed by Engineer in charge.
Supply, laying , jointing and testing in replacement XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 16 Sq mm 4 Core with aluminium thimble of same size, complete all as specified and directed by Engineer in charge.
Supply, laying , jointing and testing in replacement XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 10 Sq mm 4 Core with aluminium thimble of same size, complete all as specified and directed by Engineer in charge.
M&L for cable jointing kit for 1100 volts grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 35 to 95 sqmm, complete all as specified and directed by Engineer in charge.
M&L for cable jointing kit for 1100 volts grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 120 to 150 sqmm, complete all as specified and directed by Engineer in charge.
M&L for cable jointing kit for 1100 volts grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size185 to 240sqmm, complete all as specified and directed by Engineer in charge.
M&L for Plain cement concrete 1:3:6, type C-1 (using 20 mm graded stone aggregate) for copping of poles Pedestal (PCC), complete all as specified and directed by Engineer in charge.
S&F in replacement of MCCB 63 Amps, 4 Pole 16 KA with thermal magnetic settings by dismantling old one from panel/feeder pillar box, complete all as specified and directed by Engineer in charge.
S&F in replacement of MCCB 100 Amps, 4 Pole 16 KA with thermal magnetic settings by dismantling old one from panel/feeder pillar box, complete all as specified and directed by Engineer in charge.
S&F in replacement of MCCB 125 Amps, 4 Pole 16 Ka with thermal magnetic settings by dismantling old one from panel/feeder pillar box, complete all as specified and directed by Engineer in charge.
S&F in replacement of MCCB 160 Amps, 4 Pole 16 Ka with thermal magnetic settings by dismantling old one from panel/feeder pillar box, complete all as specified and directed by Engineer in charge.
S&F in replacement of MCCB 200 Amps,4 Pole 25/26KA Ka with thermal magnetic settings by dismantling old one from panel/feeder pillar box, complete all as specified and directed by Engineer in charge.
Supply and fix in replacement of MCCB 250 Amps, 4 Pole 25/26 KAwith thermal magnet settings by dismantling old one from panel/feeder pillar box, complete all as specified and directed by Engineer in charge.
S&F in replacement of MCCB 315 Amps,4 Pole 25/35KA with thermal magnetic settings by dismantling old one from panel/feeder pillar box, complete all as specified and directed by Engineer in charge.
S&F in replacement of MCCB 400 Amps, 4 Pole 36/37 KA with thermal magnetic settings by dismantling old one from panel/feeder pillar box, complete all as specified and directed by Engineer in charge.
S&F in replacement of Aluminium Thimble of size 300 Sqmm.
S&F in replacement of Aluminium Thimble of size 240 Sqmm.
S&F in replacement of Aluminium Thimble of size 185 Sqmm.
S&F in replacement of Aluminium Thimble of size 150 Sqmm.
S&F in replacement of Aluminium Thimble of size 120 Sqmm.
S&F in replacement of Aluminium Thimble of size 95 Sqmm.
S&F in replacement of Aluminium Thimble of size 70 Sqmm.
S&F in replacement of Aluminium Thimble of size 50 Sqmm.
S&F in replacement of Aluminium Thimble of size 35 Sqmm.
S&F in replacement of Aluminium Thimble of size 25 Sqmm.
S&F in replacement of Aluminium Thimble of size 16 Sqmm.
S&F in replacement of Aluminium Thimble of size 10 Sqmm.
S&F in replacement of Aluminium Thimble of size 6 Sqmm.
M&L for preparation of old steel surfaces including welding work of door, hinges with locking arrangement and applying one coat of synthetic enamel ivory paint/ (Smoke grey) to steel LT Panel/bus bar box and junction boxes surface after disconnecting the electrical connections and reconnecting LT cables after painting, complete all as specified and directed by Engineer in charge. Note:- The contractor shall be fully responsible for the safety of his men engaged for executing this work and he will provide all requisite safety equipments and clothing to his men and department shall not be responsible for any mishappening/ accident/ injury to his men.
S&F in replacement of sheet metal (MS) bus bar box floor mounted single door, outdoor type weather proof, size 300x300x200mm mounted on ground with iron angles (25x25x4mm) having aluminium bus bar 4 nos, rated 100amp including suitable PCC grouting, complete all as specified and directed by Engineer in charge. Note:- Cost of foundation work is included in rate quoted by contractor.
M&L for servicing of LT panel of any size. Including disconnecting of supply, removing brunt out wires, cable joints, thimbles, MCCB and bus bar Including supply of copper wires, thimbles, rejointing of any size cable with bus bar and mccb properly. Cables of damaged PVC insulation will rejoint after removing damaged piece of cable and making new joint, complete all as specified and directed by Engineer in charge.
Supply, installing testing and commissioning in replacement of factory made and tested (Including CPRI test citified) outdoor type floor mounted LT panel board with top canopy , cubical type suitable for 415 Volts 3 phase, 4 wire 50Hz, Ac supply system having busbar chamber with insulated AL busbar of rating 1.5 times the incomer MCCB for phase installed on porcelin/SMC insulators. The panel shall be dust and vermin proof IP-64 class protection and made out of 3.15 mm thick CRCA MS sheet and angle iron frame 40x 40x 6mm thick frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coat of red oxide primer, front and back opening type with approaches for cable entry with double door shutter and locking arrangements including internal wiring with PVC insulated stranded copper conductor cable FRLS IS 694 sheathed 1100V grade of appropriate size comprising of following:-
Supply, installing testing and commissioning in replacement of factory made and tested (Including CPRI test citified) indoor type floor mounted LT panel board, cubical type suitable for 415 Volts 3 phase, 4 wire 50Hz, Ac supply system having busbar chamber with insulated AL busbar of rating 1.5 times the incomer MCCB for phase installed on porcelin/SMC insulators. The panel shall be dust and vermin proof IP-64 class protection and made out of 3.15 mm thick CRCA MS sheet and angle iron frame 40x 40x 6mm thick frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coat of red oxide primer, front and back opening type with aproaches for cable entry with double door shutter and locking arrangements including internal wiring with PVC insulated stranded copper conductor cable FRLS IS 694 sheathed 1100V grade of appropriate size comprising of following:-
S&F in repair MCB DB TPN 4 Way vertical type factory made IP 43 protection class metal double door with Shrouded Neutral Bar & Pan assembly with connecting link complete including one MCCB upto 125A after dismantling old one, complete all as specified and directed by Engineer in charge.
S&F in repair on load change over switch 400 amp 4 pole,415 V,50 Hz in sheet steel enclosure for surface mounting with padlocking facility with the connecting accessories, complete all as specified and directed by Engineer in charge.
S&F in repair on load change over switch 250 amp 4 pole,415 V,50 Hz in sheet steel enclosure for surface mounting with padlocking facility with the connecting accessories, complete all as specified and directed by Engineer in charge.
M&L for danger notice board/plate of 1.6mm thick mild steel sheet vitreous enamelled white with letter, figures and conventional skull and bones in signal red colour and fixed with MS clamps, nuts and bolts of approved size of HT 25 x 20 cm size, complete all as specified and directed by Engineer in charge.
M&L for Dismantling/disconnection of LT connections from ACB by taking down proper shutdown, opening the ACB (Panel) installed at various locations for servicing, overhauling all moving contacts, fixed contacts, tripping coil including testing the insulation value of moving and fixed contacts and cleaning the carbon from contact point with petrol etc and greasing oiling the all moving parts including testing all meters/relay such as under voltage relay and servicing, shut trip coil etc including reassembling the ACB including testing after completion, complete all as specified and directed by Engineer in charge. Note : Complete servicing and maintenance will be carried out at site only
M&L for Dismantling of old unsv PCC poles of any size /type carefully and removing from site in parts or whole, complete all as specified and directed by Engineer in charge. Note :- All T&P items deemed necessary to carry out dismantling and removing the old PCC pole are included in the overall cost quoted
S&F bracket for street light fitting made out of 40 mm dia GI pipe light grade 1.2 mtr long each bent to required shape & size as directed by EIC & fixed to pole with and including flat iron clamps 02 Nos made out of 32 x 6 mm flat iron including GI nuts, bolts & washer and painting of clamps andstreet light firtting bracket with one coat of red oxide primer, one under coat and one finishing coat with aluminium paint, complete all as specified and directed by Engineer in charge.
M&L for all steel tubular swaged poles type 410-SP-31 (09 mtr long) with mild steel base plate of size 30cmx30cmx6mm thick, welded at bottom and cap finial taper plugs, bolt, nuts and screw as specified and fixed in true vertical position complete. Note:- (a) Excavation earth work, foundation concrete shall be measured and paid separately under respective items. (b) Poles shall be painted with two coats of black bituminous paint throughout internally and externally up to planting depth. The remaining portion of the exterior surface shall be painted with two coats of aluminium paint over a coat of red oxide primer. (c) Test certificate and purchase vouchers will be submitted.
M&L for earthling with steel earth plate electrode of size 60x60cmx6mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less tha 1.5 mtr deep below normal grund level connected to galvanized iron strip size 32 x 6 mm as earthing lead by means of nuts, bolts and washers of steel after welding of GIstrip to earth electrode to the full length of earht plate, 40mm dia GI tubing lightgrade protection pipe upto test point, 20mm dia GI watering pipe with funnel and wire mesh, PCC pit 1:3:6 with pit cover ofsize 30x30 cm made of RCC 1:3: with suitable handle, angle iron frame made of angle iron of size 40x40x4m, adequate qty of charcoal dust and salt layers all around the earth plate and filling of vegetables soil to the remaining 10% removal of surplus soil and returning filling in all as required at site including test point made outof steel plate of size 75x75x6mm fixed to wall all as specified in plate No 3 of SSR Part-I, complete all as specified and directed by Engineer in charge.
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6.3 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level,the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15cm on all side and including connected toand including galvanized earth lead wire 4.0 mm dia upto 7.5 mtrs long by means of nuts and bolts, check nuts and washers of GI and connected to earhing test point and earth dolly all as shown in electrical plate No 3 of MES SSR part I and testing on completion including necessary excavation and earth work in any type of soil,PCC (1:3:6) type C1 chamber,pre-cast RCC slab 50mm thic in cement concrete (1:2:4), type B1, reinforced with welded steel wire fabric or XPM, (weight not less than 4 Kg per Sqm) with cast iron frame,funnel with watering pipe 20mm dia medium grade,wire mesh and lugs, GI protection pipe,15mm dia, light grade, 7.5 mtr long for protection of earth lead upto test point etc, complete all as specified and directed by Engineer in charge.
S&F ISI marked self adhesive PVC electrical insulation Tape roll of 25 mm wide, 0.125 mm thick and 25 RM length, complete all as specified and directed by Engineer in charge.
M&L for shifting of LT panel after disconnecting all cable connections and earthing strip from one location to another location and reconnecting all the cables with proper thimbles and connecting earthing strips to the panel, complete all as specified and directed by Engineer in charge. Notes:- 1. Cost of T&P involved is included in the quoted rate. 2. Thimbles and extra strip to be paid in separately.
Dismantling of old u/s earthing complete with accessories, complete all as specified and directed by Engineer in charge.
Dismantling of old u/s borewell earthing complete with accessories, complete all as specified and directed by Engineer in charge.
M&L for commissioning, installation and testing of maintenance free UL approved copper bonded earth rod of 10 feet length, 17.2 mm dia. (as per drg) made of high tensile low carbon steel rod , molecularly bonded with 99.9% electrolytic grade copper on outer surface (minimum copper bonding thickness - 250 microns) with exothermally jointed copper bus bar of 50 X 6 X 200 mm for connection. The rod and exothermic joint together successfully tested at 25 KA fault current by CPRI with 50 Kg eco friendly earth enhancing compound with each earth rod. The earth pit should be 125 mm dia. the compound should comply to IEC:62561-7 having passed leaching, corrosion, sulphur and resistivity test as per IEC: 62651-7 by NABL accredit Lab with FRP earth pit cover of top size lockable Lid. It includes GI Protection pipe light grade of size 40 mm dia. with GI strip of size 32X6 mm upto test point, complete all as specified and directed by Engineer in charge. Note:- GI Strip connecting between two earthing will be measured and paid separately in respective item.
M&L for Earthing complete with galvanized steel earth plate electrode 600mmx600mmx6mm thick buried directly in ground (earth) pit not less than 2.25 meter deep below normal ground level) with top edge of earth plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts check nuts and washers of galvanized iron or steel all as shown in electrical palte No 3 of SSR Pt-I connected earthing test point/panel all as specified including GI PCC earth chamber using PCC (1:3:6) Type C-2 (using 40 mm graded stone aggregate), 50mm thick cast iron frame with CI cover, funnel and wire in mesh excavation and earth work, complete all as specified and directed by Engineer in charge. Note: Pipe/strip upto 7.5 mtrs also included in quoted rate.
M&L for Earthing complete with galvanized steel earth plate electrode 600mmx600mmx6mm thick buried directly in ground(earth) pit not less than 2.25 meter deep below normal ground level) with top edge of earth plate not less than 1.5mtr below normal ground level connected to galvanized earth strip of size 25 mm x 4 mm by means of bolts, nuts check nuts and washers of galvanized iron or steel all as shown in electrical palte No 3 of SSR Pt-I connected earthing test point/panel all as specified including PCC earth chamber using PCC (1:3:6) Type C-2 (using 40mm graded stone aggregate),50mm thick cast iron frame with CI cover, funne and wire in esh excavation and earth work, complete all as specified and directed by Engineer in charge. Note: Pipe/strip upto 7.5 mtrs also included in quoted rate.
M&L for Earthing complete with copper plate 60×60cm×3.15mm thick electrode, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to 20×3 mm copper strip by means of bolts, nuts check nuts and washers of galvanized iron or steel all as shown in electrical palte No 5 of SSR Pt-I connected earthing test point/panel all as specified including PCC earth chamber using PCC (1:3:6) Type C-2 (using 40mm graded stone aggregate), 50mm thick cast iron frame with CI cover, funne and wire in esh excavation and earth work, complete all as specified and directed by Engineer in charge. Note: Pipe/strip upto 7.5 mtrs also included in quoted rate
M&L for checking earthing resistance value of any type of earthing chemical/ conventional by disconnecting the earthing connection and measuring the resistance value using earth resistance meter and taking down reading in register with signature from user unit, JE E/M and Engineer-in-charge. Note: Penalty shall be imposed for each job @ Rs 50/- for delaying the checking of earthing within the one day for one earth, complete all as specified and directed by Engineer in charge.
M&L for Borewell Earthing by drilling 6" dia bore hole with DTH bore machine and in any type of strata providing 50 mm dia medium duty GI pipe duly drilled all around 15mm dia hole at a distance of 200mm from hole to hole upto 30 meter depth and providing charcol/ salt mixture all around the pipe and connecting top edge of pipe with galvanised earth strip of size 32 x 6mm upto 7.5 meter upto test point including PCC earth chamber using PCC (1:3:6) Type C-2 (using 40mm graded stone aggregate), 50mm thick cast iron frame with CI cover, funnel and wire in esh excavation and earth work, complete all as specified and directed by Engineer in charge. Note :- Quoted rated are deemed to include suitable size PCC pit cast iron frame with CI cover, funnel of suitable size and providing 6" dia MS pipe medium grade upto 3 mtr depth from top level, Earth results should not be more than 1 (one ) Ohm.
M&L for removing earthing rod/plate from earthing pit alongwith old salt charcoal mixture/ chemical and re-filling the earth pit with new salt charcoal mixture/ chemical to recharge the earthing pit and refixing the complete earthing set, complete all as specified and directed by Engineer in charge. Note :- (i) Salt charcoal mixture/ Chemical compound to be supplied and paid separately in below mentioned items. (ii) Cost of excavation/T&P shall be deemed to be included in the overall rate quoted by contractor
Charcoal powder and chips suitable for electrical earthing, complete all as specified and directed by Engineer in charge.
Salt suitable for electrical earthing, complete all as specified and directed by Engineer in charge.
Electrical earthing grade bentonite powder, complete all as specified and directed by Engineer in charge.
Taking down carefully copper/ Aluminium strip including (porcelin cleat, PCC slabs, nuts and bolts complete etc) removing materials from site and making good disturbed surfaces of ground, walls, roofs etc, complete all as specified and directed by Engineer in charge.
M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required of size 20x3 mm copper strip, complete all as specified and directed by Engineer in charge. Note- Porcelin cleat and PCC slab deemed tobe included in quoted rate
All as per item No 81 above but for GI strip of size 25x4 mm, complete all as specified and directed by Engineer in charge.
All as per item No 81 above but for GI strip of size 32x6 mm, complete all as specified and directed by Engineer in charge.
All as per item No 81 above but for Al strip of size 25x3 mm, complete all as specified and directed by Engineer in charge.
All as per item No 81 above but for copper strip of size 32x6 mm, complete all as specified and directed by Engineer in charge.
M&L for earth pit cover bucket type Red or Green, complete all as specified and directed by Engineer in charge.
M&L for precast earthing RCC pit with cover plate of standard size duly painted in Red or Green, complete all as specified and directed by Engineer in charge.
M&L for CI plate triangular plate with 500 mm long spike for writing earthing name and value, complete all as specified and directed by Engineer in charge.
M&L for plain cement concrete 1:3:6 type C-1 (using 20 mm graded stone aggregate) for damaged earth pit chamber with fair finish internal surface of concrete chamber of earth, complete all as specified and directed by Engineer in charge.
M&L for Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw including necessary cutting and welding wk, complete all as specified and directed by Engineer in charge.
Dismantling of old air termination rod of any type complete with accessories, complete all as specified and directed by Engineer in charge.
Refixing of air termination rod obtained from dismantling after stretching, cleaning, complete all as specified and directed by Engineer in charge.
S&F in replacement air termination copper rod 12 mm dia 300 mm long, complete all as specified and directed by Engineer in charge.
S&F air termination single pointed aluminium rod 12 mm dia 300 mm long in replacement, complete all as specified and directed by Engineer in charge.
M&L for Relaying of GI strips obtained from taking down complete after stretching, bent to straight including providing porcelin cleat, brazing, nuts bolts where as required, complete all as specified and directed by Engineer in charge.
M&L for Relaying of copper strips obtained from taking down complete after stretching, bent to straight including providing porcelin cleat, brazing , nuts bolts where as required, complete all as specified and directed by Engineer in charge.
S&F epoxy based insulator of different shape size suitable for fixing GI/ Copper strip, complete all as specified and directed by Engineer in charge.
M&L in repair Pre-cast cement concrete block masonry with solid blocks PCC Type B1 1:2:4 (using 20 mm graded aggregate), exc. 10 cm in width and setting in mortar in CM 1:6, complete all as specified and directed by Engineer-in-charge
M&L for preventive maintenance of existing EOT crane at height of 20 to 22 Metre (Approx) from representative of firm as approved by GE Including. (i) dismantling of hoisting gear box. (ii) drain of old oil. (iii) Cleaning & Greasing of gear box long travel and cross travel and refilling of fresh oil. (iv) Fill up fresh oil in gear box. (v) Checking of hoisting, long travel, cross travel, brake unit, oiling of brake unit pins. greasing of long travel cross travel wheel bearing, checking of panel board and connections, checking of rail alignment, checking of cross travel alignment. checking and oiling greasing of wire rope, rope drum, pedstal bearings, load test using dead weight and any minor defects all connections Electrical/ Mechanical components, Including any minor repair deemed to be included in the above quoted rate, complete all as specified and directed by Engineer in charge. NOTE:- (i) All Work shall be executed in presence of contractor, he will be solely responsible for safety of working personels at site. (ii) Contractor shall provide necessary T&P, safety Equipments oil, grease, gear box oil, cloth waste and minor spare required and any other Material required for execution will be deemed to be in quoted unit rate. (iii) Approval of the firm shall be taken from GE before works commencement.Testing company shall be one from the OEMs TIB udhyog/Cranex/Rockwell or equivalent (iv) Load Test report for each EOT crane shall be generated signed by the the contractor and submitted to the AGE E/M office.
S&F PVC insulated Multi Stranded Copper Conductor Cable 6 Sqmm 4 Core, Round Flexible for connection with circuit including taking down unserviceable Cable of any description, complete all as specified and as directed.
S&F PVC insulated Multi Stranded Copper Conductor Cable 4 Sqmm 3 Core, Round Flexible for connection with circuit including taking down unserviceable Cable of any description, complete all as specified and as directed by Engineer in Charge.
S&F PVC insulated Multi Stranded Copper Conductor Cable 1.5 Sqmm 3 Core, Round Flexible for connection of Street Light Fitting with Bus Bar and flexible conduit including taking down unserviceable Cable of any description, complete all as specified and directed by Engineer in charge.
M&L in replacement for highly efficient LED Flood light 90 watt luminaries new generation energy saving & environment friendly with lens made of pressure die cast aluminium alloy housing LM24 for gear and exturded alluminium lamp housing & enclouser with toughened glass with IP-66 of protection class,with high power LEDs as light source having luminous efficiency should be > 80Lm/w with active power factor correction (APFC) electronic gear (Heat shrink for better heat transmission). It shall have epoxy powder coated grey finish phosphochromate treatment and operating voltage range should be fron 120 volt to 270 volt AC and frequency range 50Hz and suitable for an ambient temparature from -40°C to 50 °C and humidity level 10% to 90% including connection with PVC unsheathed wire aluminium conductor 3 x 1.5sqmm fitted on pole/building with GI bracket of suitable size and connection with 2.5 sqmm 3 core wire upto bus bar of OH line/PVC Jn box/ LT panel /building for connection including taking down of unserviceable light fitting of any type/size, complete all as specified and directed by Engineer in charge. Bajaj Cat Part No. ENXT P108L WH CR TG SD or equivalent as approved by Engineer-in-Charge.
M&L for servicing and maintenance of high mast pulley and GI wire rope system oilling, greasing etc for smooth functioning of the lowering mechanish, complete all as specified and directed by Engineer in charge.
M&L for rewinding of 0.5 Hp to 1 HP motor of high mast, complete all as specified and directed by Engineer in charge.
M&L for stainless steel wire rope with Grade/ construction: AISI 316, 7/19 construction Number of ropes: 2/3 Wire Rope having Diameter (mm): 6 mm suitable for Breaking load capacity: 2350 kg x 2, complete all as specified and directed by Engineer in charge.
All as per item No No. 05 but Reusing old bricks, complete all as specified and directed by Engineer in charge.
R.J.Enterprises (BID ID -3384713)
Truly Technos LLP (BID ID -3374916)
ANANT ENTERPRISES (BID ID -3377803)
Rasvinderpalandco (BID ID -3377197)
M/s Luxmi Constructions (BID ID -3381096)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .