CWE, HQ 134 Wks Engr
CWE, HQ 134 Wks Engr PIN-914134 c/o 56 APO
REPAIR/ MAIINT OF 11 KV AND 33 KV HT ELECT INSTALLATIONS INCL CONNECTED ITEMS SUCH AS TRANSFORMERS, VCBS, AVR, CT/PT, GOD, DO FUSES, CONTROL CABLES ETC AT MANASBAL, SONAMARG, HAWS AND GUND UNDER GE 970 EWS
2022_MES_562714_1
134 WE-61(T)/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Srinagar
9 documents required · 9 mandatory
₹500
GE 970 EWS
₹80,000
Yes
16 Mar 2023
12 Nov 2022
12 Dec 2022
12 Nov 2022
10 Dec 2022
27 Nov 2022
12 Nov 2022 - 19 Nov 2022
Amount
Excavation in trenches in hard/dense soil, not exc 1.5 mtr wide and not exc 1.5 mtr in depth for laying of cables/errection of pole etc, complete all as specified and directed.
Excavation in trenches in hard/dense soil, not exc 1.5 mtr wide and exc 1.5 mtr but not exc 3.0 mtr in depth for laying of cables/errection of pole etc, complete all as specified and directed.
Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exc 25cm thick, complete all as specified and directed.
Removing excavated soil to a distance not exc 1.5 mtr above the starting point and deposting where directed at a level, complete all as specified and directed.
M&L for dry river sand, laid in trenches for cable protection, as 15cm thick below the cable and 8cm thick above the cable, complete all as specified and directed. Note :- Punned thickness of sand shall be measured & paid.
Supplying and Laying reinforced precast concrete cable cover, lass HV, type-1, flat, of size 300x180x40mm, complete all as specified and directed.
M&L for replacement of 80mm bore GI tubing, medium grade, laid in trenches, road crossing, cable protection or fixed to walls with clamps, complete all as specified and directed.
All as per Ser item No 7.00 here-in-before but 100mm bore pipe.
M&L for PCC 1:4:8, type D-2 (using 40mm graded stone aggregate) as in foundation, mass concrete etc including necessary form work, complete all as specified and directed.
M&L for PCC 1:3:6, type C-1 (using 20mm graded stone aggregate) as in coping etc including necessary form work, complete all as specified and directed.
M&L for 40mm graded coarse aggregate (broken stone or boulders), laying in sub - station yard, complete all as specified and directed.
M&L for PCC 1:3:6 type C-2 (using 40mm graded stone aggregate) as in filling and mass concrete of pole, cutting of road etc, complete all as specified and directed.
Dismantling old and unserviceable prestressed concrete / steel poles of any type including breaking cement concrete complete and S&F and erection of steel tubular swaged pole with cast iron base plate finial tapper plug, bolts, nuts and screws and specified type 410-SP-55 (11mtr long) in truly vertical position, 1.5 mtr length of pole above ground level shall be painted with two coats of synthetic enamel paint in strips of 30cm width, black and yellow alternatively and painting with two coats of aluminum paint over a coat of red oxide primer on rest part of pole and its connected parts, complete all as specified and directed. Note :- Earth work and PCC shall be measured and paid seperately under respective items of BOQ.
Dismantling of existing old unserviceable ACSR conductor of any size and any description and S&F new ACSR conductor all as specified and directed incl stringing through existing RCC/ steel poles, fixing in insulators, jumpers with polythene pipe, aluminium binding wire etc complete of different sizes, complete all as specified and directed.
S&F in repairs mild steel cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive two coat of synthetic enamel paint over one coat of red oxide zinc chrome primer after prepration the surface, complete all as specified and directed.
M&L for replacement stay assembly complete with 20mm dia stay rod with accessories shown in electric plate No 01 incl stay clamps and galvanised stay wire of size 7/4 mm, complete all as specified and directed. Note :- Loop insulator, stay wire, excavation and concrete work shall be measured and paid seperately under respective items of BOQ.
S&F in replacement disc type insulator, porcelain vitreous, brown or white, suitable for 33 KV/11 KV HT working pressure of size 145mm height x 255mm dia including one galvanised mild steel spindle, two galvanised iron washer and one GI nut, complete all as specified and directed.
S&F in replacement pin type porcelain vitreous, brown or white insulator, suitable for 33 KV/11 KV HT of working pressure of size 150mm height, 150mm dia, including one galvanised mild steel spindle, two galvanished iron washer and one GI nut, complete all as specified and directed. Note :- Loop insulator, stay wire, excavation and concrete work shall be measured and paid seperately under respective items of BOQ.
S&F in repairs cable jointing kit for 11KV grade cable for outdoor termination, heat shrink type joint, complete with jointing material and accessories, suitable for size 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm, complete all as specified and directed. Make :- 3M/Birla/Denson
S&F in repairs cable jointing kit for 11KV grade cable for indoor termination, heat shrink type joint, complete with jointing material and accessories, suitable for size 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm, complete all as specified and directed. Make :- 3M/Birla/Denson
S&F in repairs cable jointing kit for 11KV grade cable for straight through joint, heat shrink type joint, complete with jointing material and accessories, suitable for size 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm, complete all as specified and directed. Make :- 3M/Birla/Denson
S&F in repairs cable jointing kit for 11KV grade cable for outdoor termination, heat shrink type joint, complete with jointing material and accessories, suitable for size 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm, complete all as specified and directed. Make :- 3M/Birla/Denson
S&F in repairs cable jointing kit for 11KV grade cable for indoor termination, heat shrink type joint, complete with jointing material and accessories, suitable for size 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm, complete all as specified and directed. Make :- 3M/Birla/Denson
S&F in repairs cable jointing kit for 11KV grade cable for straight through joint, heat shrink type joint, complete with jointing material and accessories, suitable for size 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm, complete all as specified and directed. Make :- 3M/Birla/Denson
M&L for painting of HT/LT panel of any description with one coat of synthetic enamel paint of standard colour code by using spray gun over the existing painted surfaces after preparing the old painted surfaces, complete all as specified and directed.
Supply, laying, testing and commissioning XLPE cable, PVC insulated, screened PVC bedded galvanised steel strip or wire armoured electric power cable, heavy duty with aluminium conductor 11000 Volts grade (earthed), of size 3 core 120 sqmm, laid in trenches/ floor/ duct/ fixed on poles through GI tubing, complete all as specified and directed.
All as per Ser item No 26.00 here-in-before but cable size 3 core 95 sqmm, complete all as specified and directed.
S&F in replacement post insulator, suitable for 33 KV HT, working pressure in GOD / DO arrangements of any description, complete all as specified and directed.
Repairing / Servicing the air break isolating switch of HT 33 KV 200/400 Amps by replacing the defective major spares including provn of minor bolts, nuts etc, complete all as specified and directed. Notes :- Major spare parts shall be measured & paid seperately under relevant items of BOQ.
Supply only following 33 KV Airbreak switch spares, complete all as specified and directed :-
Male contact/ moving contact blade.
Female contact / fix contact jaw.
Rotating contactor pipe for upto 200/400 Amps.
MS jumper carrier.
Back connector plate.
Restringing only existing HT 11/33 KV/ Jumpers including dismantling of existing old binding wire for tightening, complete all as specified and directed. Notes :- (a) Restringing of each wire/span shall be measured as one unit. (b) Binding wire shall be measured and paid separately under respective item of BOQ.
M&L for PVC insulated armoured heavy duty, single strand, solid copper conductor electric cable with 1100 Volts grade with cross sectional area of size 12 core 2.5 Sqmm, complete all as specified and directed.
S&F in replacement dropout (DO) fuse unit expulsion type, outdoor, three pole, 200 Amp suitable for HT 33 KV, comprising of insulators, steel base mounting frame, GI nut bolts etc with 30A, HT barrel type fuse, complete all as specified and directed.
S&F in replacement incl testing and commissioning of (GOD) gang operated type air break isolating switch horizontal / vertical type mounting complete, double break and operation rod of suitable length 400 Amps capacity and suitable for 33 KV HT supply, complete all as specified and directed.
S&F in replacement incl testing and commissioning of (GOD) gang operated type air break isolating switch horizontal / vertical type mounting complete, double break and operation rod of suitable length 400 Amps capacity and suitable for 11 KV HT supply, complete all as specified and directed.
S&F in replacement lighting arrestor, zinc oxide gap less type, station class suitable for 33 KV /10 KA, complete with all fittings, complete all as specified and directed. Make :- M/s Crompton Greaves / M/s Lamco / M/s Elpro / M/s Oblum
S&F in replacement single post insulator, 33 KV with mounting spindle etc, complete all as specified and directed.
S&F in replacement pin insulator, 33 KV with mounting spindle etc, complete all as specified and directed.
S&F in replacement disc insulator, 33 KV with hardware fittings etc, complete all as specified and directed.
M&L for preparation of old painted surfaces of HT 33 KV MRS at Manasbal consisting of steel poles / ISMBs, cross arms, GOD pipe, clamps etc. having of any description and applying one coat of aluminium paint by manually, complete all as specified and directed. Notes :- (a) The rates inclusive of painting all minor items such as clamps, brackets, nuts, bolts and washers which is not particularly mentioned in this item. (b) The painting work will be carried out during Holidays only to avoid electric shut down.
M&L for loose filing and levelling of stone aggregate/boulders in an uniform manner in 33/11 KV yard/sub station of size 40 to 80 mm graded, complete all as specified and directed. Note :- An average of levelled thickness of boulders shall be measured and paid.
S&F in replacement including testing of metering & protection current transformer oil filled, outdoor type of 33 KV capacity ratio 100-50/5 or 200-100/5 class=5P, 10/1 15 VA including dismantling old existing CT, complete all as specified and directed. Note :- Required and necessary setting including testing on completion shall be carried out till satisfaction of Engineer-in-Charge.
Dismantling old and burnt out PT unit, 110/220 volts draw out type, epoxy resin cast type, taking out contact with lead and bushing from the bus bar and PT, replacing by new one of same model suitable for 33 KV PT Unit incl testing on completion, complete all as specified and directed.
M&L for cutting and trimming of tree branches of girth 25mm to 75mm to 3mtr all around of any size, which is obstructing illumination of street light and touching LT/ HT over head line, by using required tools and plants including removing trimmed tree branches, complete all as specified and directed by Engineer-in-Charge. Note :- Each cleaning will be measured and paid.
S&F in replacement of synthetic insulating rubber mat, ISI Marked of size 1mtr x 2mtr x 3mm, suitable for 33/11 KV at 33/11 KV MRS Manasbal.
S&F in replacement bolted type LM 6 alloy aluminium rigid stud type terminal connector of type universal connector suitable for 33/11 KV type ACSR conductor / busbar, complete all as specified and directed.
S&F in repacement bolted type LM 6 alloy aluminium rigid pad type terminal connector for pad to conductor suitable for 33/11 KV type ACSR conductor, complete all as specified and directed.
S&F in repairs bolted type LM 6 alloy aluminium rigid parallel connector conductor to conductor suitable for 33/11 KV type ACSR conductor, complete all as specified and directed.
Taking down carefully the existing 11KV/433 V distribution transformer of capacity 25 KVA to 250 KVA by disconnecting HT overhead connection/underground cables and earth strips etc, from any substation / locations using suitable capacity of crane or by any other mechanical method irrespective of type of approach available, loading in vehicle, transportation to workshop for repairs and unloading carefully. Reloading the tranformer after repairs and testing of transformer, transportation to site and unloading including placing at given/ existing position and re-commissioning complete all as specified and directed by Engr-in-charge. Note : All required T&P for disonnection, connection, loading and loading including necessary petty items such as bolts, nuts etc will be arranged by the contractor and rates for the same deemed to be included in the quoted rates.
M&L for repairs toTransformer step down 11KV/0.433 KV of any type of capacity 25 KVA to 250 KVA, after dismantling the transformer body carefully, opening the top cover of transformer for inspection /repair, drain out the transformer oil from the tank complete, taking out the core and winding assy by disconnecting the internal connections, removing the carbon/ sludge deposit in transformer housing core, renewal/ replacement of u/s rubber bushes and washers, replacement of tap changer winding and thimbles, replacement of silica gel, replacement of top cover gasket set including pasting with pasting material, replacement of worn out nut and bolts, replacement of unserviceable LT & HT bushes, cutting the burnt out winding and re-winding the same with suitable size of super enamelled copper wire as per existing guage, insulating the winding connection by using fire proof sleeve and fire proof tape, warnishing the coil, keeping the coils in electric oven chamber for 24 hrs to remove the moisture, Painting of complete transformer body from outside and inside by weather proof type using spray gun, Marking of MES/SM Number etc, replacement of conservator tank glass, re-intalling the core and winding inside properly, making the all connection with suitable copper lugs, refilling of dehydrated transformer oil including dehydration, reinstalling the top cover after cleaning and painting of housing, conservator tank, expulsion vent etc, Meggering the LT and HT side of the Transformer and testing complete all as specified and directed by Engr-in-Charge. Note :- Winding wire including labour for making of coils and LT/HT bushes will be measured & paid seperately.
All as per Srl item No 50.00 here-in-before but of capacity 11 KV/0.433 KV, 300 KVA to 500 KVA.
M&L for disconnecting 33KV/ 11KV transformer of capacity 1000 KVA by removing HT overhead connection/ UG cables and earth strips etc, taking out the transformer from any location by using suitable capacity of crane or by any other method irrespective of type of approach available, loading in vehicle, transportation to workshop for repairs and unloading carefully. Reloading the tranformer after repairs and testing of transformer, transportation to site and unloading including placing at given position and recommissioning complete all as specified and directed by Engr-in-charge.
Supply and filling of fresh transformer power oil of BDV not less than 60 KV for topping up of reduced level of transformer due to evaporation/ leakage/losses due to dehydration in HT 33 KV transformer/ Distribution transformer 25 to 500 KVA or for replacement complete including removing of old unservicable transformer oil, complete all as specified and directed. Make :- Power oil/ Castrol/ Pure Lubes. Note : Proper document should be maintained by the contractor.
M&L for conducting oil filtration by stream line/ vacuum type filter machine to remove the moisture/ carbon particles to improve required BDV of oil 50 to 60 KV for 1 min for power transformer & as BDV of oil 40 to 50 KV for 1 min for distribution transformer incl routine testing after filtration for any capacity of transformers/ CT/ PT units, complete all as directed. Note :- The contractor shall be change the filter assy before starting the filtration of power/ distribution transformer of any capacity in presence of Engr-in-charge
S&F in replacement of brass terminal rod with nuts, bolts washers & bushings, suitable for HT side of the transformer of any make and capacity from 25KVA to 300 KVA, complete all as specified and directed.
All as per Ser item No 55.00 here-in-before but LT side.
S&F in replacement of brass terminal rod with nuts, bolts washers & bushings suitable for HT side of the transformer of any make and capacity from 315 KVA to 500 KVA, complete all as specified and directed.
All as per Ser item 57.00 here-in-before but LT side.
Supply and replacing silica gel breather clear view type including first fill of good quality silica gel of capacity suitable for 25 KVA to 300 KVA transformer, complete all as specified and directed.
Supply and replacing silica gel breather clear view type including first fill of good quality silica gel of capacity suitable for 315 KVA to 500 KVA transformer, complete all as specified and directed.
M&L for painting the outer surface of the transformer with one coat of weather proof paint after preparing the surface dust and oil free and cleaning the bushes, name plate etc, paint free after painting including writing the MES/SM Number with white enamelled paint, complete all as directed for capacity of transformer 25 KVA to 500 KVA (Indoor/outdoor type), complete all as specified and directed.
All as per Ser item No 61.00 here-in-before but for capacity of transformer 1000 KVA (Indoor/outdoor type).
Supply and replacing silica gel breather clear view type including first fill of good quality silica gel of capacity suitable for 1000 KVA transformer units, complete all as specified and directed.
M&L for earthing complete with GI earth plate of size 60cmx60cmx6mm thick electrode, burried directly in ground (earth pit not less then 2.25 metres deep below ground level) with top edge of the plate not less then 1.5 metre below normal ground level, conneceted to GI strip of size 32x6mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.5 and incl earth work, PCC pit and RCC cover, watering pipe 20mm dia light grade, funnel, wire mesh, charcoal dust, 40mm dia light grade protection pipe and salt etc. and connected to earthing test point, complete all as specified, directed and testing after completion.
M&L for earthing complete with copper earth plate of size 60cmx60cmx3.15mm thick electrode, burried directly in ground (earth pit not less then 2.25 metres deep below ground level) with top edge of the plate not less then 1.5 metre below normal ground level, conneceted to copper strip of size 25x3mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 and incl earth work, PCC pit and RCC cover, watering pipe 20mm dia light grade, funnel, wire mesh, charcoal dust, 40mm dia light grade protection pipe and salt etc. and connected to earthing test point, complete all as specified, directed and testing after completion.
S&F in replacement off load tap changer for distribution transformer of any make and capacity from 25-500 KVA, complete all as specified and directed.
M&L for super enamelled copper conductor wire of suitable gauge and size as per requirement for rewinding the HT/LT transformer / HT AVR of any capacity and any make, complete all as specified and directed.
S&F in replacement of brass terminal rod with nuts, bolts washers & bushings, suitable for 33KV side of power transformer of any make and capacity 1000 KVA, complete all as specified and directed.
S&F in replacement of brass terminal rod with nuts, bolts washers & bushings, suitable for 11KV side of power transformer of any make and capacity 1000 KVA, complete all as specified and directed.
S&F in replacement of bush type insulator white/brown/green, working pressure 33000Volts HT side, complete all as specified and directed.
S&F in replacement of bush type insulator white/brown/green, working pressure 11000Volts HT side, complete all as specified and directed.
S&F in replacement of temperature gauge, suitable size for power transformer of any capacity, complete all as specified and directed. Make :- AE or technocommercially equivalent as approved by GE.
M&L for servicing of 33 KV VCB/ 11KV VCB/ bus coupler by dismantling, cleaning, greasing the complete VCB with attached relays bus bar etc. insulation testing, setting the contact gap by measuring as required re-assembling the VCB and reinstalling back to its original position checking and repairing the current circuit panel wiring, replacement of new spares as required complete including operational testing and commissioning, complete all as specified and directed. Note :- New spares parts shall be measured and paid separately under respective items of BOQ.
M&L for carrying out primary & secondary injection test of 33KV or 11 KV indoor / outdoor type current transformer (Set of three) of VCB's by using standard injection test method and checking the electrical circuits for fault condition, all relay testing and proper functioning including submitting the test report, complete all as specified and directed. Note :- PIT/SIT for VCB will be carried out in 6 months intervals and each primary & secondary injection test will be measured and paid and considered as one unit.
Supply and fixing in replacement of the following spares for outdoor VCB 33 KV 800 A 750 MVA fault level 36V-26/2000 & VCB 11 KV 400 A 25 KA 250MVA, complete all as specified and directed.
Closing coil 24/30V DC .
Tripping coil 24/30V DC.
Antipumping device 24/30V DC.
33 KV porcelain bushing for VCB Top.
33 KV porcelain bushing for VCB bottom.
Earth Fault and over current relay of L & T Model No MC31A 24-110V.
Digital type power factor indicator meter.
Digital type Voltmeter / Ammeter 96 x 96 mm size.
LED type indicator lamp assembly.
Spout incoming side.
Spout outgoing side.
Epoxy insulators bushings for incoming / out going cables / bus bar suppors as per existng size of VCBs.
Gear system assy complete with handle for charging / discharging of VCBs.
Spring charging motor for VCBs.
Over current protection relay of ERL Model No 8431H32403 18-135V DC.
Metering and protection current transformer epoxy/resin filled of 11 KV grade of ratio 100-50/5 class = 5P, 10/1 25 VA draw out type with necessary mounting and connected items.
M/S Noor Mohammad Shalla
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .