| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAccepted-AOC 13 29 304 IIIRD FLOOR EAST PATEL NAGAR OPP HOTEL SIDDARATHA NEW DELHI 110008 | WEST | DELHI | 110008 | ₹1.3 Cr Quoted ₹1.4 Cr | L1 | Accepted-AOC BEING LOWEST REASONABLE BIDDER |
| 2 | L2₹1.4 Cr+₹2.9 L (2.15%)Rejected-Finance B 87 SHAM NAGAR KHAYALA ROAD NEW DELHI 110018 | NEW DELHI | NEW DELHI | DELHI | 110018 | ₹1.4 Cr+₹2.9 L (2.15%) | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 3 | L3₹1.5 Cr+₹9.7 L (7.14%)Rejected-Finance 04 L BLOCK MARKET SECTOR 11 NOIDA 201301 UP GAUTAM BUDHA NAGAR | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201301 | ₹1.5 Cr+₹9.7 L (7.14%) | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 4 | L4₹1.5 Cr+₹13.2 L (9.70%)Rejected-Finance | ₹1.5 Cr+₹13.2 L (9.70%) | L4 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 5 | L5₹1.5 Cr+₹13.9 L (10.2%)Rejected-Finance NOT SPECIFIED | ₹1.5 Cr+₹13.9 L (10.2%) | L5 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| Sl No | Description | Qty | Unit | United Sales Corporation L5 | DIVYA ELECTRIC CORPOORATION L8 | Leo Network power systems L1 | Vijaypower Generators Limited L10 | Paragon Electrotechnics L9 | R D Bansal L6 | Electromech Engineers L7 | GEPS PROJECTS L3 | M/S RAKESH TRADERS L4 | C L BHATIA L11 | New Era Engineers L2 | VEENUS ENGINEERS L12 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Design, Manufacture, Supply, Installation, Testing and Commissioning 11 kV / 0.433 kV, 315 kVA Factory Assembled, Factory Tested ready to install and connections type Compact Substation with an outdoor enclosure, equipped with 315 kVA Dry type Transfomer, Ring Main Unit and Air Circuit Breaker as secondary side control complete with HT Cable interconnection in between Transformer and Ring Main Unit and LT Cable interconnection in between Transformer and LV Incoming Main Switchgear-ACB for full load output current of the transformer and Internal earthing connections by GI Strips all as a single transport unit complete all as specified as detailed below. Make of Compact Sub-Station, Ring Main Unit and Air Circuit Breaker must be same. | 3 | Each Job | 43,25,000 ₹1,29,75,000 | 47,20,000 ₹1,41,60,000 | 38,20,840 ₹1,14,62,520 Lowest | 47,49,000 ₹1,42,47,000 | 47,53,000 ₹1,42,59,000 | 44,50,000 ₹1,33,50,000 | 43,50,000 ₹1,30,50,000 | 40,80,000 ₹1,22,40,000 | 43,00,000 ₹1,29,00,000 | 52,25,000 ₹1,56,75,000 | 40,00,000 ₹1,20,00,000 | 52,30,000 ₹1,56,90,000 |
| 1.01[b] Enclosure: Outdoor type galvanised enclosure having modular construction with 2mm thick Galvanized Sheet Steel in Corrugated / Louvered design type wall design for better heat dissipation and providing robust construction. The degree of protection for HT & LT switchgear compartment shall be IP54 & degree of protection of transformer compartment of the enclosure shall be minimum IP34. The enclosure exterior shall be painted with polyurethane paint / epoxy powder coated paint shade RAL 7032 and tropicalised to Indian weather conditions. Each compartment shall be provided with the door and pad locking arrangement. The Enclosure to be tested for Internal Arc fault test to the tune of atleast 21 KA for 1 second (IAC A and IAC B) to ensure Operator as well as Pedestrian / General Public Safety, adhering to as per latest IEC 62271-202. CSS should have mechanical impact test compliance of IK10. The Compartment illumination lamp with door operated switch shall be provided for each compartment. Structure of the substation shall be able to withstand the gross weight of all equipment. The Compact Substation shall be provided with lifting beams and hooks for easy installation at site and it shall be possible to transport the equipment along with Transformer & LT Panel from one site to another. Dimensions of enclosure shall be as per the components required and mentioned in BoQ. Final drawing shall be got approved from Accepting Officer. | |||||||||||||||
| 1.02[c] HT Switchgear [Inside Compact Sub-Station]: Four way 11KV, 630 Amps, 25kA/1s with IAC of 21kA/1s (gas tank and cable chamber), Non-Extensible Ring Main Unit / Compact Switchgear with Copper Busbar, consisting of 630 Amps, Two Numbers [As incomer] fixed Manual Fault Making / Load Break Switches & Two Numbers Fixed Manual/Motorised SF6 insulated Vacuum Circuit Breakers [As Outgoing], line side earth switch with own making capacity in SF6 Gas insulated sealed for life minimum 2 mm Thickness stainless steel tank IP 67 degree of protection for gas tank with Air Insulated Metering Module,One Number fault passage indicator shall be provided for each Load Break Switch with 1 NO + 1 NC Contact, One Number manometer shall be provided for outgoing feeders, One set of 50/1A, 2.5 VA, Class 1.0 for metering & One set of 50 / 1A, 2.5 VA, CL 5P 10 Current Transformers shall be provided, One number of Digital Multifunction Meter with RS 485 Port shall be provided for VCB Feeders, One Set of 11 kV / RT3 / 110 / RT3, Class 1.0, 20 kVA PTs shall be provided in Metering Module. Vacuum Circuit Breakers shall be with self-powered micro processor based Numerial Over Current and Earth Fault Relay having Charged Open / Closing Mechanism, On / Off Indicators, Mechanical Operation Counters etc. Interconnection between RMU and Transformer shall be using suitable Aluminium armoured 3 nos. 1C X 95 sq.mm. Aluminium armoured (E) XLPE cable. The vacuum interrupter of RMU must have min. of 50 nos. of short circuit operations. | |||||||||||||||
| 1.03[d] Transformer [Inside Compact Sub-Station]: 315 KVA, Scada compatible,11KV / 433V, 3 Phase, 50 Hz, DYn11, natural air without fan cooling dry type, Copper Wound, CRGO Core Transformer with Online Circuit Tap Links of range +5% to –5% in steps of 2.5% on HT side of transformer, having Primary Voltage [HT] 11 KV and Secondary Voltage [LT] of 433 Volts, Delta connected on 11 KV Side & Star connected on 433 Volts side, designed & constructed with particular reference to Tropical Condition | |||||||||||||||
| 1.04[e] LV Switchgear [Inside Compact Sub-Station]: 433 Volts, indoor LV Panel with Aluminium Busbars [100% for Phase & 50% for neutral, fabricated using 2 mm thick CRCA Sheet Steel, Ingress Protection IP4X, Compartmentalised complete with internal wiring consisting of following: [i] Incomer: ACB, 630 Amps, FP, 50 KA, 433 Volts, 3 Phase, 50 Hz, Fixed Motorised type with Microprocessor based O/L, S/C, E/F Release – 1 No [ii] Metering for Incomer: Digital Multifunction Meter with A, V, KW, KWH, PF, Class 1.0 with Port – 1 Nos, LT Metering CT’s, 630 / 1A, Cast Resin Type, Class - 0.5 – 1 Set, R, Y, B, ON, OFF, Trip LED Indicating Lamps – 1 Set, Control MCB, SP, 6 Amps – As required [iii] Outgoing: MCCB, 400 Amps, TPN, 35KA, 415 Volts, 3P, 50 Hz, Fixed Manual type adjustable with Microprocessor based O/L, S/C & E/F release –1 No. [iv] Outgoing: MCCB, 250 Amps, TPN, 35KA, 415 Volts, 3P, 50 Hz, Fixed Manual type adjustable with Microprocessor based O/L, S/C & E/F release –3 Nos. [v] Metering for Outgoing: Digital Multifunction Meter with A, V, KW, KWH, PF, Class 0.5 with Port for each outgoing feeder, LT Metering CT’s, 400 / 1A, Cast Resin Type, Class - 0.5 – 1 Set, R, Y, B, ON, OFF, Trip LED Indicating Lamps – 1 Set, Control MCB, 6A, SP – As required [vi] Outgoing MCCBs of LT Switchgear shall be suitable for termination of 2 Runs X 3½ Core X 185 Sq.mm aluminium armoured Cable. | |||||||||||||||
| 1.05[f] Condition monitoring :- Thermal sensors must be considered in cable chamber of RMU, busbar of LT panel and contacts of ACB for online temperature monitoring (24*7 monitoring). Condition monitoring solution shall be web accessible and provide Expert consultancy with advanced analytics & proactive recommendations basis insights drawn from continuous monitoring & data trends. Bidder to consider one year subscription cost for advanced anayltics by experts. | |||||||||||||||
| 1.06[g] Compact Substation shall be outdoor Plinth Mounted Type. The rate quoted is deemed to be including the cost of Erection, Commissioning of Compact Substation and Civil work such as Construction of foundation with Concrete / Brick masonry with plastering for the installation of Compact Substation of required size including trench for the cabling work etc. complete in all respect as directed by the GE. However the bidder shall furnish the foundation details for approval of GE before executing the work. [g] Compact Substation shall be complete with the internal interconnections Copper Busbar & GI Earthing on HT side and Aluminium Busbar on LT side and Aluminium Earthing for complete CSS including TF Neutral for connecting to the earth pits. | |||||||||||||||
| 1.07[h] The Compact substation shall be assembled at factory and no assembly of the same shall be allowed at site. Bidder shall be responsible for Installation & commissioning Compact substation. Technical data sheet of the Transformer, HV / LV Switchgear, Relay etc. shall be submitted to GE for approval before placing the supply order. [i] All testing shall be conducted as per IS -2026 [j] The bidder shall supply suitable & required no. of HT & LT Cable termination kits along with Compact Substation for HT & LT Cable terminations. [k] The Design for Internal Arc Fault shall be tested for 20KA for 1 Second as per IEC 1330/62271-202. [l] Pre-Dispatch Inspection: Bidder shall offer for pre-dispatch inspection at OEM works. Only after the equipments are cleared by the department in writing, the bidder can dispatch the equipment. Routine tests shall be conducted and original test certificates shall be submitted at the time of Pre-Dispatch Inspection. [m] Commissioning Spares: Additional commissioning spares such as Digital Multifunction Meter – 1 Nos, Indication lamps – 3 Nos, Protection Relay – 1 No, Spring Charging Handles – 2 Nos and Panel Keys – 2 Nos shall be provided by the bidder. [n] Suppressors or other protection devices shall be provided, if required as per schedule of quantities, wherever the sub-station installation is likely to interfere during the operation with any other electric or electronic equipment. | |||||||||||||||
| 1.08Construction of plinth for CSS : Excavation of pit of size suitable for CSS with Minimum height of 1000 mm, filling with sand for 150mm depth, laying bed concrete with PCC 1:4:8 D-2 (using 40mm well graded crushed stone aggregate) for 150mm thick, construction of plinth as per drawing (2 supports) with RR Masanory of size 0.837 cum and plastering all around the outer side with CM(1:4) 12 mm Thick and White washing 2 coats including cost and transport of all material and labour charges for all operation incidental charges etc.., complete as directed by the Engineer in Charge | |||||||||||||||
| 2.00 | Taking down old unserviceable earthing of any type and any size complete all as specified and directed.
Note: Excavation & earth work where required shall be measured & paid for separately under relevant items of this BoQ. | 12 | Each | 25 ₹300 Lowest | 500 ₹6,000 | 1,000 ₹12,000 | 1,500 ₹18,000 | 200 ₹2,400 | 100 ₹1,200 | 900 ₹10,800 | 600 ₹7,200 | 100 ₹1,200 | 400 ₹4,800 | 100 ₹1,200 | 500 ₹6,000 |
Tender Value
₹1.5 Cr
EMD Value
₹2.2 L
Closing Date
27 Jun 2025, 6:00 pmClosed
CWE JABALPUR
HQ CWE JABALPUR OPPOSITE SUPPLY DEPT SADAR 482001
Special repair to replacement of old vintage distribution transformer with compact sub station and allied work under GE (West) Jabalpur
2025_MES_709797_1
81113/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
CWE JABALPUR
AS PER NIT
7 documents required · 7 mandatory
₹1,000
GE (WEST ) JABALPUR
₹2.2 L
Yes
10 Oct 2025
23 May 2025
3 Jul 2025
23 May 2025
27 Jun 2025
13 Jun 2025
23 May 2025 - 7 Jun 2025
Amount
Design, Manufacture, Supply, Installation, Testing and Commissioning 11 kV / 0.433 kV, 315 kVA Factory Assembled, Factory Tested ready to install and connections type Compact Substation with an outdoor enclosure, equipped with 315 kVA Dry type Transfomer, Ring Main Unit and Air Circuit Breaker as secondary side control complete with HT Cable interconnection in between Transformer and Ring Main Unit and LT Cable interconnection in between Transformer and LV Incoming Main Switchgear-ACB for full load output current of the transformer and Internal earthing connections by GI Strips all as a single transport unit complete all as specified as detailed below. Make of Compact Sub-Station, Ring Main Unit and Air Circuit Breaker must be same.
[b] Enclosure: Outdoor type galvanised enclosure having modular construction with 2mm thick Galvanized Sheet Steel in Corrugated / Louvered design type wall design for better heat dissipation and providing robust construction. The degree of protection for HT & LT switchgear compartment shall be IP54 & degree of protection of transformer compartment of the enclosure shall be minimum IP34. The enclosure exterior shall be painted with polyurethane paint / epoxy powder coated paint shade RAL 7032 and tropicalised to Indian weather conditions. Each compartment shall be provided with the door and pad locking arrangement. The Enclosure to be tested for Internal Arc fault test to the tune of atleast 21 KA for 1 second (IAC A and IAC B) to ensure Operator as well as Pedestrian / General Public Safety, adhering to as per latest IEC 62271-202. CSS should have mechanical impact test compliance of IK10. The Compartment illumination lamp with door operated switch shall be provided for each compartment. Structure of the substation shall be able to withstand the gross weight of all equipment. The Compact Substation shall be provided with lifting beams and hooks for easy installation at site and it shall be possible to transport the equipment along with Transformer & LT Panel from one site to another. Dimensions of enclosure shall be as per the components required and mentioned in BoQ. Final drawing shall be got approved from Accepting Officer.
[c] HT Switchgear [Inside Compact Sub-Station]: Four way 11KV, 630 Amps, 25kA/1s with IAC of 21kA/1s (gas tank and cable chamber), Non-Extensible Ring Main Unit / Compact Switchgear with Copper Busbar, consisting of 630 Amps, Two Numbers [As incomer] fixed Manual Fault Making / Load Break Switches & Two Numbers Fixed Manual/Motorised SF6 insulated Vacuum Circuit Breakers [As Outgoing], line side earth switch with own making capacity in SF6 Gas insulated sealed for life minimum 2 mm Thickness stainless steel tank IP 67 degree of protection for gas tank with Air Insulated Metering Module,One Number fault passage indicator shall be provided for each Load Break Switch with 1 NO + 1 NC Contact, One Number manometer shall be provided for outgoing feeders, One set of 50/1A, 2.5 VA, Class 1.0 for metering & One set of 50 / 1A, 2.5 VA, CL 5P 10 Current Transformers shall be provided, One number of Digital Multifunction Meter with RS 485 Port shall be provided for VCB Feeders, One Set of 11 kV / RT3 / 110 / RT3, Class 1.0, 20 kVA PTs shall be provided in Metering Module. Vacuum Circuit Breakers shall be with self-powered micro processor based Numerial Over Current and Earth Fault Relay having Charged Open / Closing Mechanism, On / Off Indicators, Mechanical Operation Counters etc. Interconnection between RMU and Transformer shall be using suitable Aluminium armoured 3 nos. 1C X 95 sq.mm. Aluminium armoured (E) XLPE cable. The vacuum interrupter of RMU must have min. of 50 nos. of short circuit operations.
[d] Transformer [Inside Compact Sub-Station]: 315 KVA, Scada compatible,11KV / 433V, 3 Phase, 50 Hz, DYn11, natural air without fan cooling dry type, Copper Wound, CRGO Core Transformer with Online Circuit Tap Links of range +5% to –5% in steps of 2.5% on HT side of transformer, having Primary Voltage [HT] 11 KV and Secondary Voltage [LT] of 433 Volts, Delta connected on 11 KV Side & Star connected on 433 Volts side, designed & constructed with particular reference to Tropical Condition
[e] LV Switchgear [Inside Compact Sub-Station]: 433 Volts, indoor LV Panel with Aluminium Busbars [100% for Phase & 50% for neutral, fabricated using 2 mm thick CRCA Sheet Steel, Ingress Protection IP4X, Compartmentalised complete with internal wiring consisting of following: [i] Incomer: ACB, 630 Amps, FP, 50 KA, 433 Volts, 3 Phase, 50 Hz, Fixed Motorised type with Microprocessor based O/L, S/C, E/F Release – 1 No [ii] Metering for Incomer: Digital Multifunction Meter with A, V, KW, KWH, PF, Class 1.0 with Port – 1 Nos, LT Metering CT’s, 630 / 1A, Cast Resin Type, Class - 0.5 – 1 Set, R, Y, B, ON, OFF, Trip LED Indicating Lamps – 1 Set, Control MCB, SP, 6 Amps – As required [iii] Outgoing: MCCB, 400 Amps, TPN, 35KA, 415 Volts, 3P, 50 Hz, Fixed Manual type adjustable with Microprocessor based O/L, S/C & E/F release –1 No. [iv] Outgoing: MCCB, 250 Amps, TPN, 35KA, 415 Volts, 3P, 50 Hz, Fixed Manual type adjustable with Microprocessor based O/L, S/C & E/F release –3 Nos. [v] Metering for Outgoing: Digital Multifunction Meter with A, V, KW, KWH, PF, Class 0.5 with Port for each outgoing feeder, LT Metering CT’s, 400 / 1A, Cast Resin Type, Class - 0.5 – 1 Set, R, Y, B, ON, OFF, Trip LED Indicating Lamps – 1 Set, Control MCB, 6A, SP – As required [vi] Outgoing MCCBs of LT Switchgear shall be suitable for termination of 2 Runs X 3½ Core X 185 Sq.mm aluminium armoured Cable.
[f] Condition monitoring :- Thermal sensors must be considered in cable chamber of RMU, busbar of LT panel and contacts of ACB for online temperature monitoring (24*7 monitoring). Condition monitoring solution shall be web accessible and provide Expert consultancy with advanced analytics & proactive recommendations basis insights drawn from continuous monitoring & data trends. Bidder to consider one year subscription cost for advanced anayltics by experts.
[g] Compact Substation shall be outdoor Plinth Mounted Type. The rate quoted is deemed to be including the cost of Erection, Commissioning of Compact Substation and Civil work such as Construction of foundation with Concrete / Brick masonry with plastering for the installation of Compact Substation of required size including trench for the cabling work etc. complete in all respect as directed by the GE. However the bidder shall furnish the foundation details for approval of GE before executing the work. [g] Compact Substation shall be complete with the internal interconnections Copper Busbar & GI Earthing on HT side and Aluminium Busbar on LT side and Aluminium Earthing for complete CSS including TF Neutral for connecting to the earth pits.
[h] The Compact substation shall be assembled at factory and no assembly of the same shall be allowed at site. Bidder shall be responsible for Installation & commissioning Compact substation. Technical data sheet of the Transformer, HV / LV Switchgear, Relay etc. shall be submitted to GE for approval before placing the supply order. [i] All testing shall be conducted as per IS -2026 [j] The bidder shall supply suitable & required no. of HT & LT Cable termination kits along with Compact Substation for HT & LT Cable terminations. [k] The Design for Internal Arc Fault shall be tested for 20KA for 1 Second as per IEC 1330/62271-202. [l] Pre-Dispatch Inspection: Bidder shall offer for pre-dispatch inspection at OEM works. Only after the equipments are cleared by the department in writing, the bidder can dispatch the equipment. Routine tests shall be conducted and original test certificates shall be submitted at the time of Pre-Dispatch Inspection. [m] Commissioning Spares: Additional commissioning spares such as Digital Multifunction Meter – 1 Nos, Indication lamps – 3 Nos, Protection Relay – 1 No, Spring Charging Handles – 2 Nos and Panel Keys – 2 Nos shall be provided by the bidder. [n] Suppressors or other protection devices shall be provided, if required as per schedule of quantities, wherever the sub-station installation is likely to interfere during the operation with any other electric or electronic equipment.
Construction of plinth for CSS : Excavation of pit of size suitable for CSS with Minimum height of 1000 mm, filling with sand for 150mm depth, laying bed concrete with PCC 1:4:8 D-2 (using 40mm well graded crushed stone aggregate) for 150mm thick, construction of plinth as per drawing (2 supports) with RR Masanory of size 0.837 cum and plastering all around the outer side with CM(1:4) 12 mm Thick and White washing 2 coats including cost and transport of all material and labour charges for all operation incidental charges etc.., complete as directed by the Engineer in Charge
Taking down old unserviceable earthing of any type and any size complete all as specified and directed. Note: Excavation & earth work where required shall be measured & paid for separately under relevant items of this BoQ.
Taking down of old unserviceable cable of any type and any size for repair or replacement etc complete all as specified and directed.
Taking down old unserviceable LT panel/switch gear/APFC panel of any type and any size complete all as specified and directed.
Supply and laying and testing, XLPE/ PILCA cable 11000 volts grade (Earthed) XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor of cross section area 95 sqmm, 3 core, fixing or passing in trenches / on pole/ through pipes and testing on completion complete all as directed. (Note : Excavation and earthwork, sand cushioning and cable protection will be measured and paid for separately)
Supply, laying, testing and commissioning cable end termination joint out door cold shrinkable type suitable for stranded aluminium conductor 3 core, 11 KV XLPE , 95 Sq mm cross sectional area complete all as specified and directed.
M&L earthing complete with galvanised steel earth plate electrode 600x600x6.0mm thick directly burried in the ground (earth pit not less than 2.25M deep below ground level) with top edge of earth plate not less than 1.50M deep below normal ground level, connected to galvanised iron strip 32x6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, 40mm bore GI pipe light grade including necessary fittings for protection of earthing strip, watering pipe 20mm bore GI medium grade, concrete chamber in PCC (1:4:8) type D-2 using 40 mm grade stone aggregate, coping shall be in PCC (1:3:6) type C-1 using 20 mm grade stone aggregate and internal surfaces of concrete chamber shall be given 12mm thick plaster in CM (1:4), funnel with wire gauge of 22 gauge 8 mesh per linear including 50mm thick cover of RCC (1:2:4) type B-1 using 20mm grade stone aggregate reinforced with 8mm MS TMT bar @ 75 mm C/C both ways, char coal dust and common salt all as shown in electrical plate No. 3 of SSR Part-I (2009) including all necessary excavation & earth work and removal of surplus soil to a distance n. exc 50M and providing connection points with MS/ GI bolts & washers as required and connection from earth test point to earth electrode with same GI earth strip alongwith protection pipe and testing on completion complete all as specified and directed. Note:- GI strip and protection pipe from earth electrode to test point max upto 7.50M shall be deemed to be included in the unit rate as quoted by the contractor.
M&L for broken stone aggregate for loose filling under 11 KV four pole and arround the transformer , of gauge 40 mm graded in and including for stacking materials in regular heaps/stacks for measurement complete all as specified and as directed.
Supply, laying or fixing or passing through pipe commissioning and testing of XLPE insulated, armoured heavy duty, electric cable with aluminium conductor, 1100 volts grade of the cross section area 25 sqmm 4 core including suitable size lugs complete all as specified and as directed. Note:- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid for separately under relevant items of this BoQ.
Supply, laying or fixing or passing through pipe commissioning and testing of XLPE insulated, armoured heavy duty, electric cable with aluminium conductor, 1100 volts grade of the cross section area 50 sqmm 3.5 core including suitable size lugs complete all as specified and as directed. Note:- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid for separately under relevant items of this BoQ.
Supply, laying or fixing or passing through pipe commissioning and testing of XLPE insulated, armoured heavy duty, electric cable with aluminium conductor, 1100 volts grade of the cross section area 70 sqmm 3.5 core including suitable size lugs complete all as specified and as directed. Note:- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid for separately under relevant items of this BoQ.
Supply, laying or fixing or passing through pipe commissioning and testing of XLPE insulated, armoured heavy duty, electric cable with aluminium conductor, 1100 volts grade of the cross section area 120 sqmm 3.5 core including suitable size lugs complete all as specified and as directed. Note:- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid for separately under relevant items of this BoQ.
Supply, laying or fixing or passing through pipe commissioning and testing of XLPE insulated, armoured heavy duty, electric cable with aluminium conductor, 1100 volts grade of the cross section area 150 sqmm 3.5 core including suitable size lugs complete all as specified and as directed. Note:- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid for separately under relevant items of this BoQ.
Excavation in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, for laying of pipe, cable etc or n. exc.10 Sqm on plan and n. exc. 1.5m in depth for shafts, cesspits, manholes, pier holes, etc and getting out in any type of soil complete all as specified and directed.
Returning, filling in excavated approved soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed.
Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point including spreading complete all as specified and directed.
Supply and spreading clean and dry fine sand free from sharp materials (unwashed) laying in trenches around the cable for cushioning in trenches, laid to a uniform thickness of 23cm (15cm under the cable & 8cm over the cable) and gently punned down to 18cm thickness complete all as specified and as directed. (Note: Only punned thickness of sand shall be measured and paid.)
Supply and laying un-reinforced precast concrete cable covers, Class HV type1, flat, size 300 mm x 180 mm x 40 mm, complete all as specified and as directed.
supply and laying the Brick covering with width equal to length of brick as mechanical protection to cable with sub class ‘B’ fly ash bricks laid dry flat complete all as specified and directed by Engr in charge.
Supply, laying & fixing in replacement Double Wall Corrugated (DWC) pipes,50 mm outer dia and 38 mm inner dia, made of High Density polyethyline (HDPE) with all accessories i.e. all type of joints, Sockets, Elbows, bends and End caps etc. complete all as specified and directed
M&L for GI Tubes in repair of following size, medium grade, galvanised, with clamp of 25x3 flat iron welded to pipe fixed to wall/pole/ceiling or laid in floors or under road etc complete all as specified and as directed.
40 mm bore
50 mm bore
80mm bore
M & L 20x3 mm copper strip as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required
Schedule of credit amount of Rs 1,03,753.00 to be deducted during AOC
New Era Engineers (BID ID -3339114)
GEPS PROJECTS (BID ID -3336999)
M/S RAKESH TRADERS (BID ID -3337247)
United Sales Corporation (BID ID -3328068)
R D Bansal (BID ID -3330789)
Electromech Engineers (BID ID -3334399)
DIVYA ELECTRIC CORPOORATION (BID ID -3329316)
Paragon Electrotechnics (BID ID -3330722)
Vijaypower Generators Limited (BID ID -3330525)
C L BHATIA (BID ID -3339082)
VEENUS ENGINEERS (BID ID -3339184)
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .