| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.8 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹26.3 L+₹51,202 (1.99%)Rejected-AOC | L2 | Rejected-AOC Being not L1 | |
| 3 | L3₹30.3 L+₹4.5 L (17.7%)Rejected-AOC | L3 | Rejected-AOC Being not L1 | |
| 4 | L4₹30.6 L+₹4.9 L (18.9%)Rejected-AOC PLOT NO 28 SANTOSHIMA COLONY WEST MARREDPALLY SECUNDERABAD 500026 | HYDERABAD | TELANGANA | 500026 | L4 | Rejected-AOC Being not L1 |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
15 Jul 2023, 6:00 pmClosed
Shri M Saravanan, IDSE, GE
Garrison Engineer North 35 Allenby Lines Secunderabad 500087
MISCELLANEOUS REPAIRS TO INTERNAL ELECTRIFICATION AND CONVERSION OF CONVENTIONAL LIGHTS TO LED LIGHTS IN OTM MD ACCN AREA AT CDM UNDER AGE E M NORTH OF GE N SECUNDERABAD
2023_MES_603783_1
8680
Open Tender
Electrical and Maintenance Works
Item Rate
300 days
GARRISON ENGINEER NORTH SECUNDERABAD
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GARRISON ENGINEER (NORTH) SECUNDERABAD
₹80,000
Yes
21 Sept 2023
16 Jun 2023
17 Jul 2023
16 Jun 2023
15 Jul 2023
1 Jul 2023
Amount
Detailment of tradesman as per Job card for taking down existing unserviceable point wiring of any description/type/ size of light/fan/power/two way/bell etc on TW batten/conduit including removal of batten / conduit / gutties / wooden boards / switches / sockets / regulators/ light fittings etc and removal of unserviceable material out of site area and making good the disturbed surfaces of wall/ceiling complete all as specified and as directed.
Disconnecting and removing the MCB DBs from any height, stripping out the fitting for examine replacement of US spare parts, reassembling, refixing in original position including minor repairs for the smooth functioning and testing complete all as specified and as directed.
M & L for Point wiring with 1.5 Sqmm FRLS copper conductor single core PVC insulated sheathed 1100 V multistranded drawn through existing conduit and including rigid 20 MM PVC conduit and conduit accessories of suitable dia medium grade and modular accessories including fixing/grouting sunken/ surface along with existing flush box of suitable thickness covered with suitable modular cover plate including running up of 1.5 Sqmm FRLS copper conductor PVC insulated cable as earth continuity conductor along with wiring and connecting to the common earth dolly for fixing the switches/ sockets/ regulators etc., complete all as specified and as directed for one Light/Fan/Bell Point Controlled by One Switch NOTE: 1. Modular Cover Plate is inclusive of the rated quoted by the contractor. 2. Cutting & Chases will be measured and paid separately
All as per Sl item No 3 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board complete all as specified and as directed.
All as per Sl item No 3 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on the same board complete all as specified and as directed.
All as per Sl item No. 3 here in before, but for using 2.5 Sqmm single core copper conductor cable of multistranded PVC insulated sheathed FRLS 1100 Volts grade for 3 Pin 15 Amps switch socket combination point on independent board including running of 2.5 Sqmm FRLS copper conductor PVC insulated cable as earth continuity conductor complete all as specified and as directed.
All as per Sl item No. 3 here in before, but for wiring drawn through PVC Casing and Capping, but for One light/fan/Bell point controlled by one, one way switch 5 amps, SP complete all as specified and as directed.
All as per Sl item No. 7 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board complete all as specified and as directed.
All as per Sl item No. 7 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on the same board complete all as specified and as directed.
All as per Sl item No. 7 here in before, but for using 2.5 Sqmm single core copper conductor cable of multistranded PVC insulated sheathed FRLS 1100 Volts grade for 3 Pin 15 Amps switch socket combination point on independent board including running of 2.5 Sqmm FRLS copper conductor PVC insulated cable as earth continuity conductor complete all as specified and as directed.
S & F switch piano single pole Modular switch 1 way 10 Amps, 1 Module complete all as specified and as directed.
S & F switch piano single pole Modular switch 1 way 16 Amps, 1 Module complete all as specified and as directed.
S&F Modular Bell Push 10A, 1 Module complete all as specified and as directed.
Supply and fix socket outlet modular type multipurpose 2/3 Pin, 6 amps, 230 volts combined 2 Module complete all as specified and as directed.
Supply and fix socket outlet modular type multipurpose 2/3 Pin, 6/16 amps, 230 volts combined 2 Module complete all as specified and as directed.
S & F Modular ceiling fan regulator stepped type heavy duty suitable to work on 230 volts, 2 Module complete all as specified and as directed.
M & L for Point wiring with 1.5 Sqmm copper conductor single core PVC insulated FRLS 1100 Volts multistranded drawn through and including 20 mm rigid PVC conduit surface and conduit accessories of suitable dia medium grade and existing pressed steel terminal boxes including fixing/grouting sunken/ surface as per site requirement covered with suitable laminated sheet for fixing switches / sockets/ regulators etc., including running up of 1.5 Sqmm FRLS copper conductor PVC insulated cable as earth continuity conductor along with wiring and connecting to the common earth dolly all as specified for One light/fan/bell point controlled by one, one way switch 5 amps, SP Note: Cutting/chases will be measured and paid separately
All as per Sl item No 17 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board complete all as specified and as directed.
All as per Sl item No 17 here in before, but for One 3 pin, 5 Amps switch socket outlet point controlled by one switch on the same board.
All as per Sl item No. 17 here in before, but for using 2.5 Sqmm single core copper conductor cable of multistranded PVC insulated sheathed FRLS 1100 Volts grade for 3 Pin 15 Amps switch socket combination point on independent board including running of 2.5 Sqmm FRLS copper conductor PVC insulated cable as earth continuity conductor
S & F switch piano single pole flush type 5 amps, 230 volts complete all as specified and as directed.
S&F bell push 5 A flush type complete all as specified and as directed.
Supply and fix socket outlet flush type multipurpose 2 in 1, 3 Pin, 5 amps, 230 volts complete all as specified and as directed.
S & F switch socket combination flush type multipurpose 2/3 pin 5 amps 2 in 1 230 Volts complete all as specified and as directed.
S & F switch socket combination 2 in 1 multipurpose 3/5 pin 5/15 amps flush type with complete all as specified and as directed.
S & F ceiling rose three terminal surface bakelite type AC 50 Hz 230 volts of size 65 x 50 mm complete all as specified.
S & F electronic type regulator stepped heavy duty for ceiling fan suitable to work on 230 volts complete all as specified and as directed.
S&F bell ding dong working on 230 volts AC Supply complete all as specified and as directed.
S & F lamp holder insulated body surface bakelite with back plate suitable for angle / batten fittings complete all as specified and as directed.
S & F in replacement Fancy type lights (Round Type) of 18/20 watts including LED lamp complete with all accessories complete all as specified and as directed. Make:Havells/Halonix/Luker
S & F in replacement of wall mounted batten type LED light of 10/12 watts with aluminium extruded batten and system lumens of 1200 lm minimum with IP & surge protection alongwith driver efficiency >85% and power factor >0.95 , colour rendering index CRI>80 along with integrated driver complete and connecting to the point wiring with necessary flexible copper conductor of multistranded three core of suitable length from fitting to the ceiling rose complete all as specified and as directed. Make: Havells/Halonix/Luker
S & F in replacement of wall mounted box type LED batten suitable for 20 watts with LED tube 20 watts lamp along with integrated driver and connecting to all accessories from ceiling rose to fitting complete all as specified and as directed. Make: Havells/Halonix/Luker
S & F in replacement of wall mounted batten type LED light with co extruded polycarbonate body suitable for 20W LED lamp along with integrated driver complete and connecting to the point wiring with necessary flexible copper conductor of multistranded three core of suitable length from fitting to the ceiling rose complete all as specified and as directed. Make: Havells/Halonix/Luker
S & F in replacement of wall mounted batten type LED light with co extruded polycarbonate body suitable for 36/40W LED lamp along with integrated driver complete and connecting to the point wiring with necessary flexible copper conductor of multistranded three core of suitable length from fitting to the ceiling rose complete all as specified and as directed. Make: Wipro Model no:D533665 OR Havells Cat part No LHEXACP7IN1W036 or C&S Cat part No LTTB4F40WLED/W
S & F in replacement of LED security Light luminaire 24/25 Watts with deep drawn housing including all accessories and Lamp, with suitable pipe bracket 25 mm dia 0.60 Mtr length fixed on wall with suitable flat iron clamps and nut bolts complete all as specified and as directed. Make: Bajaj Model No:ENXT P 24L WH SY PC SD Havells Cat No - ENDURA SUNDOWNSL25LED765PASYBOPCIHD, C&S Cat Part No LTESS25WLED/LS
S & F in replacement of 10watt bulk head luminaire suitable for outdoor with high brightness giving glare free light complete all as specified and as directed. Make: Havells Cat part HEXAFT10WLED857SSYMBOPC or C&S Cat Part No LTB10WLED
S & F in replacement of MCB SP 6 to 32 Amps 240 volts for fixing on MCB DB's complete all as specified and as directed. Make : Havells - Cat No DHMGCSPF006-032, Standard Cat No - DSMGCSPF006-032, C&S Cat No - CSMBS1C6-32.
S & F in replacement of MCB SPN 40 Amps 240 volts for fixing on MCB DB's all as specified and as directed Make : Havells Cat No DHMGCSNF040, Standard Cat No - DSMGCNF040, C&S Cat No - CSMBS1C40N.
S & F in replacement of MCB Four pole, 415 volts suitable for fixing on MCB DB of capacity 63 Amps all as specified and as directed. Make - Havells Cat No - DHMZCTNF063, Standard Cat No - DSMGCTNF063, C&S Cat No - CSMBS3C63N.
Supply & replace MCCB Four pole, 415 volts suitable for fixing on MCCB DB of capacity 100 Amps complete all as specified and as directed.
Supply & replace MCCB Four pole, 415 volts suitable for fixing on MCCB DB of capacity 160 Amps complete all as specified and as directed.
S & F sheet metal enclosure MCB DB SPN 4 way with 200 amps rated bus bar 240 volts double door with locking system complete all as specified Make : Havells - CAT Part No DHDPSHODRWO4, Standard Cat No - DSDCSHODOW04, C&S Cat No - CSDBSPNPDD04.
All as per Sl item No 42 here in before, but SPN 8 way DB complete all as specified and as directed. Make : Havells - Cat Part No DHDPSHODRWO8, Standard Cat No - DSDCSHODOW08, C&S Cat No - CSDBSPNPDD08.
All as per Sl item No 42 here in before, but SPN 12 way DB complete all as specified and as directed. Make : Havells - CAT Part No DHDPSHODRW12, Standard Cat No - DSDCSHODOW12, C&S Cat No - CSDBSPNPDD12.
S & F in replacement of Horizontal type TPN DB 4 way double door made out of CRCA sheet housing with powder coating & confirming to IS 13032, IS 8623, BS 5486 accommodated suitably in a MS enclosure weather proof made out of 3 mm thick MS sheet having hinged and robust locking arrangement including painting by red-oxide one coat and powder coated all as specified and directed. Make : Havells - CAT Part No DHDNTHODAW04, Standard Cat No - DSDNTSODAW04, C&S Cat No - CSDBTPNPDD04.
S & F in replacement of Single pole and Neutral enclosure with a two pin and earth plug and socket metal clad complete with one single pole MCB 20 Amps (AC Box) complete all as specified and as directed. Make : Havells - CAT Part No DHDPUSN020, Standard Cat No - DSDPUSN020, C&S Cat No - CSDBACBOX020
M & L for Submain wiring with 2 runs of single core 4 Sqmm PVC insulated sheated multistranded FR 1100 volts grade with copper conductor drawn through existing non-metallic rigid PVC conduit and conduit accessories of medium grade not less than 25mm dia including one run of single core 4 Sqmm PVC insulated sheated multistranded 1100 volts grade with copper conductor cable as earth continuity conductor along with the wiring and connected from DB to DB/main board including removing the existing unserviceable submain riwing complete all as specified and as directed. Note: 3 runs of 4 Sqmm cable and 1 run of PVC conduit with accessories shall be measured as 1 unit of running metre.
All as per Sl item No 47, but 2 runs of single core 6 Sqmm and one run of single core 6 Sqmm as earth continuity conductor complete all as specified and as directed. Note: 3 runs of 6 Sqmm cable and 1 run of PVC conduit with accessories shall be measured as 1 unit of running metre.
All as per Sl item No 47, but 2 runs of single core 10 sqmm and one run of single core 10 sqmm as earth continuity conductor complete all as specified and as directed. Note: 3 runs of 6 Sqmm cable and 1 run of PVC conduit with accessories shall be measured as 1 unit of running metre.
Material and labour for earthing with galvanized mild steel earth plate electrode 60 centimetre x 60 centimetre x 6 mm thick buried directly in ground vertically to a depth not less than 2.25 metres below ground level, the top edge of the earth plate at a depth of not less than 1.5 metres below ground level connected to galvanized iron earth wire of 4 mm dia by means of bolts, nuts and washers made out of GI / steel earth wire protected by GI light grade pipe 15 mm bore, 20mm dia light grade galvanised iron pipe with funnel wire mesh for watering and connecting to main switch board / control board all s shown in electrical plate of SSR Pt - I connected to earthing test point and including testing on completion complete all as specified and as directed. NOTE: The unit rate shall also include for excavation, earth work in hard/dense soil, plain cement concrete 1:3:6 type C1 by using 20 mm graded aggregate in pit, 50 mm thick reinforced cement concrete 1:2:4 type B1 using 20 mm graded aggregate cover duly reinforced with 8 mm dia TMT bars @ 100mm centre to centre both ways, CI cover with CI frame hinges, galvanised iron funnel with watering pipe, wire mesh, complete.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earting etc., as required 4mm dia galvanised iron or steel wire complete all as specified and as directed.
M&L for Cutting chases, pinning in. making good to facings where required and pointing in cement mortar 1:3 to ends or edges of andings, steps, cills, sunshades, shelves, lintels, etc., and cutting chases for concealed water tubing or concealed conduit wiring, etc., and making good, cutting not exc 10 cm girth complete all as specified and as directed.
Supply & Replace switch piano single pole flush type 5 amps, 230 volts complete all as specified and as directed.
Supply & Replace switch piano single pole Modular switch 1 way 10 Amps, 1 Module complete all as specified and as directed.
Supply & Replace switch piano single pole Modular switch 1 way 16 Amps, 1 Module complete all as specified and as directed.
Supply & Replace bell push 5 A flush type complete all as specified and as directed.
Supply & Replace Modular Bell Push 6A, 1 Module complete all as specified and as directed.
Supply and Replace socket outlet modular type multipurpose 2/3 Pin, 10 amps, 230 volts combined 2 Module complete all as specified and as directed.
Supply and Replace socket outlet modular type multipurpose 2/3 Pin, 6/16 amps, 230 volts combined 2 Module complete all as specified and as directed.
Supply and Replace socket outlet flush type multipurpose 2 in 1, 3 Pin, 5 amps, 230 volts complete all as specified and as directed.
Supply & Replace switch socket combination flush type multipurpose 2/3 pin 5 amps 2 in 1 230 Volts complete all as specified and as directed.
Supply & Replace switch socket combination 2 in 1 multipurpose 3/5 pin 5/15 amps flush type with complete all as specified and as directed.
Supply & Replace Modular ceiling fan regulator stepped type heavy duty 2 Module suitable to work on 230 volts complete all as specified and as directed.
Supply & Replace electronic type regulator stepped heavy duty for ceiling fan suitable to work on 230 volts complete all as specified and as directed.
Supply & Replace bell ding dong working on 230 volts AC Supply complete all as specified and as directed.
Supply & Replace lamp holder insulated body surface bakelite with back plate suitable for angle / batten fittings complete all as specified and as directed.
M & L bracket made out of GI pipe 25 mm dia bore not less than 1.2 mtr long and fixed on walls with 2 nose MS clamps made out of MS flat 40x5mm thick complete with MS nuts, bolts and washers etc bent to required shape complete all as specified and as directed.
Supply & replace MCB SP 6 to 32 Amps 240 volts for fixing on MCB DB's all as specified and as directed. Make : Havells - Cat No DHMGCSPF006-032, Standard Cat No - DSMGCSPF006-032, C&S Cat No - CSMBS1C6-32.
Supply & replace MCB SPN 40/63 Amps 240 volts for fixing on MCB DB's all as specified and as directed. Make : Havells Cat No DHMGCSNF040, Standard Cat No - DSMGCNF040, C&S Cat No - CSMBS1C40N.
Supply & replace MCB Four pole, 415 volts suitable for fixing on MCB DB of capacity 63 Amps all as specified and as directed. Make: Havells Cat No - DHMZCTNF063, Standard Cat No - DSMGCTNF063, C&S Cat No - CSMBS3C63N.
Supply replace Ultra bright LED polycarbonate tube light 20 watt with very high efficiency suited for installation in existing T8 fitting with G13 lamp holders (single side connection) complete all as specified and directed. Make: Havells cat No PHOTONULTRA2.012 13T8SSTL20WLED 865SPC, C&S Cat No - LT4F20WLEDT8/WD, Halonix Cat Part No HLTD-04-20-CW-PC
Supply and Replace LED lamp 9 Watts complete all as specified and as directed.
Supply and replace PVC Round blocks of 4" complete all as specified and as directed.
Supply and replace PVC Dummy sheets circular type of 4" complete all as specified and as directed.
Supply and replace PVC Dummy sheets circular type of 6" complete all as specified and as directed.
Supply and replace Rigid PVC casing & capping 20/25 mm wide complete all as specified and as directed.
Supply and replace PVC rectangular box (Gang box) with 5 Amps switch socket complete all as specified and as directed.
Supply and replace PVC rectangular box (Gang box) with 5/15 Amps switch socket complete all as specified and as directed.
Supply and replace PVC wire of Flexible cord with copper conductor multistranded of twin core 23/0.198 complete all as specified and as directed.
Supply and replace PVC copper wire of 1.5 Sqmm single core multistranded complete all as specified and as directed.
Supply and replace PVC copper wire of 2.5 Sqmm single core multistranded complete all as specified and as directed.
Supply and replace PVC copper wire of 4 Sqmm single core multistranded complete all as specified and as directed.
Supply and replace PVC copper wire of 6 Sqmm single core multistranded complete all as specified and as directed.
Supply and replace Service wire twin core of 10.0 Sqmm aluminium type flat unarmoured complete all as specified and as directed.
Taking down ceiling fans 48”/56” sweep or Exhaust fans upto 300mm, removing/cleaning of dust properly cleaning, greasing & overhauling of bearings including refixing in same location and connecting up complete all as specified and as directed. Note : Replacement of defective/worn out parts will be measured & paid separately as supply and replace.
Supply & replace 2.00/2.50 Mfd capacitor complete all as specified and as directed.
Supply & replace 3.15/4.00 Mfd capacitor complete all as specified and as directed.
Supply & replace ball bearing/Gun Metal Bush of existing ceiling fans on site complete all as specified and as directed.
Supply & replace Flexible copper three core of size 23/0076” wire/cable complete all as specified and as directed.
Supply & replace ‘U’ clamps complete with nut, bolts & split pins Heavy duty, suitable for existing ceiling fan on site complete all as specified and as directed.
Supply & replace M.S. rod for ceiling fans 3 ft long with both end suitable size holes and cut mark complete all as specified and as directed.
Supply & replace Fan Caps of PVC type suitable for 1200/1400mm sweep complete all as specified and directed.
Supply & replace Nut of bolts washers for fan blades fixing of ceiling fan of any make/size/type as per site requirement ( 6 Nos for each set) suitable for existing ceiling fan on site complete all as specified and as directed.
Material and labour for Rewinding of burnt Ceiling fan motor of size 48"/56" sweep with super enameled copper wire of suitable size as per details given below of any make, type, model incl transporation complete all as specified and as directed.
All as per Item No 94 above, but for exhaust fan motor of sweep upto 300mm complete all as specified and as directed.
Material and labour for Painting of ceiling fans 48”/56” size complete at site, with super synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc complete all as specified and as directed.
Taking down the geysers of capacity 25/35 from its mounting position by removing all water and electric connections and de-assembling the geyser after carrying out the following works:- (a) Descaling, cleaning the inner tank thoroughly and there should not be any bad taste of water. (b) Examining the water tightness of storage tank after cleaning. (c) Examining the physical condition of thermostat, base assembly fusible plug and outer tank for its serviceability. (d) Inspection of pilot lamps. (e) Reassembling the geyser parts and testing including checking all electrical system (ensuring there is no current leakage) and also conducting hydraulic testing. (f) Re-fixing the Geyser and making electric connections, inlet and outlet water connections and testing and checking of all water inlet, outlet valves connected with geysers. Note : Defective /worn out parts if required shall be measured and paid separately under relevant items in this schedule as supply and fix.
Supply and fix braided PVC connection of 2 feet complete all as specified and as directed.
Supply & fix braided rubber PVC connection of 3 feet complete all as specified and as directed.
Supply & fix MS base plate cup any type with screws of suitable size as per requirement complete all as specified and as directed.
Supply & fix heating element of the 1.5 KW rating as required at site including rubber washers of any make and type complete all as specified and as directed.
Supply & fix Steel inner tank of 25 litre capacity geyser tank by made out of steel sheets appropriate thickness complete all as specified and as directed.
Supply & fix thermostat suitable for the geysers of 25 Litres capacities complete all as specified and as directed.
Supply & Replace Air Release Valve suitable for geyser 25 ltrs complete all as specified and as directed.
Supply and Replace Indication lamp of Existing Size/Model (Set of Two) Red & Green complete all as specified and as directed.
S&F in replacement of 1100 Volt grade cable flexible 3 core PVC insulated PVC sheathed with stranded copper conductor of size 2.5 Sqmm complete all as specified and as directed.
Supply and Fix in replacement of Rigid non-metallic PVC conduit 25mm exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc., complete all as specified and as directed.
Supply and Fix in replacement of Rigid non-metallic PVC conduit 20 mm exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc., complete all as specified and as directed.
Detailment of tradesman as per Job card for disconnecting and removing any fitting of any size from any height, stripping out the fitting for examine replacement of US spare parts, reassembling, refixing in original position including minor repairs for the smooth functioning testing complete all as specified and as directed.
Description as per item No 109, but for MCBs complete all as specified and as directed.
Description as per item No 109, but for Switch boards complete all as specified and as directed.
gsrinivasarao
M/S P UDAY RAJ CONSTRUCTION
Universal refrigeration and Engineering Company
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .