Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.3 LAdmitted-Finance | ₹8.3 L | L1 | Admitted-Finance |
| 2 | L2₹8.4 LAdmitted-Finance | ₹8.4 L | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M/S KALHANA ASSOCIATES L2 | Vibgyor Power and Suppliers L1 |
|---|---|---|---|---|---|
| 1.01SITC of 11kV VCB panel along with allied equipment for Water supply Scheme Muradpora Canal Colony Mangnipora Bandipore at Receiving Station Aloosa. | |||||
| 1.02 | Supply ,Installation Testing and Commissioning of 11 kV VCB Panel Board (12 kV, 1250A, 25 kA, indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port (CTR 100-50/5-5 Amps) GTp To be approved | 1 | No | 5,70,000 ₹5.7 L | 6,30,000 ₹6.3 L |
| 1.03 | Supply ,Installation Testing and Commissioning of 11kV, Gapless Surge Arrestor,9 kV ,10 kA ,LA with Polymer housing, Stn. Type. | 1 | Set | 3,000 ₹3,000 | 1,500 ₹1,500 |
| 1.04 | Supply ,Installation Testing and Commissioning of 11 kV 3-Core XLPE 185 mm² armoured, FR | 50 | Meter | 1,12,500 ₹1.1 L | 50,000 ₹50,000 |
| 1.05 | Supply ,Installation Testing and Commissioning of 11kV 185 sq.mm 3-core Indoor Heat Shrinkable Cable Termination Kits | 1 | Set | 2,500 ₹2,500 | 900 ₹900 |
| 1.06 | Supply ,Installation Testing and Commissioning of 11kV 185 sq.mm 3-core outdoor Heat Shrinkable Cable Termination Kits | 1 | Set | 2,500 ₹2,500 | 900 ₹900 |
| 1.07 | Supply ,Installation Testing and Commissioning of 9mt long ST poles with base and top (ST 410 SP 33) . | 2 | No | 42,000 ₹42,000 | 37,000 ₹37,000 |
| 1.08 | Supply ,Installation Testing and Commissioning of 11 kV Isolator, Double Break,3-pole, 600 Amp, horizontal mounting Type, with Earth Switch. (set of 3 No's) | 2 | Set | 50,000 ₹50,000 | 48,000 ₹48,000 |
| 1.09 | Supply and laying of Cement Bottoming of ST poles 1:2:4 mix as per REC standards (0.48 cum/pole) | 2 | No | 7,000 ₹7,000 | 2,400 ₹2,400 |
| 1.10 | Supplying and fixing of Danger Plates with Clamps | 2 | No | 200 ₹200 | 20 ₹20 |
Updated dates
Tender Value
₹9.7 L
EMD Value
₹19,300
Closing Date
9 Feb 2026, 2:00 pmClosed
EXECUTIVE ENGINEER STD GANDERBAL
DIV OFFICE STD GANDERBAL
SITC of 11kV VCB panel along with allied equipment for Water supply Scheme Muradpora Canal Colony Mangnipora Bandipore at Receiving Station Aloosa.
2026_PDD_300427_1
STDGBL e-NIT NO 30 OF 2025-26 DATED 12-01-26
Open Tender
Electrical Works
60 days
BANDIPORA
REFER SBD
8 documents required · 8 mandatory
₹500
EXECUTIVE ENGINEER STD GBL
₹19,300
17 Feb 2026
12 Jan 2026
10 Feb 2026
12 Jan 2026
9 Feb 2026
14 Jan 2026
12 Jan 2026 - 14 Jan 2026
SITC of 11kV VCB panel along with allied equipment for Water supply Scheme Muradpora Canal Colony Mangnipora Bandipore at Receiving Station Aloosa.
Supply ,Installation Testing and Commissioning of 11 kV VCB Panel Board (12 kV, 1250A, 25 kA, indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port (CTR 100-50/5-5 Amps) GTp To be approved
Supply ,Installation Testing and Commissioning of 11kV, Gapless Surge Arrestor,9 kV ,10 kA ,LA with Polymer housing, Stn. Type.
Supply ,Installation Testing and Commissioning of 11 kV 3-Core XLPE 185 mm² armoured, FR
Supply ,Installation Testing and Commissioning of 11kV 185 sq.mm 3-core Indoor Heat Shrinkable Cable Termination Kits
Supply ,Installation Testing and Commissioning of 11kV 185 sq.mm 3-core outdoor Heat Shrinkable Cable Termination Kits
Supply ,Installation Testing and Commissioning of 9mt long ST poles with base and top (ST 410 SP 33) .
Supply ,Installation Testing and Commissioning of 11 kV Isolator, Double Break,3-pole, 600 Amp, horizontal mounting Type, with Earth Switch. (set of 3 No's)
Supply and laying of Cement Bottoming of ST poles 1:2:4 mix as per REC standards (0.48 cum/pole)
Supplying and fixing of Danger Plates with Clamps
Supplying and fixing of Anticlimbing devices with clamps
Supply and laying of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
Providing and Painting of Aluminium paint on ST Poles as per REC standard
Providing and Painting of Red Oxide paint on ST Poles as per REC standard
Supply ,Installation Testing and Commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply ,Installation Testing and Commissioning of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
Supply ,Installation Testing and Commissioning of Galvanised iron of sorts
Dismantling of existing 1.8 cum RCC Structure and constructing of new RCC Structure (1:1½:3 (1 cement :1½ coarse sand :3 graded stone aggregate 20 mmnominal size)) for extension of cable trenchue for installation of new VCB Panel
Providing adaptor box with flexible copper bus bar 1250 Amp to match the existing panels with the new panels including all accessories.
Supply of Galvanised nut and bolts
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.60 MB
GTPmuradpora.pdf
Other Document • 0.71 MB
BOQ_974594.xls
BOQ • 0.25 MB
SBD30.pdf
Tender Documents • 1.58 MB
Download all tender documents and submit your bid