SENIOR MANAGER MAINTENANCE
SITC of Electrical Installations and allied work for Township Substation Building at HAL, Lucknow
HAL-ADL/9995/26-27/TOWNSHIP-SUBSTATION/2044::01
HAL-ADL/9995/26-27/TOWNSHIP-SUBSTATION/2044
Open Tender
Works
9 days
Accessories Complex - Lucknow Divn - Plant Maintenance
AS PER ELIGIBILITY CRITERIA MATRIX
₹0
₹11.3 L
13 Nov 2026
13 Nov 2026
11 Dec 2026
11 Dec 2026
24 Nov 2026
HINDUSTAN AERONAUTICS LIMITED ACCESSORIES DIVISION, LUCKNOW PQ FORM/ELIGIBILITY CRITERION-MATRIX
NAME OF THE WORK: "SITC of Electrical Installations and allied work for Township Substation Building at HAL, Lucknow"
Estimated Cost (in Rs.) 56,348,495.20
S# Intending bidders must meet the following eligibility criterion: COMPLIED/NOT COMPLIED
PART-A: Desirable Criteria
1 Name of the Individual / Firm / Company: * Mandatory
2 Type of ownership Pvt. Ltd./ Proprietorship/Partnership/ Public limited/ Govt. Agencies/ Trust If Other, please specify
3 Details of Constitution or Legal Status such as certificate of incorporation, shops and establishments, Contractor registration No etc.,
4 Registration with HAL/ other organization if any
5 Address of Correspondence:
Contact Details: Contact person name: Designation: Mobile No:. Ph. No. with STD code: Email Id :
6 Contractor must give his acceptance to provide services as per ‘Requirement, Scope of work, Drawings’ and ‘Terms & Conditions' contained in Technical Bid.
7 Self attested copy of PAN Registration certificate issued by income tax authority.
PART-B: Essential Criteria
8* Self attested Copy of GST Registration Certificate.
9* Average annual turnover during the last 3 years, ending 31st March of previous financial year, should be at least 30% of the approximate estimated amount put to tender. Profit & loss statement duly certified by chartered accountant with UDIN shall be considered for evaluation of turnover for the respective financial Year i.e. Fin Year 2022-23, 2023-24 & 2024-25. 16,904,549.00
10* Valid “A” class Electrical contractor licence of appropriate voltage issued by any state Govt. Under clause 45 of Indian Electricity Rules 1956 or as amended from time to time.
11* The Solvency required will be 40% of the approx. estimated amount put to tender. The solvency certificate shall be from a nationalized or scheduled bank and issued within a period of 12 months from the final date of Submission of tender (in Rs.). 22,539,399.00
12* EMD amount (in Rs.) 1,126,970.00
13* Self attested Copy of PF Code Certificate(if applicable).
14* Self attested Copy of ESI Number certificate (if applicable).
15* Experience of having successfully completed similar works as indicated in the work details during last 7 years ending last day of month previous to the one in which applications are invited should be either of the following (in Rs.):-
i Three similar completed each work costing not less than 40% of estimated amount. OR 22,539,399.00 PO no.: Value : Completion Date: Customer:
22,539,399.00 PO no.: Value : Completion Date: Customer:
22,539,399.00 PO no.: Value : Completion Date: Customer:
ii Two similar completed work costing not less than the amount equal to 50% of the estimated cost. OR 28,174,248.00 PO no.: Value : Completion Date: Customer:
28,174,248.00 PO no.: Value : Completion Date: Customer:
iii One similar completed work costing not less than the amount equal to 80% of the estimated cost. 45,078,797.00 PO no.: Value : Completion Date: Customer:
16* Bid Capacity: List A and B to be prepared by Bidder and attached separately. List A: list of value of works completed in last five years as specified duly certified by Chartered Accountant. List B: Details of existing commitments and ongoing works to be completed by Dec'26 duly certified by Chartered Accountant.
i. Bidder has to provide the list of value of works completed in last five years i.e from Apr' 21 onwards to March'26. (List A) ii.Details of existing commitments and ongoing works to completed by Aug' 27. (List B) Bid capacity of the bidder shal be calculated using formula 2xAxN-B, where N is number of years for completion of subject project/contract. Bidder shal only be qualified only if their available bid capacity is more than the estimated project cost.
17* Integrity Pact:
The Integrity Pact agreement (Omni or standalone) is to be executed by the Contractor on Rs.200/- non judicial stamp paper and to be uploaded along with the other documents. Please note original to be sent along with the EMD (if not transferred online) and tender cost (if not transferred online),if any, to HAL. Format of Integrity pact is available in Technical bid.
PART-C: Declaration
16 DECLARATION I ACCEPTED/NOT ACCEPTED
The document being viewed / downloaded from the website and having read & understood all the contents of the tender document mentioned under terms and conditions including price bid do hereby accept all the terms and conditions laid down in the said Tender document and will abide by the same on acceptance and ward of work.
17 DECLARATION II ACCEPTED/NOT ACCEPTED
I/We declare and confirm that - 1. All information and attachments submitted along with this offer are true and correct. 2. I/We are aware that any false information provided herein will result in the rejection of my offer . 3. I/We shall not make refund claims of expenditure incurred in processing this offer. 4. I / We aware that document sought only be uploaded for evaluation of offer. 5.I/We are not debarred / blacklisted from any Govt agencies, if debars for specified period reason for debar and copy of resumption of same shall be provided. 6. I/We have not concealed any information which may adversely effect my qualification.
18 DECLARATION III ACCEPTED/NOT ACCEPTED
I/We declare and confirm that all the documents related to NIT mentioned at Technical Bid Document Sl.No.2 and 3 have been attached with the technical bid.
Name of Bidder:
* 1. To be filled by Bidder essentially and carefully. Supporting documents must be attached as proof. Clarifications shall be sought w.r.t. information provided with tender documents. 2. Similar works implied that works related to HT/LT Electrical Works in nature. Mere supply of electrical goods does not mean qulification in the tender. 3. Scanned copy of completed work orders and completion certificate issued by respective clients to be attached. If the completion certificate is form private organization the same shall be uploaded with TDS certificate. 4. The work shall be completed as a whole, Partial value/completion will not be considered. 5. The Bidders are requested to attach scan copies of all the relevant / desired / required proofs/ documents on e-portal, failing which tender shall be summarily rejected without assigning any reason to bidders.
SITC of Electrical Installations and allied work for Township Substation Building at HAL, Lucknow
Sl.No Description Unit Qty Rate Total
A Sub Head: A(Sustation related work)
1 Supply, Installation, Testing and Commissioning of Safe Plus V vacuum circuit Breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbar,interlocking, earthbar and stored spring energy mechanism, 12KV, 630A, 21KA/3Sec, One side extensible, Motorised, Indoor Type, SF6 Gas Insulated, Ring Main unit with Six(6) Vaccum Circuit Breakers (One Incommer and Five Outgoings), Air Insulated Bus PT Panel Compact Type(Configuration:VVVVV+V+M) Metering 1. Further standard essential accessories like operating handle , Two set of Gloves, HT Terminal Boots-06 Nos etc are included in the scope of supply. The detail technical specification of HT Panel shall be as per Annexure-I and the work shall be carried out as per direction of engineer incharge. Make: ABB/Schneider/L&T/Siemens Set 1.00 0.00
2 Supply, Installation, Testing and commissioning of 415V, 50Hz, 2000A , 3 phase, 4wire, Air Insulated bus duct(AIBD) complete with all necessary straight lengths, bends, offsets, flanges, end covers, flexible conncetion, expansion joints, jointing Hardware, Hangers/Supports, earthing arrangement and accessories. Bus Duct shall be totally enclosed, non segregated type and suitable for indoor installation. Busbar shall be of high conductivity electrolytic copper or aluminium, properly supported and insulated from the enclosure. The enclosure shall be fabricated froom corrosion resistant CRCA/GI/ Aluminium sheet of adequate thickness and mechanically strong enough to withstand transportation, Installation and Short circuit stresses. Electrical Rating:- Rated Current: 2000 A Rated Voltage:415V AC System 3-Phase, 4 Wire Frequency :50 Hz Rated Insulation Voltage: 1000V AC Minimum Short time withstand Current: 50kA for 1 Sec Peak Withstand Current: 105 kA minimum Neutral Conductor: 100% rated Earthing: Continuous electrical continuity of enclosure with suitable earth connection at both ends. Protection: Minimum enclosure protection shall be IP55 Joints: Bus Duct joints shall use high pressure bolted joints with suitable jointing hardware. contact surface shall be suitably plated/protected against oxidation. Joints covers shall provide same degree of protection as the bus duct enclosure. Temperature Rise: Temperature rise shall remain within the permissible limit specified in IEC 61439-1 and IEC 61439-6 at rated current. Standard: Bus duct shall comply with IEC 61439-1 and IEC 61439-6.Design verification and routine verification shall be carried out as required by applicable standard. Testing: Manufacturer shall submit routine verification and test certificate and design verification document. Test shall include dielctric properties, continuity of protective circuits, temperature rise/verification/design verification, short circuits withstand capability and enclosed protection as applicable. Note:- Drawing of the whole bus duct system must be get approved from EIC before the fabrication work. Supply of Straight Run (Vertical / Horizontal) 2000A Running Meter 45.00 0.00
3 Supply of Edgewise / Flatwise Elbows 2000A Set 12.00 0.00
4 Supply of Flange End 2000A Set 6.00 0.00
5 Supply of Adaptor Box 2000A only fabrication Set 6.00 0.00
6 Supply of Rubber Bellows at Transformer end Set 6.00 0.00
7 Supply of copper Flexible Connector & Terminations 2000A Set 6.00 0.00
8 Installation, testing and commisioning charges for complete bus duct sytem from transformer end to LT panel(Complete) including all type of consummable items . Enclosures at Transformer End termination is also included in the scope of supply. The work shall be done as per direction of engineer in-charge. Running Meter 45.00 0.00
9 Supply, Installation, Testing and Commissioning of Main LT Panel as per IEC 61439 with EMS and Gas suppression system with detail technical specification as per Annexure II. The EMS sytem shall be real time monitoring of all essential electrical parameter and shall have the storage capacity of one year data and two nos of latest 21.5 Inch Full HD (1920 X 1080) IPS, Antiglare i5, 256 GB SSD +1TB HDD) dispaly unit. Incomer: 1600A 4P 50kA EDO ACB, Release: Microprocessor based Trip Unit (with current metering), Under Voltage Release, Multifunction Energy Meter with RS485, Parameters: Volts, Amps, PF, THD, F, W, Wh, VA, VAh, Var, Varh, Runhrs, Onhrs, Interupts with LED indicators (R/Y/B/Trip/OFF indicator) x 3 Nos Buscoupler & DG Panel: 2000A 4P 50kA EDO ACB, Release: Microprocessor based Trip Unit (with current metering), Under Voltage Release x 3 nos Outgoings: 1. 1000A 4P 50kA EDO ACB, Release: Microprocessor based Trip Unit (with current metering), Under Voltage Release x 3 nos 2. 400A 4P 50kA EDO MCCB, Release: Microprocessor based Trip Unit (with current metering) or equivalent SFU 3P with fuse x 18 Nos. 3. 250A 4P 50kA EDO MCCB, Release: Microprocessor based Trip Unit (with current metering) or equivalent SFU 3P with fuse x 12 Nos. 4. 630A 4P 50kA EDO MCCB, Release: Microprocessor based Trip Unit (with current metering) or equivalent SFU 3P with fuse x 3 Nos. Under Voltage Release, Multifunction Energy Meter with RS485, Parameters: Volts, Amps, PF, THD, F, W, Wh, VA, VAh, Var, Varh, Runhrs, Onhrs, Interupts with LED indicators (R/Y/B/Trip/OFF indicator) The scope of work include the additional supply of following: 1) 1600 Amp ACB:- 01 Nos, 2) 2000Amp ACB:-01 Nos, 3) 400 Amp MCCB/SFU : 04 Nos,4) 250 Amp MCCB/SFU:04 Nos 5) 630 Amp MCCB/SFU : 01 Nos with Fuses of same make & model as installed in LT panel. * Note: Vendor has to use either SFU or MCCB as a whole to meet the homogeneity of LT Panel. Set 1.00 0.00
10 Supply, Installation, Testing and Commissioning of padestal DB 250A 4P 36kA MCCB with Microprocessor Based ETS 6 Trip Unit (built in LSIG protection),Type: EasyPact CVS or equivalent SFU 3P with fuse. The detail technical specification shall be as per Annexure II. Nos 1.00 0.00
11 Supply, Installation, Testing and Commissioning of of 1 MVA (continous loading), 11/0.433 KV, BEE 5 Star rated (Corresponding Level as per BIS amended upto date of receipt of tender) , 3 Phase, 50 Hz, Dyn 11 vector group, ONAN Oil Natural Air Natural] copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better),Dielectric material shall be type -A, suitable for out door/indoor applications with OFF Load Tap Changer (OLTC) on HV side having AVR relay and Remote Tap Changer Control (RTCC) for automatic sensing of incoming voltage, automatic operation of OLTC and facility for remote and manual operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, having cable end boxes on HV side suitable for 3 x 185 sqmm XLPE cable of 11 KV grade, including bus trunking arrangement on LV side, including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions as per relevant IS 1180 (Part-3) including first filling of filtered dehydrated Synthetic organic Ester oil, i/c supplying and grouting of suitable M.S. Channel with all accessories and transformer shall be confirming to IS : 2026 (Part 1 to Part 5), IS : 1180 (Part-3) complete in all respects etc as required at site. (losses at 50% loading < 3600 watt, losses at 100% loading < 10000 watt) including inspection charges if required including charges for inspection at manufacturer. Nos 1.00 0.00
12 Charges for Testing and Inspection of substation for which Supply & Installation of safety equipments MAT and fire Extinguishers and CEA inspection charges i. Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical safety purpose as per IS 15652-2006 or lastest amendment suitable for electrical shock safety of size 2mtr (L)x 1 mtr(W), Qty -20 Nos. ii. CO2 Cylinders (10 Nos.) iii. Meeting the requirement eg SLD etc for CEA Inspection, coordinating, commissioning charges iv. Danger Notice Board-10 Nos v. Sand Buckets with stand as per statutory requirement-03 Nos vi. First Aid Box-02 Nos etc are included Job 1.00 0.00
13 Supply Installation Testing and commissioning of complete set of maintenance free chemical earthing with copper bonded electrode Diameter 17.2 mm(approx) or Pipe in Pipe electrode 100 mm, Length 03 Meter UL listed with min 80 X 6 X 150 mm copper strip exothermally welded at top of the rod in T shape for connecting strip or wire with RoHS compliance for enviromrntally carbon based backfill compound (Maintenance Free Type) -25 KG X 2 Bag with 400 mm X 400 MM CI Pit Cover with civil work and checking of earth resistance less than 3 Ohms. Nos 26.00 0.00
14 Supply and laying of 50x6 mm size G.I. Earth Strip. The work includes bending, welding, connecting etc. as per site requirement. If earth strip is to be laid under ground than floor cutting work/ digging of soil will be done without any extra cast, if earth strip is laid on wall/pucca trench, the strip shall be properly supported & saddled. Complete job. Work is to be done as per the direction of engineer in charge. Mtrs 200.00 0.00
15 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. The work includes bending, welding, connecting etc. as per site requirement. If earth wire is to be laid under ground than floor cutting work/ digging of soil will be done without any extra cast, if earth wire is laid on wall/pucca trench, the wire shall be properly supported & saddled. Complete job. Work is to be done as per the direction of engineer in charge. Mtrs 200.00 0.00
B Sub Head: B(Building Electrification Work)
16 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in conceiled/surface/ recessed medium class PVC conduit, with suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Nos 30.00 0.00
17 Wiring for light point one plus one with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in conceiled/surface/ recessed medium class PVC conduit, with suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Nos 10.00 0.00
18 Supplying and fixing of 5/6 A switch modular on the existing modular plate & switch box including connections but excluding modular plate etc as required. Nos 40.00 0.00
19 Supplying and fixing of 6 module Modular base & cover plate on existing modular metal boxes etc as required. Nos 6.00 0.00
20 Supplying and fixing of 12 moldule Modular base & cover plate on existing modular metal boxes etc as required. Nos 4.00 0.00
21 Supplying and fixing of 8 moldule Modular base & cover plate on existing modular metal boxes etc as required. Nos 6.00 0.00
22 Supplying and fixing of 3 Module Modular base & cover plate on existing modular metal boxes etc as required. Nos 25.00 0.00
23 Supplying and fixing of 1 or 2 Module Modular base & cover plate on existing modular metal boxes etc as required. Nos 2.00 0.00
24 Supplying and fixing of 3 pin 5/6 A socket outlet modular on the existing modular plate & switch box including connections but excluding modular plate etc as required. Nos 10.00 0.00
25 Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. Nos 10.00 0.00
26 Wiring for circuit/ submain wiring along with earth wire with the 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire +1 x1.5 sq mm inverter wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. Mtrs 150.00 0.00
27 Wiring for circuit/ submain wiring along with earth wire with the 2 X 4 sq. mm + 1 X 1.5 sq. mm earth wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. Mtrs 250.00 0.00
28 Supplying and fixing of 15/16 A Mini MCB/switch modular on the existing modular plate & switch box including connections but excluding modular plate etc as required. Nos 25.00 0.00
29 Supplying and fixing of 6 pin 15/16 A socket outlet modular on the existing modular plate & switch box including connections but excluding modular plate etc as required. Nos 25.00 0.00
30 Supplying and fixing of 4 way (4 + 12), Double door, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V conceiled to the wall as per direction of engineer incharge. Nos 2.00 0.00
31 Supplying and fixing of 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of single poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Nos 24.00 0.00
32 Supplying and fixing of four pole, 415 V, 63 Amp isolator in the existing MCB DB complete with connections, testing and commissioning etc as required. Nos 2.00 0.00
33 Supplying and fixing of two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc as required. . Nos 10.00 0.00
34 LED Panel light 1 x 4 ft., (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 1 x 4 ft., 40 W of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends ,CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as 44 DELHI SCHEDULE OF RATES (E&M)-2025 required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm). The installation work shall be done by suspension of light fitting through 100 cm long downrod on both side or as directed by engineer incharge. Nos 30.00 0.00
35 Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 100 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value 63DELHI SCHEDULE OF RATES (E&M)-2025(CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion)less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. Size 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) Nos 30.00 0.00
36 Supply of heavy duty exhaust fan with louvers of Size 450 mm with minimum warranty of one year. Nos 20.00 0.00
37 Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. of size 450 mm sweep or as required. Nos 14.00 0.00
38 Supply and Installation of wall mount split air conditioner with copper evaporator and condensor, Condensor Type: Inverter- Variable Speed, 1.5 Ton, BEE Star Rating- 5star, Eco Friendly Referigerant R32 with warranty of compressor-10 Year, Warranty on PCB 05 Year and overall warranty 01 year Make:- Voltas/Hitachi/lloyd/Daikin/Blue star Nos 4.00 0.00
C External Electrification work
39 Supply of 07 Mtrs. high Hot Dip Galvanized OCTAGONAL continuously tapered street light pole (bottom size 130 mm min. & top size 70 mm min.) with single arm GI bracket (length of bracket shall be based on design) for installation of LED Street light luminaire (90 Watt) suitable for wind velocity as per IS 875 (but not less than 50 m/sec.), fabricated out of 3 mm MS plate in single section, suitable for installation on a precast foundation with supply of minimum 4 nos. of foundation bolt & anchor plate, rigid flange plate (200x200x12mm min.) welded with the base of pole from inside & outside both sidesfor fixing on foundation bolts complete as reqd. for structural stability as specified, weather proof and vandal resistant of 500mm length door flush with the exterior surface containing a terminal plate of 5 mm thick backlite sheet with 32 Amp heavy duty connector for loop in loop out cable terminations suitable for upto two numbers 4 core 25 Sq.mm cables & 2A DP MCB for each fixture connections, earthing bolts for continuous earth connection complete and wiring upto the street light fitting arm as required. Nos 10.00 0.00
40 Erection of 07 Mtrs. high Hot Dip Galvanized OCTAGONAL continuously tapered street light pole (bottom size 130 mm min. & top size 70 mm min.) with single arm GI bracket in cement concrete foundation 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation with nut and bolt etc including excavation and refilling etc. as required. Nos 10.00 0.00
41 Supply and Installation of LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥105 <120 lm/Watt) of 90 W street light Fitting. Nos 10.00 0.00
D Shifting of Cable and allied works from Old Substation To New substation
42 Laying of one number PVC insulated and PVC sheathed / XLPE Aluminium power cable of 1.1 KV grade of following size direct in ground 1 meter deep including excavation, sand cushioning, protective covering with B class of brick in C formation and refilling the trench etc as required. Size of Cable 4 Core 35 Sqmm to 95 sqmm. Mtrs 200.00 0.00
43 Laying of one number PVC insulated and PVC sheathed / XLPE Aluminium power cable of 1.1 KV grade of following size direct in ground 1 meter deep including excavation, sand cushioning, protective covering with B class of brick in C formation and refilling the trench etc as required. Size of Cable 3.5 Core 185 Sqmm to 400 Sqmm. Mtrs 200.00 0.00
44 Laying of one number additional PVC insulated and PVC sheathed / XLPE Aluminium power cable of 1.1 KV grade of following size direct in ground 1 meter deep including excavation, sand cushioning, protective covering with B class of brick in C formation and refilling the trench etc as required. Size of Cable 4 Core 35 Sqmm to 95 sqmm. Mtrs 1,000.00 0.00
45 Laying of one number additional PVC insulated and PVC sheathed / XLPE Aluminium power cable of 1.1 KV grade of following size direct in ground 1 meter deep including excavation, sand cushioning, protective covering with B class of brick in C formation and refilling the trench etc as required. Size of Cable 3.5 Core 185 Sqmm to 400 Sqmm. Mtrs 3,400.00 0.00
46 Supply of PVC insulated and PVC sheathed / XLPE Armoured , Multistrand, LT Aluminium power cable of 1.1 KV grade as per IS 7098 (Part 1) 1988 with latest Amendments. Size of cable. 4 Core X 25 Sqmm Mtrs 300.00 0.00
47 Supply of PVC insulated and PVC sheathed / XLPE Armoured , Multistrand, LT Aluminium power cable of 1.1 KV grade as per IS 7098 (Part 1) 1988 with latest Amendments. Size of cable. 3.5 Core X 95 Sqmm Mtrs 400.00 0.00
48 Supply of PVC insulated and PVC sheathed / XLPE Armoured , Multistrand, LT Aluminium power cable of 1.1 KV grade as per IS 7098 (Part 1) 1988 with latest Amendments. Size of cable. 3.5 Core X 120 Sqmm Mtrs 1,500.00 0.00
49 Supply of PVC insulated and PVC sheathed / XLPE Armoured , Multistrand, LT Aluminium power cable of 1.1 KV grade as per IS 7098 (Part 1) 1988 with latest Amendments. Size of cable. 3.5 Core X 240 Sqmm Mtrs 1,500.00 0.00
50 Supply of PVC insulated and PVC sheathed / XLPE Armoured , Multistrand, LT Aluminium power cable of 1.1 KV grade as per IS 7098 (Part 1) 1988 with latest Amendments. Size of cable. 3.5 Core X 400 Sqmm Mtrs 800.00 0.00
51 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground 1.20 mtr deep, including excavation, sand cushioning, protective covering with B class of brick in C formation and refilling the trench or in existing trench/ double arm pole etc as required. Mtrs 1,900.00 0.00
52 Supply of HT Aluminium Cables, Stranded Compacted, Circular Aluminium Conductor, Conductor Screen with Extruded Semi Conducting Compound, XLPE Insulated, Insulation Screening with Extruded Semi Conducting Compound in Combination with Copper Tape, Cores Laid Up, Innersheath of PVC, Galvanised Steel Flat Strip Armoured, & Overall PVC Sheathed Cable Conforming to IS 7098 (Part-2) 2011 with latest amendment. Size of cable. 3 Core X 185 Sqmm Mtrs 2,000.00 0.00
53 Supply and installation of 800 VA Digital power inverter with 12 volts exide maintenance free battery, complete item. Fitted with cooling fan, facility for protection from over current and over loading, short circuiting,. Input voltage: 155 to 290 volts AC, Output voltage: 230 v +/- 3%, 50 Hz. Temp. 0 to 5 Deg.c. Battery voltage 12 VDC, deep discharge, overcharge, charging voltage: 13.7v, no load current less than 5 A DC (ideal case), 150 AH. Work is to be done as per the direction of engineer in charge. Complete job. All material required for the work shall be supplied by the contractor. Make- Microtek/Su-kam/Luminous/APC Nos 1.00 0.00
54 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Size of cable. 4 Core X 25 Sqmm Nos 20.00 0.00
55 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Size of cable. 3.5 Core X 95 Sqmm Nos 20.00 0.00
56 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Size of cable. 3.5 Core X 120 Sqmm Nos 30.00 0.00
57 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Size of cable. 3.5 Core X 240 Sqmm Nos 30.00 0.00
58 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Size of cable. 3.5 Core X 400 Sqmm Nos 8.00 0.00
59 Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Size of cable. 4 Core X 25 Sqmm Nos 4.00 0.00
60 Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Size of cable. 3.5 Core X 95 Sqmm Nos 10.00 0.00
61 Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Size of cable. 3.5 Core X 120 Sqmm Nos 20.00 0.00
62 Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Size of cable. 3.5 Core X 240 Sqmm Nos 25.00 0.00
63 Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Size of cable. 3.5 Core X 400 Sqmm Nos 10.00 0.00
64 Supplying and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : Size of cable. 3 Core 120/185 sq. mm Nos 10.00 0.00
65 Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminiumconductor cable of 11 KV grade as required : Size of cable. 3 Core 120/185 sq. mm Nos 1.00 0.00
66 Supplying and making straight through cable jointing with cast resin compound, including ferrule and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required Size of cable. 3 Core 120/185 sq. mm Nos 4.00 0.00
67 SITC of Control Panel, double door, 415 V, 50Hz, having Incomer of 400A, 50kA 4 Pole MCCB, Ics=100% Icu rating or equivalent SFU with fuse, Ammeter, Voltmeter, phase indicating lamps, ON, OFF, trip indicating lamps, Copper Bus Bar 500A. OUTGOING 2 nos. for 250A, 50 KA TPN MCCB/SFU with contractor and timer for auto manual operation of street lights etc. Note: Drawing of control panel shall be get approved before fabrication work and making of foundation for installation work is in the scope of supplier. Nos 1.00 0.00
68 Supply & Installation of feeder pillar box outdoor type double door , vermin and weather proof made out of 14 SWG thick CRCA sheet including canopy type roof 15 cm extended in all side and two part hinged door in front side with knobs closing the front side door gasket arrangement and back side fixed with Nut, bolts and gasket, including provision of one set of aluminium busbar 400A rating for phase and 240 A for neutral fixed on DMC/SMC insulator with RYB Black colour code with heat shrinkable PVC sleeves and holes in bus bar strip and provision of suitable cable gland for cable entry including two coat of powder quoted paint complete and installation on PCC foundation with following: 1. Incoming:- MCCB/Switch Fuse unit 250A rating with HRC fuses Knife Type Make: L&T/Siemens - 01 Nos 2. Outgoing: 32/63 Amp HN Type Fuse Fitting L&T/Siemens - 06 Nos per Phase 3. Phase indicating lamps for RYB on Each incomming/outgoing 5. Voltmeter(0-500v) & Ammeter (0-200A) on each incomming/outgoing 6. Digital Multi Function Meter of Make: L&T/Essen/AE/Rishab/Siemens Note: Drawing of feeder pillar shall be get approved before fabrication work and making of foundation for installation work is in the scope of supplier. Work is to be done as per the direction of Engineer- In-Charge Nos 1.00 0.00
69 Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required Nos 40.00 0.00
70 Only labour charge for removal of old unground cable by digging soft soil upto 1.5 mtr deep and taking out cable for re-routing of cable. The scope of work include the disconnection of cable from panel and the removal of underground cable laid in road crossing also. Mtrs 2,000.00 0.00
71 Supply and fixing of 1.5 ft inner dia, RCC Hume Pipe Length 2.5 Mtr for crossing of drain line near new proposed substation. Nos 4.00 0.00
72 Only labour charge for removal of all electrical connection including earthing of 1 MVA Transfomer at existing substation and shifting it safely to the new substation using Hydra around 200 meter distance and positioning it properly at its new foundation. Nos 3.00 0.00
E Telephone Related Work
73 Supply of 0.5 mm dia copper conductor PVC insulated PVC sheathed telephone wire as required of following sizes(Make: Polycab / Delton / Finolex): 2 Pair (4 Core) Mtrs 90.00 0.00
74 Supply of 0.5 mm dia copper conductor PVC insulated PVC sheathed telephone wire as required of following sizes(Make: Polycab / Delton / Finolex): 5 Pair (10 Core) Mtrs 90.00 0.00
75 Laying and fixing of 0.5 mm dia copper conductor PVC insulated PVC sheathed telephone wire in etc. as required of following sizes (Make: Polycab / Delton / Finolex): 2 Pair (4 Core) Mtrs 90.00 0.00
76 Laying and fixing of 0.5 mm dia copper conductor PVC insulated PVC sheathed telephone wire in etc. as required of following sizes (Make: Polycab / Delton / Finolex): 5 Pair (10 Core) Mtrs 90.00 0.00
77 Supply of 0.5 mm dia 10 pair armoured copper conductor PVC insulated PVC sheathed telephone wire(Make: Polycab / Delton / Finolex) Mtrs 100.00 0.00
78 Laying of 0.5 mm dia 10 pair armoured copper conductor PVC insulated PVC cable with digging of 90 cm dept with bricks and sand trench. Mtrs 80.00 0.00
79 Supplying and fixing of 2 Modular Box with modular base, cover plate and telephone socket as required. Nos 3.00 0.00
80 Supplying and fixing of 50 pair telephone DB with Frame and Krone Module. Nos 1.00 0.00
81 Wall cutting for rotuing of PVC Pipes Mtrs 20.00 0.00
F IT Related work
82 Supplying and drawing 24 core Fiber Optic Cable having corrugated steel armoring. The Fiber should be SM Fiber Central -loose tube filled with Thixotropic jelly, duly following Standards: ISO 11801, IEC 60793-1/60794-1-2, ITU-T-REC G.652D and Telecordia GR-20-core, High quality Electro Chromium Coated Corrugated Steel tape (ECCS ) and HDPE- Sheath, Operating ambient Temperature should be – 5 0C to +50 0C and Storage Temperature shall be -5 C to +50 C, Max Attenuation ± 0.36 (db / km) at Operational Wavelength 1310 nm and ± 0.22 db / km at Operational Wavelength 1550 nm. type of fiber should be 9/125 / G.652D & Refractive Index should be .4670/1.4675. The value for Mode-filed, Cladding Diameter 9.2 ± 0.4 μm and 125 ± 0.7 μm correspondingly. The Dispersion value < 3.5 < 18 ps/nm-km and PMD value < 0.2 ps/km and Cable Cutoff wavelength < 1260 nm including splicing & marking etc complete as required. Single Mode 24 Core Optical fiber cable. Make: D-Link / Digilink / Digisol / Molex. Mtrs 1500 0.00
83 Supplying, installation, Testing and commissioning of following capacity 24 port Layer 2 indoor Network Switch having features and specifications etc. as mentioned here under: At least 24 X RJ-45 Gigabit Ethernet Ports and additional 04 numbers of 10 G SFP+ Port (Uplink) with non-blocking architecture by having Switching capacity of min. 128Gbps and packet forwarding rate of 96Mpps or higher, 16K MAC table. Console Port, USB port. Internal dual AC Power supply (Desirable), Security Features - (802.1xAAA, CoA, Port and MAC based Authentivation, ACL, RADIUS, TACACS+, Guest VLAN, Auto VLAN, DHCP, Traffic Monitor sFlow), Basic Layer-3 Protocol (STATIC ROUTING), Management Protocol (CLI, WEB, Telnet, SNMP v1/v2/v3, SSL, SSHv1/v2, SNTP/NTP, Authentication by RADIUS and TACACS, FTP/TFTP, Syslog and external Syslog server), Qos (802.1p, Policing/Rate Limiting, Queues, DSCP, STP/RSTP/MSTP etc,.), 6 kV surge protection on all Gigabit Ethernet ports and on all GE RJ-45 access ports. The offered product or any product from the offered product family/ product series should be VAPT certification, Certifications: UL, CE, FCC, RoHS, MTCTE, OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India etc. complete as required. Vendor must submit valid OEM authorisation certificate (MAF) with contact details of authoriser like phone no. email id name designation etc,. 24 port Layer 2 Non-PoE Network Switch. Nos. 3 0.00
84 Supplying, Installation, Testing and commissioning of small form-Pluggable (SFP) for Network Switches. Must be hot Pluggable, RoHS Complaint, etc.complete as required. 10 G SFP + Single Mode. SFP Shall be of same make/OEM as switch supplied. Nos. 6 0.00
85 Supplying, Installation, Testing and commissioning of small form-Pluggable (SFP) for Network Switches. Must be hot Pluggable, RoHS Complaint, etc. complete as required. 1 G SFP + Single Mode. SFP Shall be of same make/OEM as switch supplied. Nos. 6 0.00
86 Desktop Computer. Detail specifications as per Annexure III. Nos. 3 0.00
87 Line Interactive UPS 1KVA. Detail specifications as per Annexure III. Nos. 3 0.00
88 Supplying and fixing of 9U size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD)Shape, Vertical Mounting Rail 1.6 mm with 'U' Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required. Nos. 3 0.00
89 Supply and fixing 24 port Rack Mount loaded LIU with required pigtails OS2 (LC), Front-mounted cable saddles for jumper management, suitable to manage both splices and terminations, Pre-assembled shelves in multiple configurations, Rubber fiber slotted bracket built-in, metal splice shelf to protect the fibers, 2 fiber spools built-in for 900μm tight buffered fiber storing, Capable of storing up to 3 meters of 900μm tight buffered fiber per adapter, Removable front and rear covers for better access to interior of LIU, Should be Single mode LC Type fully loaded. Accessory kit consists of cable ties, mounting ear screws, and spiral wrap tube etc complete with splicing as required. 24 Port LIU. Nos. 3 0.00
90 Supply and fixing 12 port Rack Mount loaded LIU with required pigtails OS2 (LC), Front-mounted cable saddles for jumper management, suitable to manage both splices and terminations, Pre-assembled shelves in multiple configurations, Rubber fiber slotted bracket built-in, metal splice shelf to protect the fibers, 2 fiber spools built-in for 900μm tight buffered fiber storing, Capable of storing up to 3 meters of 900μm tight buffered fiber per adapter, Removable front and rear covers for better access to interior of LIU, Should be Single mode LC Type fully loaded. Accessory kit consists of cable ties, mounting ear screws, and spiral wrap tube etc complete with splicing as required. 08 Port LIU. Nos. 2 0.00
91 Supplying and fixing Patch Cord of Optical Fiber Single Mode LC to LC Fiber Duplex having high precision ceramic ferrule with good concentricity, Fiber corning single mode G652D, Cable Type 2mm with Mechanical specification Apex Offset < 50 μm, Fiber Height + 100 nm, End-face radius of Curvature 7mm < R <25mm, Repeatability < 0.2 db, Working ambient Temperature – 5 °C to +50 °C, Storage Temperature – 10 °C to +50 °C, Length -- 2meter, Type -- LC-LC Duplex etc complete as required. Nos. 10 0.00
92 Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Cable in PVC conduit/HDPE/on surface/(as per site), Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force : 11.5Kg etc. complete as required for 1 Run of cable. Mtrs 900 0.00
93 Supplying, Installation, Testing and commissioning of following CAT6 Patch Cord should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required. Copper Patch Cords of length 3 mtrs. Nos. 10 0.00
94 Supplying, Installation, Testing and commissioning of following CAT6 Patch Cord should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required. Copper Patch Cords of length 1mtrs. Nos. 50 0.00
95 Supplying Installation Testing and Commissioning of 8 port Cat6 Patch Panel loaded. Must be of 1U height with clear label holders and white label with the panel. 08 Ports Cat-6 Patch Panel should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required. Nos. 3 0.00
96 Supplying, Installation, Testing and commissioning of CAT6 Copper Information Outlet (IO) preloaded with outlet box with 8-position/8-contract jacks. All copper Cable and Components should be prefably from same OEM to maintain compatibility and interoperability etc. complete as required or as per site requirements. Nos. 20 0.00
97 Supply Installation of RJ45 Connector for CAT 6/6A Cables. RJ45 modular plug supports 4 twisted pairs, 8 positions, 8 connectors. Housing: PC, UL94V-2, transparent color, Use for 24- 26 AWG stranded wires etc. complete as required. Nos. 25 0.00
98 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess/under floor including cutting the wall/floor as per site requirement and making good the same in case of recessed conduit as required for telehone wire as well as for network wire. Size: 25mm. ISI mark. Color:Ivory/off-white only. Make: AKG / CAP / Havells / Anchor. Mtrs 200 0.00
99 Underground laying of OFC & Power cables by horizontal directional drilling (HDD) cable laying machine and laying / pulling of HDPE pipe coupled by HDPE sockets and sealing of HDPE pipe end by end caps. For HDD cable laying, guided boring/drilling technology is to be used. Detection system should be used for avoiding damage to existing underground utilities. The contractor has to arrange HDD/moling machine at his own arrangement basis. HDD machine shall be capable of going 5 meters or more below the ground level. After laying any excavated work surface to be returned to original state. Work will also include Laying & pulling of OFC cables & Power cables etc. within HDPE pipe on wall or overhead as per site requirement with the use of clamps for fixing the cable. Work also include Laying & pulling of OFC cables / Network Cables / Electrical cables etc. within HDPE pipe as per site requirement. Mtrs 1400 0.00
100 Digging of hard soil, soft soil, road cutting with laying / pulling OFC/ data cable / power cable in GI Pipe / HDPE & Cementing for locations where laying not possible by HDD machine. While road crossing (hard soil) it should be done by cutting the road or manual blowing for laying OFC cable in pipe, after completion of work surface to be returned to original state. Work will also include Laying & pulling of OFC cables etc. within HDPE pipe on wall or overhead as per site requirement with the use of clamps for fixing the cable. Mtrs 100 0.00
101 Cable Route markers: Supply and installation of surface markers (stone) to indicate route of the cables shall be planted to mark cable routes and indentify underground fiber optic cables. Display marker should have visible engraved message like "CCTV OFC LAID BELOW" and cable depth or as per EIC. Nos. 8 0.00
Applicable GST@18% 0.00
Amount in Words:
Name of Bidder:
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
detail.html
html • 0.06 MB
NIT.pdf
pdf • 6.18 MB
Tender_doc.pdf
pdf • 1.61 MB
Annex_1.pdf
pdf • 0.05 MB
Annexure_II.pdf
pdf • 0.48 MB
Annexure_III.pdf
pdf • 0.43 MB
ELIGIBILITY_CRITERION_MATRIX.xlsm
xlsm • 0.06 MB
Price_Bid.xlsm
xlsm • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .