The Executive Engineer, Kolkata Electrical Div
The Executive Engineer Kolkata Electrical Division P.W.Dte. BlockI (1st Floor) Writers Buildings, Kolkata 700 001
Electrical works related to repair renovation works of the Directorate of Agriculture situated on the 1st floor of Jessop Building 63 N.S Road Jessop Building Kolkata 70000.Electrical works.
2025_WBPWD_952379_1
WBPWD/EE-KED/eNIQ-37Q/25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Jessop Building
Please refer Tender documents.
5 documents required · 5 mandatory
₹38,350
O/O The Executive Engineer Kolkata Electrical Divi
15 Dec 2025
18 Nov 2025
15 Dec 2025
18 Nov 2025
13 Dec 2025
28 Nov 2025
27 Nov 2025
Average run 11 mtr
Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate and 2 no. suitable size “Ph & N” copper bar & earthing attachment fixed. Average run 10 mtr
Average run 11 mtr
on board
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required
2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC
2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC(TPNDB to SPNDB)
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 2X25mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required
4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection. (6-16 A) & 32A SPMCB (Make Legrand/Schneider/ABB itus)
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection
Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall incl. making earthing attachment, and mending good damages as per GS.
i)150 mm x 100 mm x 65 mm
iii)200 mm x 150 mm x 65 mm
iii)240 mm x 200mm x 65 mm
Supply & Fixing bakelite / perspex top cover on existing Inspection board by Brass screws
i)150 mm x 100 mm x 65 mm
ii)200 mm x 150 mm x 65 mm
iii)240 mm x 200 mm x 65 mm
Before the repairing works by pwd Civil, the existing computer/power Boards are dismantled by skilled electrician and store in lock and key room as per direction of Junior Engineer and after civil works completed, The physically and electrically good condition computer and power boards are reinstalled at new location with necy screw incl. internal connection (where authority wants), the whole work will be executed as per direction of EIC.
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.
Before the repairing works by pwd Civil, carefully taken down all good condition ceiling fans from existing location by skilled electrician and store in lock and key room as per direction of Junior Engineer and after civil works completed, The physically and electrically good condition ,light weight fans are reinstalled at new location after civil work compeltion, all necessary works like split pin, jam nuts and rubber bobin incl. S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. etc may be replaced as per requirments and over all works should be executed as per direction of EIC
Before the repairing works by pwd Civil, good condition LED fittings and tubes are taken down by skilled electrician and store in lock and key room as per direction of Junior Engineer and after civil works completed then reinstalled at the existing location complete with all accessories directly on wall/ceiling by screws etc., the whole work will be executed as per direction of EIC.
Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
Supply and Fixing 2'' Aluminium Floor channel as per Requirment
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.69 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.47 MB
BOQ_2278453.xls
BOQ • 0.36 MB
2911.pdf
Tender Documents • 0.54 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .