PROVN OF KLP UNDER GE LALGARH JATTAN
2023_MES_612626_1
CE BTZ/LGJ/TOKEN-05 OF 2023-24
Open Tender
Coal Works
Lump-sum
730 days
LALGARH JATTAN
As per NIT
9 documents required · 9 mandatory
₹3,000
GE Lalgarh Jattan
₹9.1 L
Yes
10 Oct 2023
8 Aug 2023
21 Sept 2023
8 Aug 2023
19 Sept 2023
5 Sept 2023
Amount
Lump sum price worked out by the tenderer for “BUILDING /STRUCTURE WORKS" as listed in Schedule ‘A’ Section - I
Sch 'A' Sec - II (Part-II), (INTERNAL ELECTRIFICATION WORKS)
Material and labour for concealed Point wiring for one light point/fan point /bell point controlled by one switch (using red, black and green colour wires as colour coding) complete with 1.5 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 50mm deep and 1.6mm thick sheet, suitable size) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switches/ socket / regulator etc, including provn of 1.5 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3), including fixing of switch/socket/regulator etc complete all as specified and as directed. (switch, socket, regulator shall be measured and paid separately under appropriate item of BOQ as supply only but cost of labour for fixing the same shall deemed to be included in the unit rate. ).
All as per above Srl item No. 03 but for one socket out let 5 Amps point controlled by one switch (on same board) complete all as specified and as directed by Engineer-in-charge. (switches, sockets etc. shall be measured and paid separately under appropriate item of BOQ/Sch A).
All as per above Srl item No. 03 but for one socket out let 5 Amps point controlled by one switch (on independent board and not below the any other switch board) complete all as specified and as directed by Engineer-in-charge. (switches , sockets etc. shall be measured and paid separately under appropriate item of BOQ/Sch A).
Material and labour for concealed Point wiring for one light point controlled by two Nos- two way switch (using red, black and green colour wires as colour coding) complete with 1.5 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 50mm deep and 1.6mm thick sheet, suitable size ) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switch, including provn of 1.5 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3), including fixing of switches complete all as specified and as directed. (switches shall be measured and paid separately under appropriate item of BOQ as supply only but cost of labour for fixing the same shall deemed to be included in the unit rate. ).
Material and labour for concealed Point wiring for one socket out let 15/16 Amps point controlled by one switch (on independant board) (using red, black and green colour wires as colour coding) complete with 2.5 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 50mm deep and 1.6mm thick sheet, suitable size ) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switches / socket, including provn of 2.5 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3), including fixing of switch, socket complete all as specified and as directed. (switch, socket shall be measured and paid separately under appropriate item of BOQ as supply only but cost of labour for fixing the same shall deemed to be included in the unit rate).
Supply only modular switch 6Amps, single pole, one way (1 module) complete all as specified and as directed by Engineer-in-charge.
Supply only modular switch 6/16Amps, single pole, one way (1 module) complete all as specified and as directed by Engineer-in-charge.
Supply only modular switch 6Amps, single pole, two way (1 module) complete all as specified and as directed by Engineer-in-charge.
Supply only modular Bell Push switch, 6Amps, single pole, one way (1 module) complete all as specified and as directed by Engineer-in-charge.
Supply only modular Socket outlet multipurpose type 6 Amp, flush type (2 module) complete all as specified and as directed by Engineer-in-charge.
Supply only modular Socket outlet multipurpose type 6/16 Amp, flush type (2 module) complete all as specified and as directed by Engineer-in-charge.
Supply and fixing Batten holder polycarbonate cased body (B22 base), top line series, with back plate complete all as specified and as directed.
Supply and fixing Ceiling Rose, polycarbonate, isolated body, surface bakelite 3 terminal, 240 volts, 5/6 Amp complete all as specified and as directed.
Supply and fixing electric calling Bell Ding Dong type, AC 230 Volts single pole including making elctric connection complete all as specified and as directed by Engr-in-charge.
Supply and hanging /fixing ceiling fan 1200 mm sweep AC Supply (Input Voltage Range ; 120 to 280V), BLDC type, 5 star rated, BEE and ISI Marked super enamelled, copper winding of 'B' class insulation, single phase, maximum 30W (± 10%), Temperature rise 40 degree maximum without remote with and including capacitive regulator, 03 No blades, down rod including accessories, white colour, total harmonic less than 10%, 5 speed, hanging in position including making connection with flexible cord three core twisted copper conductor of suitable size from ceiling rose to fan complete all as specified. Note :- (i) Serial Number as issued by Engr-In-Charge of celing fan and GE Office name shall also be written on fan with red colour permanent marker and fixing of regulator on switch board, cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
Supply and fixing exhaust fan (heavy duty) steel body, AC single Phase 230V, 50Hz, 900RPM, size 300mm sweep with blades and frame including self closing GI louvers off mode protection against birds etc mounted in suitable opening arrangement in wall and connecting up and including three core PVC Insulated PVC Sheathed copper conductor flexible cable 24/0.2mm drawn in flexible PVC conduit and hanging on wall with 4 Nos steel fastners 10mm dia 100mm long and making good the disturbed surface complete all as specified and as directed by Engineer-in-charge. Note :- (i) Serial Number as issued by Engr-In-Charge of fan and GE Office name shall also be written on fan with red colour permanent marker, cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
Supply and fixing exhaust fan (heavy duty) steel body, AC single Phase 230V, 50 Hz, 1400RPM, size 450mm sweep with blades and frame including self closing GI louvers off mode protection against birds etc mounted in suitable opening arrangement in wall and connecting up and including three core PVC Insulated PVC Sheathed copper conductor flexible cable 24/0.2mm drawn in flexible PVC conduit and hanging on wall with 4 Nos steel fastners 10mm dia 100mm long and making good the disturbed surface complete all as specified and as directed by Engineer-in-charge. Note :- (i) Serial Number as issued by Engr-In-Charge of fan and GE Office name shall also be written on fan with red colour permanent marker, cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 250 Amp rated bus bar) VTPN, 4 Way 415V, suitable for mounting MCCB/MCB, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCCB/MCB shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) TPN, 4 Way 415V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 12 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 8 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 4 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing MCB ‘B’ curve suitable for 415 volts AC supply, 63 Amps, TPN with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 40 Amps, SPN with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 6 to 32 Amps, SPN with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 06 to 32 Amps, SP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 40 Amps, SP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing blanking plate suitable for any type of DB complete all as specified and as directed by Engineer-in-charge.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 6 Sqmm single core (05 run i.e 4 runs for main 3 phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable drawn through and including PVC conduit 25mm dia (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :- Five runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 6 Sqmm single core (03 run i.e 2 runs for main phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable drawn through and including PVC conduit 25mm dia (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :- Three runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 4 Sqmm single core (03 run i.e 2 runs for main phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable drawn through and including PVC conduit 25mm dia (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :- Three runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
Supply and fixing LED lamp minimum 3 star rated 9W LED B-22 base complete all as specified and directed by Engr-in-Charge with following specifications (a) Lumen system efficacy of lamp should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) CRI : More than 70
Supply and fixing LED tube light fitting polycarbonate housing 1 x 20 Watt, appx 4 feet long, with decorative box linear, housing environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts. (c) Temp operating range : Minus 5°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Current THD Max10% and voltage THD max 5% (f) IP rating : IP-20. (g) LED Driver of the same make as of the luminaire. (h) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (j) Surge protection minimum 2.5 kV. (k) CCT : Minimum 6000K (l) CRI : Minimum 80 (m) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply and fixing LED light fitting 1 x 10 Watt, appx 2 feet long with decorative ultra ceiling square profile linear LED lighting fixture with extruded polycarbonate environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to light fitting, complete fitting with all accessories and following specifications, including taking down old Unserviceable light fitting any type complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 5°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Current THD Max10% and voltage THD max 5% (f) IP rating : IP-20. (g) CRCA pre coated housing with plastic end cap. (h) LED Driver of the same make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection minimum 2.5 kV. (l) CCT : Minimum 6000K (m) CRI : Minimum 80 (n) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply and fixing energy efficient LED security light fitting of 25W pressure die cast aluminium housing/body, heat resistant clear toughened glass, better optics for uniform distribution street luminaire, with driver, including electric connection with using 2 core flexible copper conductor cable 1Sqmm from ceiling rose to light fitting, fixing the light fitting with new bracket made out of GI tubing light grade 25mm dia, 1.2 metre long bent to shape at 120 degree angle at half metre from bottom, including two Nos clamps made out of MS Flat iron size 25x3 mm with suitable nuts and bolts for fixing of bracket including painting to MS clamp and nut bolts with two coats of aluminium paint over a coat of red oxide primer, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP66. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : Minimum 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply and fixing High bay beam LED light fitting of 50 Watt, specifically designed heat sink for long life vertical high bay/medium LED luminaries complete with body robust, corrosion resistant, superior finish and without any cracks or through holes, made in a single piece by high pressure die cast aluminium alloy including fixing on wall/roof with help of suitable GI clamps, nut bolts/fastners, pendant of suitable length and washers etc, the luminaries shall be monolithic construction totaly enclosed dust and water proof with minimum IP 65 protection as per IS-10322 (1982, Part-I) with latest amendments and input voltage range 140-300V, AC frequency 50-60Hz, PF should be more than 0.9 with total Harmonic distoration THD (I) less than 15%, cool white colour and lamp starting time should not be more than 10 second, Fitting should be provided with 10KV Surge protection, Driver should be constant current constant voltage driver. Driver should have high voltage withstanding capacity upto 300V, AC, Driver should also have double phase protection, no load, open circuit and short circuit protection. LED light fitting should be suitable for ambient temperature from 10 degree centigrade to 50 degree centigrade and humidity level 10% to 90% RH. Covers should be polycarbonate/toughened glass to ensure IP 65 degree protection, cover should not degrade due to heating and ageing. The efficiency of LED luminaries system shall be more than 100 lumens per watt and must be certified by the LM-79 test report.complete all as specified and as directed.
Material and labour for concealed wiring for TV antenna connection complete with coaxial RG-6 heavy duty PVC insulated sheathed cable with copper conductor having single strand of 0.7 mm dia and a aluminium wire net drawn through PVC conduit complete all as specified and as directed. (TV antenna connection socket outlet, terminal box, conduit with fittings shall be measured and paid separately under appropriate item of BOQ).
Material and labour for Pressed steel powder coated sunken terminal box of size 100mm x100mmx50mm concealed in wall, including inner and outer plates (cover plate) suitable for fixing and including modular type (1 module) 2 pin TV antenna connection socket outlet round flush type duly marked with symbol of TV and making good disturbed surfaces of walls by using CM (1:3) complete all as specified and as directed.
Material and labour for concealed wiring for telephone connection complete with PVC insulated sheathed cable with copper conductor having single strand of 0.4 mm dia twin core (one pair) taped for telephone wiring drawn through PVC conduit complete all as specified and as directed. (Telephone connection socket outlet and terminal box, conduit with fittings shall be measured and paid separately under appropriate item of BOQ).
Material and labour for Pressed steel powder coated sunken terminal box of size 100mm x100mmx50mm concealed in wall, including inner and outer plates (cover plate) suitable for fixing and including modular type (1 module) telephone connection socket outlet flush type duly marked with symbol of telephone and making good disturbed surfaces of walls by using CM (1:3) complete all as specified and as directed.
Material and labour for concealed in wall rigid non matallic PVC conduit 20mm dia (medium duty, ISI marked) for telephone wiring, cable TV etc inclusive of all fitting & accessories such as tees, bends, elbow, reducer, junction box, pipe hooks etc, bell mouth tube ends including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3) complete all as specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “INTERNAL WATER SUPPLY WORKS" as listed in Schedule ‘A’ Section - III (Part-I)
Sch 'A' Sec - III (Part-II), (INTERNAL WATER SUPPLY WORKS)
Supply and fixing hand shower (health faucet) fancy type, CP including 1.2 meter long 8mm dia flexible tube and including wall hook and fixing material complete all as specified and as directed by Engineer-in-charge.
Supply & fixing CP connection 15 mm size with CP nuts of length 450 mm and fixed complete all as specified and as directed by Engineer-in-charge.
Subtotal
Lump sum price worked out by the tenderer for “ROAD, PATH, CULVERT AND HARDSTANDING WORKS" as listed in Schedule ‘A’ Section -IV (Part-I)
Sch 'A' Sec - IV (Part-II), (ROAD, PATH, CULVERT AND HARDSTANDING WORKS)
Supply and laying/fixing 60 mm thick (M-35 grade) precast interlocking tile/paving block factory casted (made by using PVC/ Rubber moulds on Vibrating Table Machine) using grey cement and no pigment, any shape haxagon / trigular / zigzag / I-shaped etc, as directed, confirming to relevant IS, laid over and including 25mm thick layer of sand cushining and filling the interstices etc with sand complete all as specified and as directed.
Material and labour for Thermo plastic paint road marking 2mm thick painting (lines, dashes, arrows, letters etc) with road safety spikeries glass beads @ 8% by weight including preparation of new or previously treated road surfaces and applying paint by using special applicator machine with heating arrangement complete all as specified and as directed.
Material and labour for Forming 12mm thick Expansion joints filled with pre-formed bituminous filler and top 30mm primed and filling the Joints with and including bitumen and sand (1:3) by weight ( Thickness of concrete slab in 100mm) complete all as specified and as directed.
Material and labour for Forming Contraction (Dummy) joints 30mm deep x 10mm wide, and filling the Joints with and including bitumen and sand (1:3) by weight complete all as specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “AREA DRAINAGE WORKS)" as listed in Schedule ‘A’ Section -V (Part-I)
Sch 'A' Sec - V (Part-II), (AREA DRAINAGE WORKS)
Material and labour for Pre-cast factory made RCC drain of size and shape as directed by GE alongwith male and female ends for proper joining, made of 75mm thick RCC M-30 using 20mm graded aggregate, duly embeded two Nos socket for hoisting including form work etc, hosting and placing at site and jointed in CM (1:4) to form uniform length and fair finish to drain upto 80cm girth (width measured @ Avg of inner and outer girth) complete all as specified and as directed by Engineer-in-Charge. Note : Reinforcement shall be measured and paid separately under appropriate item of this Sch.
Subtotal
Lump sum price worked out by the tenderer for “SEWAGE DISPOSAL WORKS" as listed in Schedule ‘A’ Section - VI (Part-I)
Sch 'A' Sec - VI (Part-II), (SEWAGE DISPOSAL WORKS)
Material & Labour for Precast M-30 factory made manhole cover, set in CM (1:4) including necessary form work complete all as specified and as directed (Reinforcement and MS handle shall be measured and paid separately under appropriate item of this Sch).
Supply and laying DWCPE (SN8) drain pipes 150mm nominal dia as per IS-16098 (Part-II), laid in trenches on and including bed 100mm thhick beding comprising of well compacted clean poorly graded gravel, gravel/sand mixture with little or no fines to required slope, including all accessories/fittings/jointing ring, jointing and testing complete all as specified and as directed by Engineer-in-Charge. Note : Excavation, earth work and pedestal /anchorage if required shall be measured & paid separately under appropriate item of BOQ/Sch A.
Supply and laying DWCPE (SN8) drain pipes 200mm nominal dia as per IS-16098 (Part-II), laid in trenches on and including bed 100mm thhick beding comprising of well compacted clean poorly graded gravel, gravel/sand mixture with little or no fines to required slope, including all accessories/fittings/jointing ring, jointing and testing complete all as specified and as directed by Engineer-in-Charge. Note : Excavation, earth work and pedestal /anchorage if required shall be measured & paid separately under appropriate item of BOQ/Sch A.
Subtotal
Lump sum price worked out by the tenderer for “SECURITY FENCING AND GATE WORKS" as listed in Schedule ‘A’ Section - VII
Lump sum price worked out by the tenderer for “ EXTERNAL WATER SUPPLY WORKS" as listed in Schedule ‘A’ Section - VIII (Part-I)
Sch 'A' Sec - VIII (Part-II), ( EXTERNAL WATER SUPPLY WORKS)
Supplying, laying, jointing and testing Ductile iron pipe (ISI marked) class K-7, bore 100mm, confirming to IS : 8329-2K, spigot & socketed ends centrifugally cast, with cement mortar lining inside and metallic zinc coating with finishing layer of bituminous paint on outside the pipe, suitable for and including rubber tyton joints (Push-on joint) complete all as specified and as directed. Note : (i) Earth work, DI specials/ fittings shall be measured and paid separetly. (ii) Test Certificate for pipes from manufacturer shall be produced. No payment shall be entertained without Test Certificate.
Supply and fixing cast iron sluice valve 100 mm dia with flanged ends class PN 1.0 (ISI marked) confirming to IS:14846-2000, drilled type, steel spindle, CI gate with brass ring, iron wheel handle, suitable for CI/DI pipe line, complete including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Supply and fixing cast iron sluice valve 80 mm dia with flanged ends class PN 1.0 (ISI marked) confirming to IS:14846-2000, drilled type, steel spindle, CI gate with brass ring, iron wheel handle, suitable for CI/DI pipe line, complete including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Material and labour for Construction of brick masonary valve pit chamber size 105 X105 X105 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, returning fillig and disposal of surplus soil to distance not exceeding 50m and deposited where directed, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate, brick work in cement mortar (1:4), inner plaster 12 mm thick in cm (1:3) finished even and smooth and pionting flush externally as the work proceeds in the same mortar, MS sheet cover 3.15mm thick mounted on angle iron frame of size 40 x 40 x 6mm with handle and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and embeded portion of MS work duly applying black bitumenous paint before embeded complete all as specified and as directed.
Material and labour for Construction of brick masonary valve pit chamber size 90 X90 X90 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, returning fillig and disposal of surplus soil to distance not exceeding 50m and deposited where directed, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate, brick work in cement mortar (1:4), inner plaster 12 mm thick in cm (1:3) finished even and smooth and pionting flush externally as the work proceeds in the same mortar, MS sheet cover 3.15mm thick mounted on angle iron frame of size 40 x 40 x 6mm with handle and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and embeded portion of MS work duly applying black bitumenous paint before embeded complete all as specified and as directed.
Supply and fixing DI fitting upto 150 mm bore pipe line for reducing/bends (any type radius and angle) tapers any type, straight, bend, increasing decreasing or double socket extra Tee pieces single branch Y 'Junction' double branch cross collers cap etc complete all as specified and as directed. Note:- Make of DI fittings shall be same make as DI pipe or as per recommendation of DI pipe manufacturer.
Subtotal
Lump sum price worked out by the tenderer for “EXTERNAL ELECTRIFICATION WORKS" as listed in Schedule ‘A’ Section - IX (Part-I)
Sch 'A' Sec - IX (Part-II), (EXTERNAL ELECTRIFICATION WORKS)
Material and labour for Earthing complete with galvanised iron earth plate electrode of size 600 x 600 x 6 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI earthing wire of size 4 mm dia by means of GI bolts/nuts/washers and protected by 15 mm bore GI light grade pipe upto test point or upto main switch board, HT/LT equipments, fixing with 02 Nos nuts and bolts and protection pipe fixed with and including flat iron clamps, bolts, nuts and washers. Earth plate shall be surrounded by alternate packed layer 15 cm thick of charcoal or coke and common salt all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50m, Pit cover 40mm thick made with RCC (1:2:4) type B1 (using 20 mm graded stone aggregate) including TMT reinforcement 8mm dia @ 75mm c/c both way, MS handle 12mm dia, cover rest on MS angle iron frame 40x40x6mm embeded in concrete duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I) complete all as specified and as directed by Engineer-in-charge. Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) Protection pipe and GI earthing wire upto test point or upto electric equipment from top of earth plate shall be included in the unit rate of this item. (iii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge.
Material and labour for Earthing complete with galvanised iron earth plate electrode of size 600 x 600 x 6 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI earthing strip 32x6mm by means of GI bolts/nuts/washers and protected by 40 mm bore GI light grade pipe upto test point or upto main switch board / electric equipment / pole / lightning arrestor / HT/LT equipments / GODO switch etc, fixing with 02 Nos nuts and bolts and protection pipe fixed with and including flat iron clamps, bolts, nuts and washers. Earth plate shall be surrounded by alternate packed layer 15 cm thick of charcoal or coke and common salt all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50m, Pit cover 40mm thick made with RCC (1:2:4) type B1 (using 20 mm graded stone aggregate) including TMT reinforcement 8mm dia @ 75mm c/c both way, MS handle 12mm dia, cover rest on MS angle iron frame 40x40x6mm embeded in concrete duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I) complete all as specified and as directed by Engineer-in-charge. Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) Protection pipe and GI earthing strip upto electric equipment from top of earth plate shall be included in the unit rate of this item. (iii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge.
Supply and fixing energy efficient LED street light fitting of 45W pressure die cast aluminium housing/body, heat resistant clear toughened glass, better optics for uniform distribution street/Roadway luminaire, with driver, including electric connection with suitable size of wire from junction box to street light fitting (drawn through steel pole/protection pipe along PCC pole), fixing the light fitting with and including bracket made out of GI tubing light grade 32mm dia, 1.2 metre long bent to shape at 120 degree angle at half metre from bottom, including two Nos clamps made out of MS Flat iron of size 25x4 mm with suitable nuts and bolts for fixing of bracket including painting to MS clamp and nut bolts with two coats of aluminium paint over a coat of red oxide primer, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 105 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : Minimum IP65. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : Morethan 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply, installing, commissioning & testing Power transformer suitable for unbalanced load of capacity 160 KVA step down, out door platform mounting type, double wound copper 3 phase, 50 cycles (50 Hz) AC, oil immersed, natural air cooled ("ON, AN" type) with external cooling tubes/radiators core type no load voltage ration 11000/433 volts (corresponding to prinicipal tapping) winding delta connection on primary side (HV side) and star connection on secondary side (LV side) in accordance with vector symbol Dy-11 (vector group-4) with neutral brought out on LV side for earthing and having tapping HV Side for constant output so as to alter/vary secondary voltage by + 7.5% in steps of 2.5 % to be changed by means of manually operated "off load" tap changing gear. The limit of temperature rise after continous full load run as specified, all as per IS:1180 (Pat I)/2014, BEE L-2 (2 star) rating, shall be suitabily adjusted to suit the Max ambient temp of 50 Deg C at prevailing at site. The transformer shall be complete with the following fittings and accessories :-
(a) Oil conservator tank with fillings holes and cap filter type drain valve and oil level gauge. (b) Silica gel breather with connecting pipe, first fill of dehydrating agent and oil seal. (c) Shut off valve between the conservator and main tank. (d) Explosion relief vent mounted on tank with double diaphram and equalizer pipe connected to conservator air tank (pressure release valve) (e) Air release plug (f) 150mm dia magnetic oil level gauge with low level alarm contacts. (g) 150mm dia oil temperature indicator having range 0-120 deg C with max reading pointer and electrically separate sets of contacts for alarm and trip. (h) 150mm dia winding temperature indicator having range 0-120 deg C with max reading pointer and electrically separate sets of contacts for alarm and trip. (j) Thermometer pocket. (k) Pressure release valve. (l) Double float Buchholz relay with trip and alarm contacts. (m) Marshelling box. (n) Filter valves with threaded adopter (Top and bottom). (o) Sample valve. (p) Hand pole of sufficient size for access to the interior tank. (q) Inspection cover. (r) Cover lifting eyes. (s) Earthing terminals. (t) Jacking pads handing and lifting pulgs. (u) Bl-directional rollers- 04 Nos. (v) Rating plate and terminal making plate. (w) Extra brushing for neutral outside the cable box brought out on LV side. (x) First filling of oil. (y) HV bushing on 11 KV (HV side) having brass/gun metal studs with additional length of brass studs at least 300mm over the top of bushing the three nuts and washers and provision of arcing horns. (z) One cable box on LV side suitable for LT cable 630 sqmm 3.5 core with disconnecting chamber and suitable terminals. (aa) Necessary wiring connection from transformer safety devices i.e. Buchholz relay/WT/OTI/Mag lol gauge to control panel and control panel to VCB.
Note :- (a) Transformer shall be Pre-Commisioned by SEI after installation. (b) Cost of all necessary T&P and measuring devices shall be provided by the contractor without any extra cost. (c) Drawing of transformer shall be approved by GE before placing the order. (d) PCC foundation, plateform as per manufacturer recommendation (one metre high from ground level) shall be provided by the contractor without any extra cost. (e) Any other item which is required for efficient functioning of transformer is deemed to be included in the quoted rate.
Supply, installing, commissioning and testing of factory made LT panel board (CPRI approved) (out door for 415 volts, 3 phase, 4 wire AC supply) cubical type suitable size, outer shell made out of 3.15 mm thick CRCA epoxy powder coated sheet and inner shell made out of 2mm thick CRCA epoxy powder coated sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully comparted type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and brass cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
Four Pole, Aluminium bus bar 400 Amps
MCCB 250 Amps, Four pole, adjustable thermal magnetic protection, 35 KA, 415 V AC supply - 01 No (Incoming)
MCCB 160 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 01 No (Outgoing)
MCCB 100 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 02 No (Outgoing)
Nature Switch Three-Phase load of 5 KW for automatic Street Light control Switch - 01 No (Outgoing)
Indicating lamps set RYB - 01 Set of three
Internal power and control wiring with suitable size PVC insulated multistranded copper wire and incl 03 Nos bakelite control fuses.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installing, commissioning and testing of factory made LT panel board (CPRI approved) (out door for 415 volts, 3 phase, 4 wire AC supply) cubical type suitable size, outer shell made out of 3.15 mm thick CRCA epoxy powder coated sheet and inner shell made out of 2mm thick CRCA epoxy powder coated sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully comparted type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and brass cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
Four Pole, Aluminium bus bar 100 Amps
MCCB 63 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 01 No (Incoming)
MCB 16 Amps, TPN, 10 KA, AC supply - 02 No (Outgoing)
Indicating lamps set RYB - 01 Set of three
Internal power and control wiring with suitable size PVC insulated multistranded copper wire and incl 03 Nos bakelite control fuses.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installing, commissioning and testing of factory made LT panel board (CPRI approved) (out door for 415 volts, 3 phase, 4 wire AC supply) cubical type suitable size, outer shell made out of 3.15 mm thick CRCA epoxy powder coated sheet and inner shell made out of 2mm thick CRCA epoxy powder coated sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully comparted type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and brass cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
Four Pole, Aluminium bus bar 150 Amps
MCCB 63 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 01 No (Incoming)
MCB 32 Amps, TPN, 10 KA, AC supply - 01 No (Outgoing)
MCB 16 Amps, TPN, 10 KA, AC supply - 02 No (Outgoing)
Digital time switch, single phase with contactor - 01 No (Outgoing)
Indicating lamps set RYB - 01 Set of three
Internal power and control wiring with suitable size PVC insulated multistranded copper wire and incl 03 Nos bakelite control fuses.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installing, commissioning and testing of factory made LT panel board (CPRI approved) (out door for 415 volts, 3 phase, 4 wire AC supply) cubical type suitable size, outer shell made out of 3.15 mm thick CRCA epoxy powder coated sheet and inner shell made out of 2mm thick CRCA epoxy powder coated sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully comparted type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and brass cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
Four Pole, Aluminium bus bar 150 Amps
MCCB 100 Amps, Four pole, adjustable thermal magnetic protection, 35 KA, 415 V AC supply - 01 No (Incoming)
MCB 32 Amps, TPN, 10 KA, AC supply - 01 No (Outgoing)
MCB 16 Amps, TPN, 10 KA, AC supply - 03 No (Outgoing)
Digital time switch, single phase with contactor - 01 No (Outgoing)
Indicating lamps set RYB - 01 Set of three
Internal power and control wiring with suitable size PVC insulated multistranded copper wire and incl 03 Nos bakelite control fuses.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply and fixing cable junction box of Size 225mm x 295mm x 122mm or any other higher size (Suitable for Pole mounting) complete with fixing accessories. Junction box should be insulated and made out of polycarbonate with glass fiber re-inforced material. The polycarbonate junction box shall be environment frinedly, recyclable, UV resistant, halogen and silicon free, anti acid and anti corrosive. The junction box knock out on four side wall and following specifications and all as directed by Engr-in-Charge :- (a) The junction box shall be rated for degree of IP 65 (ingress protection) in accordance with IEC 60529. (b) The gasket material shall be polyurethane or silicon and gasket shall be internally embedded. (c) Junction Box must meet the provision laid down in IEC 60998-1, IEC-60695-22, IEC 60670-2 to 5 and grey color according to RAL-9011/ 7035. (d) The manufacturer of junction box shall submit a copy of IEC certificate and glow wire test for 960 degree. (e) Junction box shall be fire retardant and self extiguishing in accordance with IEC60695-2 to 11, DIN VDE 0304 Part-3, UL94 V-2 flammability standard. (f) The impact strength of polycarbonate enclosures /boards i.e. the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK08. (g) Junction box shall have 4 pole tinned copper bus bar of size 25mmx3mm complete with one number 6 Amp MCB SP 10KA (h) Manufacturer should submit routine test certificate for junction box. (j) Clamps and screws for fixing of junction box shall be made of SS
Supply and fixing 9 watt cylindrical shape, integral decorative LED Bollard light with Opal acrylic, and IP-65 protection, made in 3 parts i.e. spun aluminium dome shaped top cover, cylindrical opel acrylic diffuser for pleasant light output and seamless GI pipe bottom housing the control gear for 9W LEDs complete fitting with all accessories and LEDs, including fixing arrangement with material as directed by Engineer-in-charge including making electric connections, complete all as specified and as directed and as per the following specifications:- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) CCT : 3000 K. (g) IP rating : IP65. (h) Built in LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 4.5 kV (l) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing LED Post Top light fitting of 20W, 230 volts AC outdoor type, decorative design, Glare-free and better uniformity, for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete compete fitting with all accessories and LED lamp, fixing on and including 40mm dia GI pipe light grade of length 2.5 mtr, embeded in PCC block of size 0.3x0.3x0.5m made with PCC (1:2:4) type B-2 using 20 mm graded crushed stone aggregate, including making electric connection with suitable size of wire, complete fitting with all accessories and following specifications complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficiency of luminaire should be minimum 100 lumen per watt. (b) Input voltage range : 140 to 270 volts. (c) Temp operating range : Minus 10*C to plus 50*C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) CRI : More than 70 and CCT : 5700K (g) IP rating : IP 65 (h) IK rating : minimum IK 07 (j) Built in potted LED Driver of the make as of the luminaire. (k) LED driver should e complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (l) Surge protection 10kV (inbuilt +extended) (m) Lens - High Efficiency wide angle lens. (n) BIS approved fixtures and driver (o) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Sand cushioning, with dry and clean river fine sand (for under ground cable) 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified and as directed. Note:- (i) Punned thickness shall be considered for payment purpose (ii) Approved sand free from vegetations, grass and other deleterious substances shall be used.
Subtotal
Lump sum price worked out by the tenderer for “SUMMER APPLIANCES AND WASHING MACHINE WORKS" as listed in Schedule ‘A’ Section - X (Part-I)
Sch 'A' Sec - X (Part-I) , (SUMMER APPLIANCES AND WASHING MACHINE WORKS)
Supply, installing, commissioning and testing frost free refrigerator electric driven single phase 220 volts, AC 50 Hz, 195 ltrs or next higher capacity with BEE approved, minimum 3 star rating single door, stablizer free operation, Inverter Technology, R600a Refrigerant,LED display, tempered glass self, deodorizer and with fruit & vegitable drawer complete all as specified and as directed.
Supply, installing, commissioning and testing Water Cooler fully stainless steel, electric driven single phase having approx storage capacity of 120 Ltr and nominal cooling capacity of 60 Ltr per hour with inlet PVC connection pipe of size 15 mm dia and 600 mm long of good quality complete with both ends CP nuts including electric connection through Voltage stablizer complete all as specified and as directed.
Supply, installing, commissioning and testing hi wall split units indoor / outdoor Air conditioner cooling type both complete with cordless remote control unit and within built air purifier, dehumidifier, air filter and dust filter for better indoor air quality with minimum BEE approved, minimum 3 star rating with hot and cold provision inverter type all and EER 3.2, Electric driven single phase 220 volts, AC, 50HZ, R-410A refrigerant of capacity 1.5 Ton, inverter type, noise level should be less than 45 DB including copper piping of adequate size and required length as directed duly insulated with suitable insulating material e.g. glass wool, plywood, moulded thermo coal etc including antibacterial coating complete with steel bracket for condensing unit and copper cable of suitable size for making electric connections, including necessary fixing arrangement (indoor unit at suitable place and height inside the room and outdoor unit at suitable place outside the room) complete as specified and as directed. Note:- (a) Suitable piping shall be provided of adequate length of size 5/8" for draining of condensate water from indoor unit. Cost of same shall deemed to be included in quoted rate. (b) Suitable Copper tubing in addition if required extra as per site requirement from indoor unit to outdoor unit shall be provided and cost of same shall to be included in quoted rate. (c) Cost for Metallic bracket and nut bolt for fixing indoor and outdoor unit including necessary cutting / grouting in walls by cutter and making good the surface in CM 1:3 and to the original finishes (white wash/colour wash/Distemper) shall deemed to be included in quoted rate. (d) Contractor shall submit original purchase voucher and Warranty card. Minimum warranty should be 1 year for complete product, 10 year for compressor, 5 year for condensor and PCB card after Installation and commissioining of complete unit.
Supply, installing, commissioning and testing hi wall split units indoor / outdoor Air conditioner cooling type both complete with cordless remote control unit and within built air purifier, dehumidifier, air filter and dust filter for better indoor air quality with minimum BEE approved, minimum 3 star rating with hot and cold provision inverter type all and EER 3.2, Electric driven single phase 220 volts, AC, 50HZ, R-410A refrigerant of capacity 2.0 Ton, inverter type, noise level should be less than 45 DB including copper piping of adequate size and required length as directed duly insulated with suitable insulating material e.g. glass wool, plywood, moulded thermo coal etc including antibacterial coating complete with steel bracket for condensing unit and copper cable of suitable size for making electric connections, including necessary fixing arrangement (indoor unit at suitable place and height inside the room and outdoor unit at suitable place outside the room) complete as specified and as directed. Note:- (a) Suitable piping shall be provided of adequate length of size 5/8" for draining of condensate water from indoor unit. Cost of same shall deemed to be included in quoted rate. (b) Suitable Copper tubing in addition if required extra as per site requirement from indoor unit to outdoor unit shall be provided and cost of same shall to be included in quoted rate. (c) Cost for Metallic bracket and nut bolt for fixing indoor and outdoor unit including necessary cutting / grouting in walls by cutter and making good the surface in CM 1:3 and to the original finishes (white wash/colour wash/Distemper) shall deemed to be included in quoted rate. (d) Contractor shall submit original purchase voucher and Warranty card. Minimum warranty should be 1 year for complete product, 10 year for compressor, 5 year for condensor and PCB card after Installation and commissioining of complete unit.
Supply & installing of Voltage stabilizer for automatic operation having input & output voltage, Amps, Over & low voltage cutout and timer delay function etc digital display single phase naturally air cooled indoor type & designed for input variation between 170 V to 280 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 1 KVA with wall mounting bracket complete all as specified and as directed.
Supply & installing of Voltage stabilizer for automatic operation having input & output voltage, Amps, Over & low voltage cutout and timer delay function etc digital display single phase naturally air cooled indoor type & designed for input variation between 170 V to 280 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 4 KVA with wall mounting bracket complete all as specified and as directed.
Supply and Installation of Desert cooler of size 26 x 26 x 33 inch or next available higher size, electric driven single phase 230 volts steel body having nominal air flow capacity of 4000 Cu M per hours, factory made GI sheet body 18 SWG and side panells of 22 SWG, water sump capacity not less than 40 ltrs, including water pump submesible type of suitable capacity ISI marked, complete including electric connection complete all as specified and as directed. Note (a) : Sufficient length of 3 core PVC sheathed round copper cable size 23/.0076 to enable fixing in to plug point shall be provided by contractor. (b) GI Pipes, float valve, stop valve, PVC connection shall be measured and paid seperately under respective item. (c) Serial Number as issued by Engr-In-Charge of cooler and GE Office name shall also be written on cooler with red colour permanent marker or paint, cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
Supply & installing of Voltage stabilizer for automatic operation having input & output voltage, Amps, Over & low voltage cutout and timer delay function etc digital display single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA with wall mounting bracket complete all as specified and as directed.
Supply, testing and install washing machine with in built hydro extractor of capacity 10 Kg (per charge) front loading electrically heated stainless steel body controlled fully automatic with Pneumatic operated valves for auto water inlet, auto drain V.F.D (Variable Frequency Drive) for variable speed, electric motor 5.4-6.0 KW, through programmable logic control (PLC), with touch screen display. Extraction speed - 850 R.P.M. Basket Size: 560 mm washer drum dia X washer drum height 743mm, washer drum volume 103 Liters all as specified and as directed.
Supply, testing and install Drying tumbler electrically heated having loading capacity of 10 Kg per charge Electric Heated with Electric load 5.4-6.0 KW, front loading type, auto timed, auto reverse, Microprocessor controlled with electric motors and electric panel complete. Fully die pressed door, inner basket S.S, Outer body M.S sheet insulated with glass wool, as our detailed technical specification. Basket size : 663 mm dia x 570mm depth all as specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “HOT WATER SUPPLY AND SOLAR WATER HEATER WORKS" as listed in Schedule ‘A’ Section - XI (Part-I)
Sch 'A' Sec - XI (Part-II), (HOT WATER SUPPLY AND SOLAR WATER HEATER WORKS)
Supply, installing, commissioning and testing of electric water heater (Geyser) storage type ABS body of capacity 25 litre, BEE approved 5 Star rating, 230 V , single Phase, AC supply, inner tank made out of heavy duty stainless steel sheet (Designed with single weld line, factory tested with hydraulic pressure as per latest IS code) with glass lined coating complete with all accessories such as safety valve, thermostate, NRV, connection piece PVC connection for HOt and cold water, three core PVC insulated PVC Sheathed copper conductor flexible cable including 15 Amp plug suitable for existing socket and fixing material, 04 no Nut bolt grouting in wall in PCC (1:2:4) using 12.5mm graded stone aggregate for hanging the geyser and making good the disturbed surface complete all as specified and directed by Engr-in-Charge.
Supply, installing, commissioning and testing of Solar Water Heating system (Flat Plate Collector) based on indirect transfer of heat of capacity 500 Ltrs Per Day including electric backup stainless steel hot water tank suitable for inlet water with chlorine and fluoride content up to 100 PPM and comprising of solar flat plate collector, collector stand assembly with collector 'A' Size aluminium box collector comprising of following :-
Insulated stainless steel Hot water storage tank non pressure type made of stainless steel grade 04 Cr 18 NI or 07 Cr 18 NI of IS 1570 (Part-3)-1985, TIG Welded of 500 Ltrs capacity, non-magnetic tank with stainless steel fittings with following specification -01 No shall be insulated with 40 mm thermal grade PU insulation with FRP Cladding Tank stand assembly shall be made of Size 38 x38 x 4 mm duly pre-treated and stove enamelled with black colour paint.
Provisions of electrical back up with min 3 KW heating element - One Job Solar water heating system shall be provided on roof of single / double storey building. The electrical back up connection shall be tapped from sub main board provided at ground floor.
Heat exchanger shall be cage type and made of stainless steel tube of grade 04 Cr 18 NI or 0718 NI of IS 1570 (Part-2) 1885
All other pipe /civil work, steel staging work for PVC tank, electrical work, outlet and inlet thermometer, air release valves, check valves, gate valves, controls and instruments etc. all as required shall be deemed to be included in unit rate quoted by the contractor for this item. System internal piping shall be ISI Marked GI pipe medium class of IS: 1239 duly insulated with 50 mm thick rock wool of 48 Kg/M3 Density and 26 SWG AI Cladding.
Note:- (i) The system shall be tested on completion to ensure that 500 ltrs of water at 65 degree centigrade is available in hot water tank on a normal day in cold season. (ii) Normal water pipes and accessories from the normal overhead water tank to inlet of both make up water tank and plate collector shall be included in the quoted rates only. Similarly hot water pipes from hot water storage tank to bathrooms/ kitchen shall be measured and paid for separately.
Supply, installing, commissioning and testing of Solar Water Heating system (Flat Plate Collector) based on indirect transfer of heat of capacity 300 Ltrs Per Day including electric backup stainless steel hot water tank suitable for inlet water with chlorine and fluoride content up to 100 PPM and comprising of solar flat plate collector, collector stand assembly with collector 'A' Size aluminium box collector comprising of following :-
Insulated stainless steel Hot water storage tank non pressure type made of stainless steel grade 04 Cr 18 NI or 07 Cr 18 NI of IS 1570 (Part-3)-1985, TIG Welded of 300 Ltrs capacity, non-magnetic tank with stainless steel fittings with following specification -01 No shall be insulated with 40 mm thermal grade PU insulation with FRP Cladding Tank stand assembly shall be made of Size 38 x38 x 4 mm duly pre-treated and stove enamelled with black colour paint.
Provisions of electrical back up with min 3 KW heating element - One Job Solar water heating system shall be provided on roof of single / double storey building. The electrical back up connection shall be tapped from sub main board provided at ground floor.
Heat exchanger shall be cage type and made of stainless steel tube of grade 04 Cr 18 NI or 0718 NI of IS 1570 (Part-2) 1885
All other pipe /civil work, steel staging work for PVC tank, electrical work, outlet and inlet thermometer, air release valves, check valves, gate valves, controls and instruments etc. all as required shall be deemed to be included in unit rate quoted by the contractor for this item. System internal piping shall be ISI Marked GI pipe medium class of IS: 1239 duly insulated with 50 mm thick rock wool of 48 Kg/M3 Density and 26 SWG AI Cladding.
Note:- (i) The system shall be tested on completion to ensure that 500 ltrs of water at 65 degree centigrade is available in hot water tank on a normal day in cold season. (ii) Normal water pipes and accessories from the normal overhead water tank to inlet of both make up water tank and plate collector shall be included in the quoted rates only. Similarly hot water pipes from hot water storage tank to bathrooms/ kitchen shall be measured and paid for separately.
Subtotal
Sch 'A' Sec - XII, (EOT CRANE WORKS)
Designing, Supply , installation commissioning and testing 2 Ton capacity electrically operated overhead traveling crane (EOT) with suitable standard hooks, Class II, Medium duty indoor double girder type structural steel, totally enclosed, floor operated with pendent type push button switches, including rails and rail fixing arrangement, Electric motor of suitable size with VFD drive for cross travel, 3177 & 807 capacity 2 ton (EOT) with span 11 Mtrs centre to centre of gantry/track rail complete cofirming to relevant IS and with following parameters :- (a) Capacity - 2 Ton. (b) Class- II indoor type double girder. (c) Lift - 5.25m. (d) Hoist speed - 3m/min. (e) Creep speed - 0.3m/min. (f) Long travel - 15m/min. (g) Cross Travel - 10m/min. (h) Creep Speed - 1.5m/min. Note :- (i) Contractor shall submit design drawing of EOT crane for approval of GE before fabrication. (ii) Make of EOT crane manufacturer will be approved by CWE before execution. (iii) All the necessary accessories including rail to make the crane functional deemed to be included in the quoted rates of the item. Balance items as shown in the drawing deemed to be included in the lumpsum quoted of the building under Sch 'A' Sec-I.
Subtotal
Lump sum price worked out by the tenderer for “EXCAVATION, EARTHWORK AND SITE DEVELOPMENT WORKS" as listed in Schedule ‘A’ Section - XIII (Part-I)
Sch 'A' Sec - XIII (Part-II), (EXCAVATION, EARTHWORK AND SITE DEVELOPMENT WORKS)
Surface excavation not exc 20 cm deep and getting out in soft/ loose soil complete all as specified and as directed.
Subtotal
SACKSON ENTERPRISES
A.V BUILDERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
BOQ_685872.xls
BOQ Document • 0.35 MB
126723299.pdf
Tender Document • 0.13 MB
TenderdocT05_KLPLGJ.pdf
Tender Document • 3.25 MB
MainDrg1.rar
Tender Document • 7.83 MB
MainDrg2.rar
Tender Document • 8.31 MB
BTD1.rar
Tender Document • 6.36 MB
BTD2.rar
Tender Document • 5.47 MB
BTD3.rar
Tender Document • 6.91 MB
126723302.html
Tender Document • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .