Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.0 LAccepted-AOC 8 51 PLOT NO 6 LIC COLONY SUJATA NAGAR PENDURTHY MANDAL VISAKHAPATNAM 530042 AP | 530042 | L1 | Accepted-AOC ACCEPTED BEING L1 | |
| 2 | L2₹45.0 L+₹8.0 L (21.8%)Rejected-AOC | L2 | Rejected-AOC REJECTED DUE TO NOT BEING L1 | |
| 3 | L3₹54.5 L+₹17.6 L (47.5%)Rejected-AOC | L3 | Rejected-AOC REJECTED DUE TO NOT BEING L1 | |
| 4 | Rejected-Technical | - | Rejected-Technical REJECTED SINCE THE FIRM HAVE NOT SUBMITTING DOCUMENTS TO MEETING THE STIPULATED CRITERIA IN NIT |
Tender Value
₹35.4 L
EMD Value
₹70,800
Closing Date
16 May 2024, 6:00 pmClosed
Garrison Engineer M NAS Arakkonam
Garrison Engineer M NAS Arakkonam 631006
SPECIAL REPAIRS TO REPLACEMENT OF BER DECLARED DG SET 160 KVA AT THIRUMALPUR PUMP HOUSE AND PROVISION OF 6 IN NUMBER STREET LIGHTS IN VARIOUS LOCATION AND PROVISION OF ELECTRICAL POINTS AT POST OFFICE AND FLAME PROOF FITTINGS TO BE INSTALLED FOR PO
2024_MES_650347_1
8353E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Garrison Engineer M NAS Arakkonam
AS PER NIT
7 documents required · 7 mandatory
₹500
Garrison Engineer M NAS Arakkonam
₹70,800
Yes
1 Jul 2024
18 Apr 2024
18 May 2024
18 Apr 2024
16 May 2024
2 May 2024
Amount
Supply, install, test and commissioning of accoustic proof AMF type diesel engine driven generating set fully wired, 415V, +5%, AC 3 phase, 4 wire, 50 Hz having capacity 160 KVA continous rating power factor 0.8 (lagging), connecting as per IE rules and mouted on a common base plate with anti vibration pad recommended by the manufacturer all as specified and directed., The DG set shall comprise of following :- . The diesel engine will comprise of following:-
(A) Diesel Engine - The engine should be six cylinder,liquid cooled, turbocharged with after cooler, developing 206 BHP @ 1500 RPM. is inline, electric start, compression ignition, 4 stroke, designed to run continuously at 1500 RPM confirming to IS/IEC 60034-1 strandard. Diesel Engine will comply with present CPCB -IV norms. Make - CUMMINS / KIRLOSKAR/ CROMPTON GREAVES
Dry type air cleaner
Exhaust silencer suitable for canopy
Expansion bellow
lube oil coller
Lube oil filter
Fuel filter
Radiator with pusher type fan and mounting
In-line mono block fuel injection pump
Electronic governor and fuel feed pump
Flywheel with starter ring and bell housing suitable for close coupling
12 Volt electric starter motor
Battery charging alternator
Microprocessor based KG745 controller fixed in power panel
Protection system for Low lube oil pressure, high water temperature
(B) Alternator, The alternator shall be designed for an output of 160 KVA suitable for continuous operation rated at 1500 rpm 415 V, 0.8 PF, 50Hz, 3Ph in SPDP enclosure, self exicted & self- regulated, Brush less, floor mounted with Ball or Bearing on end shields. The alternator conforms to IS : 4722, BS EN 60034-1 & will be suitable for tropical condition. Make;- KIRLOSKAR/ ALSTOM/STAMFORD/JYOTI/ CROMPTON GREAVES.
(C) Electric system : The electric system of the starter motor and charging alternator shall have the following components:- (i) Charging alternator 12V, DC (ii) Voltage regulator built in type IC regulated (iii) Starter motor 12 volts DC (iv) Battery 12 volts DC and capacity 120 AH 02 nos with one set of connecting leads of 70 Sqmm size copper cable.
(D) Fuel tank (Service tank) : The fuel tank shall be mild steel suitable to hold 290 ltrs capacity and shall be inlducing fuel level indicator duly marked to read 25%, 50%, 75%,100% per division fuel line from tank to engine arrangement for fuel filling fuel and digital display and drain out facility etc. compelte all as specified.
Disconnecting the existing DG sets from its all electrical connections (including control panel connection) and removing the DG set 82.5 KVA capacity from its foundations ,shifting the DG set safely from the following locations and hand over to MES stores all as specified and as directed
Material and labour for Earthing complete with using copper earth plate electrode of size 600mm x 600mm x 3.15 mm thick buried directly underground vertically (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate at a depth not less than 1.5m below ground level connected with and incl copper strip 20x3 mm including 40 mm dia GI pipe light grade by means of nuts bolts, washers and copper earth strip protected by GI pipe light gradev 40 mm bore up to 7.5 mtr and connectingDG sets etc, as per site requirement necessary earth work in any type of soil PCC (1:3:6) type C1 chamber and RCC(1:2:4)type B-1cover and watering pipe 20 mm dia medium grade with funnel complete with mesh , refiling with soil all as specified.
Labour for surface excavation strictly manually without damaging any electric LT /HT , route indicators and earthing pits ect noty exceeding 30 cm deep and average 18 cm deep and getting out in soft/loose soil including removing gree vegetation, rrots , bushes in the substation area and near instalations fencing are etc complete all as specified and directed
Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, in hard/ dense soil.
Material and labour for cement concrete type D2 1:4:8, (Using 40mm graded stone aggregate) in foundations, filling and mass concrete complete all as specified and as directed by Engr-in-charge.
S&F Steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I. S.1161-1979 grade St.-240
S & F wind ties for roof including securing bolts, posts and struts, including cutting tops to shape as directed, drilling holes, bolting or riveting etc and similar work conforming to Fe-290 Gde E-165.
S&F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified
S&F Pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified
Surface excavation n.exc 30cm deep and averaging 15cm deep and getting out in hard/dense soil
Material and labour for 100mm cement concrete type D-2, 1:4:8 (40mm graded aggregate) complete all as specified and as direced by Engr-in-charge.
M&L HARD CORE OF GAUGE N.EXC.63 MM filling under floors or in foundations N EXC 15MM thick including watering and consolidation
M&L Sand filling under floors or in foundations including watering and consolidation
M & L for 70 mm thick PCC 1:2:4 type B1 (20 mm graded aggregate) as in flooring.
Material and labour for two coats of synthetic enamel paint over one coat of red oxide priming including preparation of new steel surfaces over 10 cm in width or girth, not otherwise described complete all as specified and as directed by Engr-in-charge.
Supply, installation, testing and commissioning walk in cold storage of refrigeration capacity 10,000 Btu/hr x 02 Nos outdoor unit having chiller room dimension 12 x 10 x 8 Feet (External Dimension) to maintain room temperature + 2 to + 8 Deg C for keeping fruits, Vegetables, Dairy etc of total product capacity 1000 kg/day maintain product temeprature for ambient temperature up to 41 Deg C. 60mm thick PUF Insulated panels with Pre Painted GI inside & outside finish for Walls and Ceilings and 60mm thick PUF Insulated panels with Pre Painted GI inside & Anti Skid GI outside finish for flores. 60mm thick PUF Insulated ( 34” x 78” ) Manual typeSwing Door 01 No with Pre Painted GI inside & outside finish. Note :- 1. Chiller Room with supply of PUF Panels, doors and accessories - 01 Nos 2. Refrigeration units of capacity 10,000 Btu/hr and its controls with standby - 02 Nos
Supply, installation, testing and commissioning Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 90 V to 300 V with output voltage stabilized at 240 with accuracy ± 2.5% of capacity 05 KVA 4000 W all as specified and directed by Engineer-in-Charge .
Material and labour for Sub main wiring with four run single core 6 sqmm and two run single core 6 sqmm ass earth wire with multi stranded copper conductor PVC insulated unsheathed FRLS cable 1100 volts grade confirming to IS-694 continuity conductor drawn into and including non-metallic rigid PVC conduit 20 mm dia concealed wiring through wall/ceiling/floor/roof etc including conduit accessories including taking down old sub main wiring with PVC conduit and taken as credit complete all as specified and as directed. Notes: (i) The disturbed surfaces shall be made good with existing surface including finishes as applicale. (i) Two different color wires shall be used for phase and neutral . (iii) Connections of cables with MCBs or bus bars shall be done through appropriate size brass/ copper thimbles . (iv) Six run of 6.0 Sqmm cable, and one run of PVC conduit will be measured as one unit. Make of cable:- Finlex/Poly cab/ Asian. Make of PVC conduit : Avon plast/ Kon seal / Garware.
Material and labour for Sub main wiring with two run single core 4.00 sqmm multi stranded copper conductor PVC insulated unsheathed FRLS cable 1100 volts grade and one run of 4.00 Sq mm multi stranded copper conductor cable as earth continuity conductor with colour code drawn through and including one run of 25 mm dia rigid PVC conduit and conduit accessories or casing cappings including accessories fixed on wall/ceiling etc., or concealed in wall and connecting to common earth dolly complete all as specified and as directed. Notes: (i) Two different color wires shall be used for phase and neutral . (ii) Connections of cables with MCBs or bus bars shall be done through appropriate size brass/ copper thimbles . (iii) Two run of 4.0 Sqmm cable and one run of PVC conduit will be measured as one unit. (iv)Make of PVC copper conductor cable:- Finlex/Poly cab/ Asian. (v)Make of PVC conduit : Avon plast/ Kon seal / Garware.
Supply and fix in repair for MCB TPN 415 V, 40 Amps with breaking capacity 10KA C curve complete Including taking down old unserviceable all as specified and as directed by Engr-in-charge. Make: Siemens/Scheneider/ABB.
Supply and fix for MCB SP 230 V, 6-32 Amps with breaking capacity 10KA C curve complete all as specified and as directed by Engr-in-chargeMake: Siemens/Scheneider/ABB
S&F Metal Clad double pole and earth enclosure with socket complete with one single pole and nuetral MCB 20 Amps, 415 Volt, complete all as specified and as directed. Make: Legrand/Siemens/Scheneider/ABB.
S&F DB for MCB TPN 04 way double door DB with 200 amps rated copper bus bar in SS enclosure double door type having IP 43 and IK 09 protection Including taking down old u/s DB, and MCB's all as specified and directed . Note : MCB SPN/SP shall be measured and paid under the respective item of the schedule. Make: Legrand/Siemens/Scheneider/ABB.
Material and labour for Earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick buried directly in ground vertically to a depth of not less than 2.25 mtr below ground level , with top edge of the earth plate at a depth of not less than 1.5 mtr below ground level connected with and incl GI strip earth 25 x 4 mm size including alternate 5 layers of charcoal (250 kg) salt crystal (200 kg) top two inches layers with Back filling compound (100 Kg) including 15 mm dia GI pipe light grade by means of nuts, bolts, washers and necessary earth work upto 7.5 mtr and connecting to test point, LT Switchgear etc as per site requirement including necessary excavation, earth work in any type of soil, PCC (1:3:6) type C-1 earth chamber, 40 mm thick RCC Cover with 6 mm dia MS bars 10 cm C/C on both ways as reinforcement complete all as shown in elecrical plate No 3 of SSR Pt- I including testing on completion complete all as specified and as directed. Notes:-The rates quoted is inclusive of galvanised earth lead strip 25x4mm conductor upto a length of 7.5m from the earth pit, necessary earth work PCC chamber, RCC cover, reinforcement, removal of surplus soil , site clearance etc. .
Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete
Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete.
Excavation in trenches, n. exc 1.5 m wide and n. exc 1.5 m in depth for taking up / laying cable etc and getting out for soft/loose soil complete all as specified and directed.
Spreading riddled earth for low thermal resistivity UG cable cushioning complete all as specified and directed
Supply and lay standard size common burnt clay building bricks sub class 'B' for cable protection, laid dry complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25cm for soft/loose soil complete all as directed.
Removing excavated material n.exc 50m and depositing where directed at a level n.exc 1.5 m above the starting point complete all as directed.
Supply and lay pipe galvanised iron tubing light grade of 50 mm dia in trenches/under road or floor/on wall / near pole/panel etc all as per site requirement complete all as specified and directed.
Supply,laying XLPE insulated, screen, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor of size 16 sqmm 4 core, connecting with proper size Aluminium lugs, glands whereever necessary near LT Panels / Bus bar chamber panel / Street light boxes all as per site requirement , testing complete all as specified and directed.
Supply and fixing Service cable 2 core 4 sqmm aluminium complete all as directed by Engineer in Charge
Material and labour for cutting of bituminous road / floor for laying of U/G cables/water line not exceeding 1.5 meter wide and not exceeding 1.5 meter deep including refilling / with material and , watering well ramming / compacting and making good with 1:3:6 type C-1 (20 mm graded aggregate) complete all as specified and directed by Eing-in-charge.
S & F Street light control box metal type including MCB SPN 20 Amp complete with bracket and clamp.
Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 metres long)
M&L Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, ashers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint
Material and labour for PCC for foundation for street light pole whereever necessary 1:4:8 type D-2 (Using 40mm graded stone aggregate) complete all as specified and as directed by Engr-in-charge.
PCC for coping for Light pole, road cutting etc whereever necessary 1:3:6 type C-1 (20 mm graded aggregate) complete all as specified and directed.
Taking down copper/aluminium point wiring (light,fan, socket or power) complete, including fixtures and fittings such as switches, ceiling roses, pendents, regulators, sockets, light fittings, exhaust fan etc. removing materials to store for keeping in safe custody to refix in nearest location and making good disturbed surfaces of wall, floors, etc.complete all as specified and as directed
Refixing of switch piano 5/6 Amp in existing location complete all as specified and as directed
Refixing of socket 15 Amp in existing location complete all as specified and as directed
Refixing of 6 module metal box in existing location complete all as specified and as directed
Refixing of 6 module modular plate with frame in existing location complete all as specified and as directed
Disconnecting & Removing of the existing ceiling fans & Exhaust fans and handed over to the E/M stores.
Material and labour for point wiring of One light/fan point controlled by one switch with 1.5 Sqmm single core PVC insulated unsheathed multi stranded copper conductor drawn into including in stove enamelled steel conduit fixed on wall / roof , of size not less than 20 mm dia and provision of 1.5 Sqmm single core PVC insulated unsheathed multi stranded copper conductor as earth wire including provision of 1.5 Sqmm single core PVC insulated FRLS unsheathed multi stranded copper conductor as earth wire and cast iron / pressed steel treminal boxes for mounting switches, sockets, fan regulator etc with 3 mm thick plastic laminated sheet cover complete.
Supply and fix Fluorescent tube light fitting. 1x 16 W ,LED flame proof type FLP-WP made of aluminium alloy LM6, with electronic ballast, bipin holders, connector block,etc. complete with all accessories prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size and terminate with metal spiral conduit pipe from ceiling rose
Supply and fixing of flame proof exhaust fan with standard accessories ,330mm sweep, AC, single phase, 230/240 volts complete all as specified and terminate with metal spiral conduit pipe from ceiling rose
Material and labour point wiring one of One light/fan point controlled by one switch with 1.5 Sqmm single core PVC insulated FRLS unsheathed multi stranded copper conductor drawn into including PVC casing & caping/fixed on wall/roof/ceiling etc of size not less than 20 mm dia including provision of 1.5 Sqmm single core PVC insulated FRLS unsheathed multi stranded copper conductor as earth wire Complete
All as per item ser no-51 above here in before but one 3 pin socket outlet 5 Amps, indipendent board with cables 1.5 Sqmm size.
All as per item ser no-51 above here in before but one 3 pin socket outlet 5/15 Amps, indipendent board with cables 4.0 Sqmm size.
Supply and fixing LED lights fitting 1x 16W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete
S&F Modular metal flush box but 3 module
S&F Modular metal flush box but 6 module
S&F White cover plate with frame 3 module
S&F White cover plate with frame 6 module
S&F Modular switch socket outlet multi purpose 3 pin, 15 amp and one pin, 5 amp controlled by one switch
S&F Modular switch 1 way 6A, 1 modul
S&F Ceiling rose, 3 phase/PVC/ polycarbonate, isolated body.
S&F MCB,DB SPN 04 way double door DB with 200 amps rated copper bus bar in SS enclosure double door type. Note : MCB SPN/SP shall be measured and paid under the respective item of the schedule.Make: Legrand/ Siemens/Scheneider/ABB.
Supply and fix for MCB SPN 230 V, 32 Amps with breaking capacity 10KA C curve complete all as specified and as directed by Engr-in-charge.Make: Legrand/ Siemens/Scheneider/ABB Note : Including taking down old unserviceable.
Supply and fix for MCB SP 230 V, 6-32 Amps with breaking capacity 10KA C curve complete all as specified and as directed by Engr-in-charge.Make: Legrand/ Siemens/Scheneider/ABB.
Supply and fix on wall/ceiling/any other given situation, XLPE insulated GI wire/strip armoured electric power cable (Heavy duty) with stranded aluminium conductor 1100 volts grade, cross sectional area 185 Sqmm 3.5 Core including necessary lugs and clamp for fixing cable on wall complete all as specified and as directed Make: Polycab/Havells/Crystal Cables
Demolition of cement concrete ( unreinforced) in ground floors and paving n. exc 15 cm thick ( below & above ground level) and removal & rubish of Premises exc 250 m but n exc 500 m complete all as specified and as directed.
Green Ray Technologies
Sree Nandhees Technologies Pvt Ltd
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .