| 1.00 | Building Work Construction of DG set Bldg with toilet and rest room for operator (made up of RCC framed structure as per codal provisions) of size DG set bldg 12.00 Mtr X 6.00 Mtr Toilet of size -3.00 Mtr X 1.50 and Rest room of size 4.30 X3.00 as per arch line drg. The structural design of bldg needs to be prepared and also to be vetted from NIT or IIT by the contractor. Certificate from IIT/NIT in their letter head needs to be in conjunction with codal provns and submitted by the contractor before execution of the wk.
Design criteria: The structural shall be designed in accordance with relevent IS Provns/NBC code/ extant govt guidelines suitable for Thoise, however, some of design criteria are listed as under:
(a) Seismic Co-efficient:As per Seismic Zone IV.
(b) Snow load :As per IS codal provn applicable at Thoise.
(c) Wind load :Equivalent to wind speed of min 55 mtrs/sec or as per relevent IS applicable at Thoise .
(d) Roof slope: as per design requrement.
(e) Design load: As per IS 875/Relevent IS provn.
(f). Design of fdn as vetted by the auth as mentioned above.
(g) SBC of nearby area is roughly 15Ton/sqm at a depth of 1.5m . However, Contractor shall untertake actual SBC of site from Govt approved Lab/Agency and shall be approved by GE in case the SBC is less than 15Ton/Sqm the fdn design shall be accordingly modified and shall be got approved from GE . The quoted rate is deemed to incl this aspect.
(h) The FFL should be 450mm above the GL and subsequent filling and PCC work must be included in the quoted rates by the contractor.
(l) RCC Work of M30 Designmix should be considered in Thoise Area.
(A) Dimension Data.
(i) DG Set Bldg
(a) Length : 12.00 M. (Inner Wall to Inner Wall)
(b) Width : 6.00 M. (Inner Wall to Inner Wall)
(c) Height : 6.25 Mtr from FFL. (ii) Operator Rest Room
(a) Length : 4.30 M. (Inner Wall to Inner Wall) | 1 | Each Job | 65,00,000 ₹65 L | 28,00,000 ₹28 L |
| 1.01(b) Width : 3.00 M. (Inner Wall to Inner Wall) (c) Height : 3.50 Mtr from FFL. (iii) Toilet (a) Length : 3.00 M. (Inner Wall to Inner Wall) (b) Width : 1.50 M. (Inner Wall to Inner Wall) (c) Height : 3.50 Mtr from FFL. (B) Foundation : shall be designed by the tenderer and quoted rate is deemed to include the same (Design Cost). All the items i.e. Exavation for foundation/PB, removal/refilling of soil, PCC Work in fdn, Reinforcement/RCC work, formwork are deemed to be included in the quoted rate for this item. Quoted rate is also deemed to include necessary vetting of Structure duly signed and stamped from any IIT/NIT of the structural drawing prepared by the approved structural design consultant of tenderer. (C) Column : shall be designed by the tenderer and quoted rate is deemed to include the same (Design Cost). All the items i.e. Reinforcement/RCC work, formwork are deemed to be included in the quoted rate for this item. Quoted rate is also deemed to include necessary vetting of Structure duly signed and stamped from any IIT/NIT of the structural drawing prepared by the approved structural design consultant of tenderer. (D) Beam (Plinth Beam, Lintel Beam & Room Beam) & Roof Slab : shall be designed by the tenderer and quoted rate is deemed to include the same (Design Cost). All the items i.e. Reinforcement/RCC work, formwork are deemed to be included in the quoted rate for this item. Quoted rate is also deemed to include necessary vetting of Structure duly signed and stamped from any IIT/NIT of the structural drawing prepared by the approved structural design consultant of tenderer. (E) Wall: Pre-cast cement concrete block masonry with solid blocks type B1, 1:2:4 (20 mm graded stone aggregate) and setting in cement mortar 1:4, complete all as specified and are deemed to be included in the quoted rate for this item. (For thickness of wall ref arch drg). (F) Rendering : (a) External Rendering 15 mm thick (in two layer of 10 mm and 5 mm) on precast concrete block masonry/Concrete surface in cm 1:4, finished even and smooth without using extra cement, using water proofing compound complete all as specified and are deemed to be included in the quoted rate for this item. NOTE: WPC should be added as per manufacturing instruction or 3% of weight of cement. | |||||
| 1.02(b) Internal Rendering 15 mm thick on fair faces of precast concrete block masonry surface in cm 1:6, finished even and smooth without using extra cement complete all as specified and are deemed to be included in the quoted rate for this item.(c) Rendering 5 mm thick on fair faces of roof slab, soffits of slab surfaces in cm 1:3, finished even and smooth without using extra coment complete all as specified and are deemed to be included in the quoted rate for this item. (G) Flooring/Wall Tiling (i) DG set Bldg : (a)18 to 20 mm thick machine cut kota stone flooring over incl 20mm thick cement screed bed in CM 1:6 laid and jointed with grey cement slurry mixed with pigment to match the shade of the flooring and incl rubbing and mirror polishing complete over sub base : 75 mm thick, Plain cement concrete type D-2, 1:4:8 using 40 mm graded stone aggregate, finished even & rough over Hardcore 100 mm thk : (Broken stone boulders) of guage exc 63mm but n exc. 100 mm, deposited, spread and levelled in layers, watered and rolled/rammed to a true surface over rammed earth filling under floor are deemed to be included in the quoted rate for this item. (b) kota stone 18 to 20mm thk over 10 mm thick plaster in cm 1:4 as in skirting 100mm hight etc set and joing free in net cement slurry and pointing white or coloured cement to match complete. (ii)Operator Rest Room (Floor & skirting) (a) Non Skid ceramic joint free coloured tiles 7 to 8mm thick (square/rectangular) area of each tile exceeding 0.18 sqm but not exceeding 0.38 sqm, over and including15 mm thick screed bed in cm 1:4 in floors etc. set and joint free in neat cement slurry and pointed in white or coloured cement to match complete over sub base : 75 mm thick, Plain cement concrete type D-2, 1:4:8 using 40 mm graded stone aggregate, finished even & rough over Hardcore 100 mm thk : (Broken stone boulders) of guage exc 63mm but n exc. 100 mm, deposited, spread and levelled in layers, watered and rolled/rammed to a true surface over rammed earth filling under floor are deemed to be included in the quoted rate for this item. (b) Non Skid ceramic joint free coloured tiles 7 to 8mm thick (square/rectangular) in wall matching with floor over and including10 mm thick plaster in cm 1:4 in Skiting 100mm high etc. set and joint free in neat cement slurry and pointed in white or coloured cement to match complete. | |||||
| 1.03(iii) Toilet (Floor & Wall tile): (a) Non skid Ceramic coloured tiles 7 to 8 mm thick area of each tile exceeding 0.06 sqm but not exceeding 0.11 sqm, over and including15 mm thick screed bed in cm 1:4, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match complete over sub base : 75 mm thick, Plain cement concrete type D-2, 1:4:8 using 40 mm graded stone aggregate, finished even & rough over Hardcore 100 mm thk : (Broken stone boulders) of guage exc 63mm but n exc. 100 mm, deposited, spread and levelled in layers, watered and rolled/rammed to a true surface over rammed earth filling under floor are deemed to be included in the quoted rate for this item. (b) Glazed ceramic coloured tiles in vertical surface 300X 200X7mm/ 450X 300X 7mm thick set over 10 mm thick rendering in CM 1:4 and jointed in neat cement slurry and pointed in white or colour cement to match, complete all as specified and as directed by Engr-in-Charge. (H) Roof Treatment: APP based polymeric membrane minimum weighing 3kg/sqm and minimum 3mm thick reinforced with polyster non wove fabric (wt. not less than 150 gms/sqm) land on primed surface by forced application including 20 mm thick plaster in 1:4 incl WPC as per manufacturing instruction complete all as specified are deemed to be included in the quoted rate for this item. (J) Plinth Protection : 75 mm thick, PCC 1:3:6 over 75mm thk stone hard core (broken boulder) n exc 63mm, deposited, spread and levelled in layers watered and rammed to a true surface, complete all as specified are deemed to be included in the quoted rate for this item. (K) Chajjas: RCC chajjas to be provided as per details in arch and structural drg are deemed to be incl in the quoted rate for this item. (L) Joinery (Doors & Window as shown in drg) (i) Frame : Pressed steel frames for doors with one or more rebates including necessary fixing lugs, hinges, lock strike plate, etc., complete, (ii) Door shutters : 35mm 2nd class hardwood plain, panelled shutters (any number of panels), with panels of timber flat on both sides (feather edged), or of veneered particle board medium density, wood particle board with commercial face incl all fitting assy. (iii) Window/Ventilator: (a) steel window with side hung shutter including projecting type hinges with steel handle and steel pegstay complete with glazing bars, dovetailed or welded as per specification, complete all as specified are deemed to be incl in the quoted rate for this item. | |||||
| 1.04(b) Sheet glass 4.0 mm thick, ordinary quality and glazing with oil putty in square n exc 0.5 sqm in each pane complete all as specified are deemed to be incl in the quoted rate for this item. (M) Rolling Shutter. Steel rolling shutters 1.25 mm thick, gear operated type with bevel gear box and crank handle with out ball bearing, as specified including top cover, anchoring rod, hasp and staple and one shop coat of primer; erected in position as indicated and incl Safety lever locks mild steel with 4 levers for rolling shutters, complete all as specified are deemed to be incl in the quoted rate for this item. (N) Finish (Internal & External) : (a) External Wall : Preparation of new surfaces of walls/concrete and applying two coats of cement base paint over a coat of priming paint complete all as specified and directe by engr in charge are deemed to be incl in the quoted rate for this item. (b) Internal Wall : Preparation of new surfaces of walls/concrete and applying three coat of white wash complete all as specified as specified and directed by engr in charge rate are deemed to be incl in the quoted rate for this item. (c) Ceiling: Preparation of new surfaces of ceiling and applying three coats of white wash complete all as specified as specified and directed by engr in charge rate are deemed to be incl in the quoted rate for this item. (d) Steel Surfaces : Preparation of new steel surface and applying two coat synthetic enamel pait over one coat of red oxide complete all as specified as specified and directe by engr in charge are are deemed to be incl in the quoted rate for this item. Note: (a) Anything missed out above but reqd as per arch line plan for construction of functional structures is deemed to be included in quoted rate and no extra claim shall be admissible. (b) Yard stick of bldgs as above to be provided by contractor before payment. specified and directde by engr in charge areare deemed to be incl in the quoted rate for this item. (c) Ceiling: Preparation of new surfaces of ceiling and applying three coats of white wash complete all as specified as specified and directe by engr in charge areare deemed to be incl in the quoted rate for this item. (d) Steel Surfaces : Preparation of new steel surface and applying two coat synthetic enamel pait over one coat of red oxide complete all as specified and directed by engr in charge rate are deemed to be incl in the quoted rate for this item. | |||||
| 2.00 | Internal Water Supply Supply & Fixing , 20 3-layer PP-R Polypropylene random copolymer) concealed pipes SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded Polypropylene random fittings fixed complete to walls, ceilings or in floors etc. | 10 | Running Metre | 500 ₹5,000 | 695 ₹6,950 |
| 3.00 | Supply & Fixing , 16mm 3-layer PP-R Polypropylene random copolymer) concealed pipes SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded Polypropylene random fittings fixed complete to walls, ceilings or in floors etc. | 8 | Running Metre | 450 ₹3,600 | 695 ₹5,560 |
| 4.00 | S& F 20 mm dia PP-R Gate valves (brass insert) all as specified and directed. | 1 | Each | 500 ₹500 | 950 ₹950 |
| 5.00 | S&F vitreous China squatting pan, Orissa pattern, size 580 x 440 mm white, with integral foot rests (excluding flushing cistern and flush pipe) incl fxing of WC and making good floor to match the existing surface, complete all as specified and as directed by Engr-in-Charge. | 1 | Each | 3,000 ₹3,000 | 4,900 ₹4,900 |
| 6.00 | S&F PVC valveless, syphonic action type, flushing cistern, 10 litres capacity, low level, white, with inlet, ball valve, float and handle including brackets and flush pipe of polyethylene of low or high density or PVC. 32 mm dia, for low level cisterns, complete all as specified and as directed by Engr-in-Charge. | 1 | Each | 1,500 ₹1,500 | 3,500 ₹3,500 |
Updated dates
Tender Value
₹1.2 Cr
EMD Value
₹2.1 L
Closing Date
4 May 2026, 4:00 pmClosed
CWE(AF) Leh
HQ CWE(AF) Leh
PROVN OF CENTRALISED HEATING AND COOLING SYSTEM WITH HUMIDITY CONTRAL FOR DANGER BUILDING AT AFS THOISE
2026_MES_757582_1
82141/E8
Open Tender
Civil Works
180 days
GE(AF) Thoise
As per NIT
9 documents required · 9 mandatory
₹1,000
GE(AF)Thoise
₹2.1 L
Yes
11 May 2026
25 Mar 2026
6 May 2026
25 Mar 2026
4 May 2026
17 Apr 2026
Internal Water Supply Supply & Fixing , 20 3-layer PP-R Polypropylene random copolymer) concealed pipes SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded Polypropylene random fittings fixed complete to walls, ceilings or in floors etc.
Supply & Fixing , 16mm 3-layer PP-R Polypropylene random copolymer) concealed pipes SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded Polypropylene random fittings fixed complete to walls, ceilings or in floors etc.
S& F 20 mm dia PP-R Gate valves (brass insert) all as specified and directed.
S&F vitreous China squatting pan, Orissa pattern, size 580 x 440 mm white, with integral foot rests (excluding flushing cistern and flush pipe) incl fxing of WC and making good floor to match the existing surface, complete all as specified and as directed by Engr-in-Charge.
S&F PVC valveless, syphonic action type, flushing cistern, 10 litres capacity, low level, white, with inlet, ball valve, float and handle including brackets and flush pipe of polyethylene of low or high density or PVC. 32 mm dia, for low level cisterns, complete all as specified and as directed by Engr-in-Charge.
S&F Vitreous China wash basin, flat or angle back type, size 600x480mm, white, including cutting for and pinning in ends of brackets or erecting stand, waste coupling 32 mm PTMT, PVC waste pipe excluding taps, chain and plug and porcelain stopper but including brackets, complete all as specified and as directed by Engr-in-Charge.
S&F Bib tap cast copper alloy chromium plated fancy type with crutch or butterfly handle, screwed down, screwed for iron pipe/PPR pipe or for brass ferrule of 15mm bore complete all as specified and as directed.
S&F Pillar taps 15 mm dia, cast copper alloy, with capstan heads, chromium plated, screwed down high pressure, with or without lettered 'Hot' or 'Cold' with long screwed shanks and fly-nuts, screwed for iron pipe and fixed, complete all as specified and as directed by Engr-in-Charge.
S&F Stop valves, 15mm dia, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed, complete all as specified and as directed by Engr-in-Charge.
S&F in soap tray vitreous china embedded in wall, complete all as specified and as directed by Engr-in-Charge.
РVС соnnection 15mm dia with PTMT nuts of length 450mm complete all as specified and as directed.
S&F 500 ltrs rotational moulded polyethylene water storage tanks (cyclindrical vertical with closed top) incl connecting up pipes securing access covers incl ball brass valves 25 mm, high pressure with polythene float and flynut etc,complete all as specified and as directed by Engr-in-Charge.
S&F towel rail 450mm long of PTMT fixed with and including chromium plated brass screws and wooden/plastic cleats (Minimum weight 170gms), complete all as specified and as directed by Engr-in-Charge.
S&F cast iron floor trap 100 mm dia with grating incl jointing to waste pipe fixed in cement concrete type B1 (1:2:4, using 20mm graded stone aggreagte), complete all as specified and as directed by Engr-in-Charge.
M&L for PVC (SWR) pipes 110 mm bore single socketed, in any length with rubber ring joints, laid in trenches or in floors, complete all as specified and as directed by Engr-in-Charge.
Internal Electrification M & L for Point wiring for one light point/ fan point/ Bell point controlled by one switch with 1.5 sqmm PVC insulated and unsheathed FR-LSH copper conductor single core multi stranded flexible copper cable 1100 Volts grade conforming to IS-694 using approved colour code as per IS code drawn through non metallic rigid PVC casing Caping heavy duty double locked with size as per site requirement in accordance with clause No 19.25 of SSR Part I) ISI marked including casing caping accessories like bends, tees, junction boxes etc fixed with all accessories complete with MS box with 3 mm thick hylam sheet for fixing of switch, socket regualtor etc along with PVC insulated and unsheathed FR-LSH 1.5 sqmm multi stranded copper conductor cable 1100V (green color) as continuous earth lead wire connected to common earth and earth dolly complete all as specified and directed by Engineer-in-Charge.
All as per Ser item No 18 here-in-before but for 06 Amp socket outlets point controlled by one switch on Independent board with the cable 1.50 sqmm size complete all as specified and directed.
All as per Ser item No 18 here-in-before but for 06 Amp socket outlets point controlled by one switch on same board with the cable 1.50 sqmm size complete all as specified and directed.
All as per ser item No 18 here-in-before but for 16 Amp socket outlets point controlled by one switch on Independent socket outlet using 4.00 sqmm PVC insulated and unsheathed FR-LSH copper conductor single core multi stranded flexible copper cable 1100V of approved colour code as per IS code for phase and neutral along with PVC insulated and unsheathed FR-LSH 4.00 sqmm multi stranded copper unsheathed cable 1100V (green color) as continuous earth lead wire connected to common earth and earth dolly complete all as specified and directed.
M&L in replacment Switch piano, flush type, single pole, one way, 5 Amps, complete all as specified and as directed by Engineer-In-Charge.
M&L in replacment Switch socket combination, 2-in-1, 3-pin, 5-Amps, flush type, complete all as specified and as directed by Engineer-In-Charge.
M&L in replacment Switch socket combination 2-in-1, 3-pin, 5 and 15 Amp flush type universal type, complete all as specified and as directed by Engineer-In-Charge.
Supply and fixing Lamp holder including 10W LED Bulb, white Polycarbonate body, with back plate suitable for batten fittings fixed in position & connecting complete all as specified and as directed.
Supply and fixing LED lights fitting 1x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete.
Supply and fixing LED Bulk Head type with high output, 10 watt, 220 V AC, Color temperature 6500K or as directed, luminous flux of light 1000 lumens (lm) with all accessories, IP 65 protection dust and water resistant, surge protection up to 2.5kV, PC opal high efficiency diffuser ,LM 80 tested made die cast aluminium housing with complete assembly, suitable for surface/wall mounted with driver holder including connecting up using 1.5 sqmm copper conductor multistrand PVC insulated with three core flexible copper conductor cable of suitable size complete all as specified and directed.
Supply and fix exhaust fan, steel body AC single Phase. 230V of size 450m sweep with, blades, and frame and louvers
S&F LED Street Light fitting 30 watt, for opearting voltage between 110V to 320V system efficiency not less than 120 lumen / watt, PF-0.95 minimum, IP66 protection, 5700CCT(K), CRI between 80-85, confirming to LM79 and LM 80 standards or as per relevant IS for estimated life span of minimum 50,000 hrs consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with LED street optics LENS for uniform light distribution, weather proof gasket for lamp & driver compartment, Heat resistance toughened UV stabilized glass fitted in cast aluminium housing with SS screws, complete all as specified and as directed by Engr-in-charge.
Supply & Fixing Bracket made out of GI light grade pipe of size 40 mm dia 1.5 mtr long bend to an angle of 120 degree with 02 Nos MS clamp 50mm x 50mm and 04 sets of nuts,bolts and washers painting with two coats of synthetic enamel paint over a red oxide primer complete all as specified and as directed by Engr-in-charge.
Sheet metal enclosure MCB distribution board Triple pole & neutral 415 volts 4 way with IP-43 protection double door complete with appropriate size bus bar and neutral link, fixed flush in wall including chases cutting in wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and directed. Note - MCBs will be measured separately.
Supply and fixing MCB Single Pole 6 to 32 Amps rating 240V, 10KA 'C' curve miniature circuit breaker complete with connection testing and commissioning complete all as specified.
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of Triple pole and neutral and current carrying capacity 16 TO 32 AMP, in the MCB DB Complete with connection testing and commissioning complete all as specified and directed.
Submain wiring with 2X6 sqmm copper conductor cable (multistrand) PVC insulated FR (unsheathed) surface type, drawing in and including casing caping suitable size alongwith continuous earth wire 1X6 sqmm FRLSH PVC insulated copper cable as required, complete, all as specified.
Single pole and neutral sheet metal enclosure with a two pin and earth plug and socket complete with one single pole & neutral 20 amp MCB,240 Volts for AC box, complete, all as specifies and directed.
Central Air Conditioning System Incl Central Heating system (HVAC) Supply and fixing central air conditioning installations including AHUs, Water pump sets, cooling towers,ducting and electrical connection suitable for 3 phase, AC supply direct expansion system of capacity of 7.5 Ton for P-2 Danger Building. The system should be able to work under following condition : (i) Altitude 3070 m at Thoise. (ii) Outside temp condition is 30 +/- 2 degree celcius (iii) Inside condition to be maintain 20 +/- 2 to be maintain (iv) The equipment propsed should cater for derating factor for thoise area.
Supply and fixing central air conditioning installations , Water pump sets, and electrical connection suitable for 3 phase, AC supply direct expansion system of capacity of 7.5 Ton for P-2 Danger Building.(Stand By)
Supply, Installation, commissioning and testing of complete heating plant including boiler unit, chimney complete with all accessories as per the following. (A) Thermic Fluid Heaters 02 Nos (01 Working+01 Standby). Supply, installation, commissioning and testing of pressurised type 3 phase reverse flame horizontal / vertical smoke tube, Thermic fluid heaters (Glycol water based boiler) each of capacities not less than 50,000 Kcal/hr complete in all respect, with standard accessories to meet the required condition of temp and humidity criteria for danger building at Thoise Station complete in all respect with combustion chamber and equipment , automatic Monoblock burner assy, fire tubes, control panel with sequence controller , photocell for frame failure , HT transfer combustion chamber and equipment automatic Monoblock burner assy, fire tubes, control panel with /sequence controller, photo cell for frame failure, HT transfer electrode blower assy, electrical panel, mounting frames, pressure gauge at inlet and outlet suitable operation on 50HZ three/single phase AC supply compete in all respect to maintain the inside temperature20+/-2 degree Celsius when the outside temperature drops to (-20) degree Celsius i.e. Thoise winter climatic conditions including following item of work. BOILER UNIT: (a) Heater Unit :- Heat echanger cosisting of closely wound Helical concentric coils, double jacket arrangement to give adequate nos of passes on flue gas side made out of ERW tubes confirming to relevant IS suitable for high temperature all as per OEM design and required heat and capacity. (b) Pressure Jet Burner:- Suitable for light oil firing with stepless modulation mechanism all as per manufacturer design and of required head and capacity. (c) Combustion air fan with drive motor assembly all as per manufacturer design and oof required head and capacity. (d) Control Panel : Dust protected pre-wired unit mounted air cooled control panel housing a burner management system , switchgear consisting of contractors, overload relays, fuses and MCB etc. All as per manufacturer design and of required capacity. Note :- (i) The boiler shall be installed in system of (01 W & 1S)
ii) The tenderer should get the plant installed by any of the original equipment manufacturer with recommended makes of compatible components of items. (iii)The capacity of boiler shall be designed to maintian the inside temp of 20 (±) 2 degree Celsius. (iv)The boiler inner shell be made from carbon steel with dished ends (curved type) with thickness as per boiler design of OEM. (v) Outer shell be made from carbon steel with thickness as per boiler design of OEM. (vi) Boiler tube shall be seamless MS tube for quality commensurate with the boiler requirement . (vii) The front door shall be openable lined with high grade insulation and refractory (viii) High efficient, low noise imported Monoblock burner (Benton/Rello) (ix)The boiler shall be insulated with 50mm thick resin bonded fibre glass wool and cladded with 22 gauge GI sheet (epoxy pointed) or any other thermal insulation as per OEM design. (x) Pre wired control panel (made from 18 gauge CRC sheet ) Main incomer, MCB in/out temperature controller (digital)fault indicating light for water high temp, burner trip, flue temp, with alarm, hour meter for maint schedule etc. (xi) 1 set of oil piping from unit to burner . (xii) It includes suitable concrete foundation for Boiler . (C) Flue Gas Chimney:- Supply, installation of mild steel flue gas chimney ( suitable for emissiono as per boiler capacity made out of 3 mm thick mild steel sheet, minimum 3 mtr above the highest point of plant room as per manufacturer recommendations which ever is higher including connection to each boiler. Note : - (i)The complete design of CHS system shall be got vetted from IIT/NIT and complete design details including connected drawings all as specified in PS shall be submitted to GE for approval before starting the work. (a) The item shall be complete with the mounting/fixing arrangement all as specified by the boiler manufacturer including the dia of the exhaust flue Gas chimney as per the design and specification of the boiler installed 01 Nos.(b) The hot water generator shall be connected to the chimney. (c) The portion of chimney inside the building shall be insulated with Fiber glass insulation wool of density 24 Kg/Cum.The item shall be complete with mounting and fixing arrangement with necessary PCC work complete all as specified and directed. Qty -01 No
Day Oil Storage Tank Supply , Installation, testing and commissiong of HSD oil day storage tank rectangular mild steel(IS2062)/or relevant IS Code construction with capacity of 500 Ltrs complete with inlet, outlet, over flow drain and vent with flame arrestor. tank shall be made out of 4mm thick mild steel sheet and will be provided with supports made out of 50mm Dia medium grade pipe to keep tank base at minimum 2500mm above finished floor level. The tank shall be provided with level switches for on - off operation of transfer pump. Extra high level and extra low level alarm shall be provided along with gauge indicator duly calibrated. Tank and structure shall be painted with synthetic enamel paint oof approved colour over one coat of primer complete all as specified and directed by Engr in Charge
Thermic Fluid (Glycol) Makeup Tank Supply and installation of 500 litre capacity MS tank made out of 5 mm thick mild steel cylindrical/ rectangular with removable lid, in/out/drain/overflows system mounting arrangement making connections etc complete all as specified and directed.
Transfer Gear Oil Pump Fuel (Self Priming). Supply installation testing and commissioning of self priming rotary gear transfer pumps of capacity not less than 15 LPM at 25 Mtrs head for Kerosene or HSD oil complete with base mounting frame. PCC Foundation including holding down bolts , coupling guard and TEFC flame proof motor of suitable capacity and other accessories i.e (for one working and one standby) required for commissioning complete all as specified and directed.
Glycol Based Water Circulation Pump For Boilers:- Supply, installing , testing and commissioning of pumping system consisting of horizontal suction and delivery pump sets having stainless steel impellers capable of delivering not less than 15 LPS of thermic/ethylene glycol water against 25 meter head at outlet and complete as per specification. The system shall comprise of the following. Centrifugal pumps with minimum 75% efficiency not less than 30 LPS delivery at 25 mtr head suitable for parallel operation speed 1500 RPM including prime mover squirrel cage induction motor with TEFC enclosure and suitable power to drive the pump efficiently with class F insulation , 1500 RPM synchronous speed, operating on 415 +10% volts, 3 Phase , 50 HZ AC supply. (01 working +01 Standby) Note: (i) Insulation of suitable thickness duly cladded by aluminium sheets off 0.5mm thickness and properly clamped to pumped as per specifications required-01 Lot (ii) Mounting frame with antivibration pads for 2 Nos Pumpseets-01 Lot (ii) RCC cement concrete foundation for the pumping unit ass per OEM .
HSD Oil Piping System. Supply, installation, testing and commissioning of MS pipe heavy duty for HSD lines confirming to IS 1239 (part-I) 2001 or relevant IS including clamps, bends, reducers, flanges, nuts, bolts etc. complete with all respects of 32mm NB
Supply, installation, testing and commissioning of MS pipe heavy duty for HSD lines confirming to IS 1239 (part-I) 2001 or relevant IS including clamps, bends, reducers, flanges, nuts, bolts etc. complete with all respects of 25mm NB
Supply, installation, testing and commissioning of Brass ball valves 32 mm dia
Supply, installation, testing and commissioning of Brass ball valves 25 mm dia
Supply, installation, testing and commissioning of Y Strainer made of CI size 25 mm dia
Duct Insulation M & L for duct insulation with resin bonded fibre glass wool roll of density 24 Kg /Cum, 50 mm thick, with factory laminated aluminium vapour barrier , Thickness of insulation as specified and including the following :- (a) M &L for cleaning the surface (to be insulated) by scrapping carefully with wire brush etc, to make the surface completely free of milliscale, dirt, dust , grease and other foreign materials , taking special care so that all duct joints are sealed against any leakge. (b) M & L for applying rubber based adhesive CPRX compound. (c) M&L for sealing of all longitudinal joints and circular overlaps with and including aluminium foil tape 50 mm wide , to make the insulation leakproof. (d) M &L for securing the insulation with and including mechanically fatened nylon/steel straps of size 12mm/50mm at maximum ntervals of 1.2 mtr
Supply Air Grilles/ Diffusers Supply, installation, testing and balancing of powder coated Extruded Aluminium supply air Grilles/Diffusers with volume control dampers in accordance with the approved shop drawings and specifications. Note : The quantities of ducts specified are tentative and can vary accoring to the duct layout submitted and approved .The contractor shall have no claim in this regard.
Fresh Air Intake/Exhaust Air Louvers Supply, installation, testing and balancing of Powder coated/Anodized extruded aluminium construction inlet air louvers with bird screen and volume damper for fresh air as per specifications and approved drawings. Note : The quantities of ducts specified are tentative and can vary accoring to the duct layout submitted and approved .The contractor shall have no claim in this regard.
Fire Dampers Supply, fixing, testing and commissioning of fire dampers in supply air ducts / main branch and return air path as & where required of required sizes including control wiring. The spring return action shall be built mechanism and not externally mounted. Note : The quantities of ducts specified are tentative and can vary accoring to the duct layout submitted and approved .The contractor shall have no claim in this regard.
Air Handling Unit Supply, installation, testing and commissioning of factory built double skin floor mounted outdoor type Air Handling Unit/Air washer with 6 Row deep coil of nominal unit of capacity having range of operation 750 to 2500 CFM made of 25mm thick panels consisting og G.I casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethene foam (PUF) insulation factoryinjected between them by injection moulding machine complete with blower suitable for static pressure as detailed below.Humidifier for maintaining the desired relative humidity of heating space cooling coil section with mechanically bonded aluminium finned copper tubes (tube thickness not less than 0.5mm) cooling coil, filter section with pre filter 90% efficiency and down to 10micron, direct drive package with flame proof TEFC variable frequency drive motor(VFD) suitable for 415+10% volts, 50H , 3Phase, AC supply, drain connections with stainless steel drain pan duly insulated and necessary vibration isolation arrangement etc complete as per specifications and drawings.
Supply, fixing, testing and commissioning of HI wall split units indoor/otdoor complete with cordless remote control unit and with cooling and heating function of capacity 1.5 TR,BEE 5 Star rated all as specified and directed.
Supply, fixing, testing and commissioning of HI wall split units indoor/otdoor complete with cordless remote control unit and with cooling and heating function of capacity 2.0 TR,BEE 5 Star rated all as specified and directed.
M&L for Pre-insulated MS Pipe of size 50mm, Class 'C' having thickness of PUF insulation 36mm of density 36 Kg/Cum and 26gauge GI cladding complete suitable for above ground as per sizes all as specified and directed.
Supply, installation, testing and commissioning of Butterfly Valve PN 16 size 50 mm dia
Supply, installation, testing and commissioning of 50mm dia. Y - STRAINER for hot water circulation
Supply, installation, testing and commissioning of 50 mm Dia Non return valve
Supply, installation, testing and commissioning of Automatic Air Purge Valves of size minimum 20mm for hot water circulation header as specified and required by Engineer In Charge. Makes : Audco/ C&R/ Adverse/ Anergy
Supply, installation, testing and commissioning of Pressure gauge 4" Dial 0-21 Kg Rating complete all as specified and directed
Supply, installation, testing and commissioning of Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25 M deep below normal ground level) with top edge of plate not less than 1.5 M below normal ground level, connecting to the Galvanised iron earth strip 32x6mm size by means of bolts, nuts, check nuts and washers of galvanised iron and earth strip protected by provision of GI light grade pipe 40mm bore including provision of concrete pit in PCC (I:2:4) type B-1 using 20mm graded stone aggregated with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 Kg/Sqm) and frame of angle iron 40x40x6mm with lugs 02 Nos and handle of 6mm Dia MS bar made to shape, GI light grade 20mm bore pipe for watering, perforated at bottom and connecting to earth test point all as specified
Excavation in trenches n.exc. 1.5 mtr wide and n.exc 1.5 mtr deep for foundations of poles/stays/cable etc not exc 10 Sqm area on plan and getting out in Hard/Dense soil complete all as specifed and as directed by Engineer-in-Charge.
Returning filling in including spreading levelling, watering and well ramming in layer each not exc. 25 cm thick in a soft/loose soil complete all as specified and directed by Enginer-in-Charge.
Removing surplus soil to a distance not exc. 50 mtr and depositing where directed at a level n.exc. 1.5 mtr above the starting point complete all as specified and directed by Engr-in-Charge.
M&L for PCC cable cover Class LV, Type I, flat, size 250 mm x 150mm x 40mm laid Flat in trenches over the cable with length 250mm perpendicular to the direction of cable, adjacent/ abutting each other complete all as specified and directed. Note:-Excavation and earth work to be measured and paid for separately
M&L Sand cushioning to protection of underground cables, laid 8 Cm before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cm thick, complete all as specified and directed by Engineer-In-Charge. Note: Punned thickness shall be measured.
Supply, installation testing and commissioning of complete cable work using XLPE insulated PVC sheathed steel tape/ wire armoured underground copper conductor cables of following sizes for electric supply from main panel in AC plant room to various loads including Supplying and making end termination with brass double compression glands and aluminium lugs including interconnections from starters to motors on existing cable trays/supports as required as per specifications. 4 core x 4 Sqmm -Copper armoured cable ( ISI marked)
Fire Alarm System M&L for Fire alarm control panel complying with BS EN 54 Single loop panel of capacity from 99 detectors & 99 modules upto 200 detector and modules with standby power backup complete all as specified and directed.
M&L for Detectors Complying with and type certified to EN-45 Addressable type multisensor detector with heat and smoke combination complete all as specified and directed .
M&L for Addressable manual call point resettable type complete all as specified and directed.
M&L Addressable electronic sounder cum strobe complete all as specified and directed.
Supply,Fixing and testing PVC insulated FRLS copper conductor cable twin core 1.5 sqmm armoured 1100 volts including GI saddle with nuts and screw complete all as specified and directed.
M &L Point wiring complete with 1100 volts grade for 3/5 pin 15Amp socket outlet independent with PVC unsheathed, multistrand copper conductor of 2.5 Sqmm and continuous PVC insulated and unsheathed 2.5 Sqmm copper conductor cable multistrand as earth wire complete all as specified and directed.
S & F Switch socket combination of 6 and 15 A flush type , one way ISI marked complete all as specified and directed.
Fire Alarm Sounders / Sirens Electronic type horizontal single stage continous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound output variation of +5 DB 1500 mtrs range complete all as specified and directed.
Hard Standing Surface excavtion not exc. 30 cm deep and averaging 15cm deep and getting out hard/dense soil, complete all as specified and directed by Engr in charge.
M&L for 100 mm PCC 1:4:8: type D2 (using 40 mm graded aggregate) in floors as sub base complete all as specified and directed by Engr in charge.
Providing and laying 80mm thick factory made chamfered edge cement concrete paver block of M-30 grade with approved colour, design & pattern as in footpath, parks, lawns, drive ways or light traffic parking etc., of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50mm thick compacted bed of coarse sand, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with fine sand and cutting of paver block as per required size and pattern, finishing and sweeping extra sand; complete all as specified and directed by Engr in charge.
M&L for PCC B1 1:2:4 (20 mm graded aggregate) in lintels upto 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded or chamfered angles and throating, sides of interlocking block, filleting etc in any position Complete all as specified and as directed by Engr-in-Charge.
Removing excavated material n. exc 50m and depositing where directed at a level n. exc. 1.5m above the starting point complete all as specified and directed by Engr in charge.
External Water Supply Supply and Laying 3 Layer PP-R (Poly- propllene randomco polymer) pipes SDR 7.4 (PN-16) UV stabilized and anti microbial fusion welded having thermal stability for hot & cold water supply including all PP-R plan & brass threaded polyproplene random fitting s fixed complete to walls , ceiling or in floors etc of size 32 mmdia complete all as specified and directed
Supply and fix PPR Gate Valves (brass Insert) of 32 MM bore.
Drilling and tapping GI/PPR water mains (in position) the existing pipe of16 mm to 40mm for branch connections including inserting tee of size50x50x25mm or as per site conditions complete all as directed by Engr in charge. Note Excavation , returning filling are deemed to be be included in item rate
Excavation in trenches n.exc. 1.5 mtr wide and n.exc 1.5 mtr deep for foundations of poles/stays/cable etc not exc 10 Sqm area on plan and getting out in Hard/Dense soil complete all as specifed and as directed by Engineer-in-Charge.
Returning filling in including spreading levelling, watering and well ramming in layer each not exc. 25 cm thick in a soft/loose soil complete all as specified and directed by Enginer-in-Charge
Removing excavated material not exc. 50m and depositing where directed at a level n exc. 1.5m above the starting point all as specified and directed by Engineer-in-charge.
External Electrical Supply Supply, installation, tesing and commissioning of Diesel Engine Driven Genrating set of capacity 50KVA including but not limited to: Continuous net rating at 0.8 PF, 415V, 3 phase, 50Hz at site altitude 3048m AMSL and ambient 50˚ C and extreme climate (-20˚ C) , CPCB-IV+ compliant norms (MoEF &CC Gazette Notification effective 01 July 2023), self contained , skid mounted type with radiator cooling, control panel, fuel system, acoustic enclosure and all standard accessories, Noise standard ≤ 75dB (A) at1m, but must be certified for CPCB-IV+ compliance by OEM and Type approval & conformity of production (COP) certificate and derating factor certificate from OEM mandatory and must comply with real time emission monitoring provisions complete all as specified and directed comprising the following (a) Diesel Engine : The Diesel engine shall be of four stroke cycle multi cylinder, direct injection water cooled,turbo charged , air to air aftercooling and optimised turbo charger for increased altitude capablities, developing suitable BHP@1500RPM under tropical condition 3048meter at MSL of BS 5514/ISO3046 with an over load capacity 110% for one hour in any specified 12 hours of continuous operation. The engine shall confirm to IS: 10000/10002/ IS 13364/IS 1460/ IS 13656 /BS:649/ BS 5514 and CPCB -IV+ emission limits as per MoEF & CC Notification GSR 804(E) and subsequent amendments. The engine shall have following accessories :-
(b) Enginr Protector (i) High coolant temperature warning and trip (ii) Low lubricating oil pressure warning and trip, (iii) Low coolant level warning and trip, (iv) Fail to crack trip (v) Over crack trip (vi) High and low battery voltage (vii) Clogged filter warning (viii) Lack of fuel (ix) High canopy temperature (x) Set fail to start after successful three consecutive start attempts (xi) Electronic ECU with CPCB-IV+ diagnostic features for emissions and engine health monitoring (c) Governer :- The Governer shall be of electronic type suitable for monitoring constant engine speed within the specified limits for parallel and auto load sharing operation shall comply with ISO 3046-IV governing class G2 /better. (d) Exhaust :- The exhaust piping system shall be supplied with a hosptial grade silencer and catalytic converter suitably optimised to meet stingent noise emission standards laid down by CPCB-IV+ emission compliant with built in catalytic coverter(DOC/DPF/SCR as per OEM design). The exhaust piping and the silencer shall be wrapped with rock wool and/or calcium silicate. The outside shall be neatly wrapped with aluminium cladding. The exhaust line shall be extended beyond the height of utility building roof as required by pollution control norms . Suitable supporting structure for installation shall be provided. Emission certificate from CPCB approved agency to be submitted at commissioning stage. (e) Hot air exhaust (Radiator cooling ):- As per OEM recommondation if sufficient exhaust for radiator is not available the contractor has to provide GI duct for hot air exhaust from DG set up to designed place of duct oulet. The duct shall be made of 14 gauge thick GI sheet including necessary civil work.Tropicalized radiator suitable for ambient up to 50˚ C, at altitude 100m;derating factor to be declared by OEM.
(f) Fuel Tank :- Inbuilt/ internal bottom mounted (within-in base frame) Diesel tank of suitable capacity with mounting brackets complete with fuel inlet,air vent drain plug, level indicator, internal connection pipes from tank to diesel generator as required, Suitable barrier shall be provided between Diesel tank and engine. The fuel tank shall be fabricated as per tropical conditons at 3048m above MSL with approx capacity or designed capacity shall be suitable for 8 hours full load condition or 14 hours of capacity of 75% load. In case the in built base frame tank is not capable to hold POL for 8 hours continuous opearation, contractor shall provide additional tank made of MS sheet capacity seperately as per manufacturer recommondations confirming to PESO norms & safety rules; return fuel line with seperator. (g) Starting system :- The engine starting shall be by means of totally enclosed axial type electric starter suitable for 12/24V volts DC starting comprising of starter motor, voltage regulator and arrangement for initial excitation complete with suitable number of batteries as per OEM specifications, sealed maintenance free batteries lead acid type confirming to IS 15549 (SMF/Lead acid) suitable for High altitude 3048m from MSL. The batteries shall be supplied with a suitable floor mounted MS stand treated with seven treatemnt, two coats of red oxide primer and acid resistant paint with wooden base, adaptor box etc with copper conductors battery leads of required length and socket / clamps. (h) Alternator :- (i) 100KVA 3 phase 0.8PF, 415V, 4 wire 1500 RPM self excited and self regulated through electronic AVR confirming to IS:4722/BS: 2613 suitable for 3048m above MSL with brushless exciter housed in screen protected drip proof enclosure. The alternator shall be confirming to IS: 13364 Part-II & IS 15999 part-I /IEC 60034 Part-I and CPCB-IV+ requires low THD (<3%) capable of delivering rated output at rated power factor 0.8 with a terminal volatage differing from the rated value by not more than +/- 5%. (ii) Frequency differing from the rated value by not more than +/- 0.5%. (iii) short circuit capacity of 300% for 10sec. (iv) Over load capacity of 110% for one hour. The insulation class for the alternator shall be H class. The temperature rise shall be limited to class B and ingresses enclosure protection shall be IP23 or better. The output terminals of each alternator shall be connected to an MCCB of suitble capacity microprocessor based, adjustible type through a cable system. The control panel shall be housed inside the acquostic enclosure.(j) Alternator protection :- Alternator protections to comply with IEC 60255 standards and should have following protections- (i) Over and under voltage (ii) under and over frequency waring and trip (iii) Loss of excitation (iv) Over current and Earth fault and short circuit protection (v) Unbalanced loads (vi) Restricted Earth fault protection (vii) Differencial protection (vii) Diode Failure.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70Sqmm x 3.5Core and as directed by Engr in charge
Supply, installation, commissioning and testing of factory made, CPRI approved LT panel indoor type made out of CRCA sheet 2.10 mm thick, frame factory fabricated with front and back openable double door with locking arrangement, with MS angle section 50x50x6mm support, duly powder coated having thickness not less than 100 microns provided suitable gasket to make it dust and vermin proof, suitable for 3 Phase 4 wire, 415 Volts, 50 Hz, AC supply system, floor mounted and grounting the legs of panel in PCC foundation 1:4:8 complete as all directed suitable for and including the following :- INCOMERS: (a) Bus Bar TPN Copper bus bars of minimum 150 A capacity (b) Change over switch 100 Amps, 415 volts, 4 pole (on load).=01 (c) MCCB 100 Amps, 415 Volt, 36 KA, 4 Pole, thermal magnetic release - 01 No for incoming (Extended Rotary Operating Handle, Phase Spreader links and Phase barriers) (d) Digital Volt, Amp meter, Power factor meter and Frequency meter-01 Nos Each OUTGOINGS: (a) MCCB 20 Amp, (b) MCCB 10 Amp, 16KA, TPN-02 Nos for Boiler (c) MCB 6Amp, 10KA, TPN with Ammeter- 04 Nos for Diesel Pump & Boiler Pump (d) MCB 6Amp, 10KA, TPN with Ammeter- 02 Nos for Chilled water pump & Condenser water recirculating pump-02 (d) DOL Starter for Diesel Pump & Boiler Pump- 04 Nos (e) DOL Starter for CWP & CWRP- 04 Nos (f) MCB TPN 20 16KA, TPN-01 Nos for Bldg Load (g) MCB SP-10 Amp for Spare (d) Digital Volt and Amp meter-01 Nos each (e) RYB Indicator-03 Nos (f) Suitable Contactor, relay & circuit protection device.
Excavation in trenches n.exc. 1.5 mtr wide and n.exc 1.5 mtr deep for foundations of poles/stays/cable etc not exc 10 Sqm area on plan and getting out in Hard/Dense soil complete all as specifed and as directed by Engineer-in-Charge.
Returning filling in including spreading levelling, watering and well ramming in layer each not exc. 25 cm thick in a soft/loose soil complete all as specified and directed by Enginer-in-Charge.
Removing surplus soil to a distance not exc. 50 mtr and depositing where directed at a level n.exc. 1.5 mtr above the starting point complete all as specified and directed by Engr-in-Charge.
M&L for PCC cable cover Class LV, Type I, flat, size 250 mm x 150mm x 40mm laid Flat in trenches over the cable with length 250mm perpendicular to the direction of cable, adjacent/ abutting each other complete all as specified and directed. Note:-Excavation and earth work to be measured and paid for separately
M&L Sand cushioning to protection of underground cables, laid 8 Cm before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cm thick, complete all as specified and directed by Engineer-In-Charge. Note: Punned thickness shall be measured.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16Sqmm x 4Core and as directed by Engr-in-Charge
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10Sqmm x 4Core and as directed by Engr-in-Charge
Supply, installation, testing and commissioning of Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25 M deep below normal ground level) with top edge of plate not less than 1.5 M below normal ground level, connecting to the Galvanised iron earth strip 32x6mm size by means of bolts, nuts, check nuts and washers of galvanised iron and earth strip protected by provision of GI light grade pipe 40mm bore including provision of concrete pit in PCC (I:2:4) type B-1 using 20mm graded stone aggregated with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 Kg/Sqm) and frame of angle iron 40x40x6mm with lugs 02 Nos and handle of 6mm Dia MS bar made to shape, GI light grade 20mm bore pipe for watering, perforated at bottom and connecting to earth test point all as specified
Supply & fixing of 32mmx6mm GI strip on surface or in recesses for earth connections etc complete as required.
Sewage Disposal Excavating in trenches, n exc 1.5m wide and n exc 1.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc n exc 10 sqm on plan and n exc 1.5m in depth and getting out hard/dense soil soil all as specified and as directed.
Returning, filling including spreading, watering and well ramming in layers n.exc 25 CM in hard/dense soil all as specified and as directed.
Removing excavated material to a distance exc 250 mtr but not exc 500 mtr depositing where directed all as specified and as directed.
M&L cement concrete 1:4:8 type D2 using 40mm graded stone aggregate for foundation of manholes all as specified and as directed.
M&L for Pre-cast cement concrete block masonry with solid blocks, Type C1 1:3:6 (using 20 mm graded aggregate) exc. 10 cm in width and setting in cement mortar 1:6 complete all as specified and directed.
M&L plastering 15mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:4 mixed with water proofing compound finished even and smooth without using extra cement all as specified and directed.
Supply only Integral waterproofing compound all as specified and directed.
M&L cement concrete 1:4:8 type D2 using 40mm graded stone aggregate to bed concrete to drain pipes including packing under and haunching against the sides of pipe after they are laid and tested for 150mm dia pipe complete all as specified & directed.
Material & labour for 150 mm dia salt glazed stone ware (SGSW) drain pipes Grade A laid in any leangth and jointed with cement concrete 1:1 laid in trenches and tested complete all as specified & directed.
M&L cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate as in benching including necessary form work all as directed and specified.
Extra for forming fair finished drain or channel 30cm inner girth in cement concrete using extra cement including forms moulds mitred/stopped ends etc all as specified and directed.
M&L for precast RCC 1:2:4 type B1 using 20mm graded stone aggregate in cover slabs including necessary form work etc for manholes covers set in CM 1:4 (reinforcement measured seperately)
M&L for steel reinf TMT bars 10 mm dia and over cut to length and bent to shape required including cranking, bending spirally for hoping for columns, hooking end and binding with mild steel wire (annealed) not less than 0.9mm dia or securing with clips all as specified and directed.
Supply and instaliation of Polythehe (LLDPE Underground septic tank) of capacity 1000 Ltr (CCST-100-01) of Roto moulding grade conforming to IS 10146:2003 and Relaince 'O' 35042 grade MFI : 2.0 to 6.0 gm/10 minutes and denisity 932 to 943 Kg/Cum and carbon black master batch content 40% ± 1% and ash content 1% max. The avarage weight of tank shall be 40+ 1Kg and wall thickness 7.3mm. The tank shall be installed as per manufacturer instructions. Note :- The excavation in any type of soil, PCC 1:4:8 below foundation, vent shaft, connection etc complete all as required as per manufacturer's instructions will be included in cost of LumpSum quoted against this item and nothing extra shall be paid on this account and tenders are to quote their rates accordingly.
Material & labour for construction of soakage well excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats, size of soakage well 1.8m dia and 3.00m effective depth all as specified and as directed as per TD CE/AF/STD-15/2000 dated 05-01-2000.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.55 MB
BOQ_848604.xls
BOQ • 0.59 MB
TenderDocuments.pdf
Tender Documents • 1.45 MB
Download all tender documents and submit your bid