| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.4 LAccepted-AOC | L1 | Accepted-AOC RATES QUOTED ARE REASONABLE | |
| 2 | L2₹29.9 L+₹95,977 (3.32%)Rejected-Finance | L2 | Rejected-Finance RATES QUOTED ARE HIGHER THAN L1 | |
| 3 | L3₹30.9 L+₹2.0 L (6.81%)Rejected-Finance | L3 | Rejected-Finance RATES QUOTED ARE HIGHER THAN L1 | |
| 4 | L4₹31.1 L+₹2.2 L (7.60%)Rejected-Finance NH 17 MAIN ROAD BINAGA BAZAR KARWAR 581307 | KARWAR | UTTARA KANNADA | KARNATAKA | 581307 | L4 | Rejected-Finance RATES QUOTED ARE HIGHER THAN L1 | |
| 5 | L5₹29.9 L+₹95,977 (3.32%)Rejected-Finance | L5 | Rejected-Finance RATES QUOTED ARE HIGHER THAN L1 |
Tender Value
₹41.8 L
EMD Value
₹83,600
Closing Date
30 Nov 2022, 6:00 pmClosed
GE(SB) Karwar
GE(SB) Karwar
ADDITION , ALTERATION AND SPECIAL REPAIRS TO ELECTRICAL WIRING INCLUDING DEFECTIVE DBs, JUNCTION BOXES AND SUBMAIN WIRING IN A,D,E,F AND H BLOCKS AT INHS PATANJALI AND PROVISION OF TWO IN NUMBER 02 TON SPLIT AIRCONDITIONERS, TWO IN NUMBER 1.5 TON SPL
2022_MES_558978_1
8937/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE(SB) Karwar
As per tender
8 documents required · 8 mandatory
₹500
GE(SB) Karwar
₹83,600
Yes
20 Jan 2023
20 Oct 2022
2 Dec 2022
20 Oct 2022
30 Nov 2022
5 Nov 2022
20 Oct 2022 - 4 Nov 2022
Amount
Taking down DB's of any size including wooden boards etc complete and making good the disturbed surface of wall/floor etc all as specified and directed.
Taking down sub main wiring with/without PVC-conduits/casing fixed/concealed in walls and making good to the disturbed surfaces of walls/floors etc. of any size all as specified and directed.
Taking down MCBs of any size complete all as specified and directed.
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets light fittings etc. Removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surface of walls, floors, etc complete all as specified and directed.
M&L point wiring with 1.5 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable 1100 volts grade single core conforming to IS-694-1990 and including one run of continous earth wire to common earth and connected to earth with 1.5 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable for light/fan/bell, draw in existing conduit including CI/MS/PVC sunk boxes for mounting of modular switches, sockets, regulators etc with frame plate sheet cover of adequate size and making good disturbed surfaces with CM (1:4) to match with the existing surface complete all as specified and directed.
All as per item No.5 above but for multi 3 pin 5 amps safety shutter type socket outlet on same board.
All as per item No.5 above but for multi 3 pin 5 amps safety shutter type socket outlet on independent board.
M&L for point wiring with 2.5 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable 1100 volts grade single core conforming to IS-694-1990 and including one run of continous earth wire to common earth and connected to earth with 2.5 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable draw in existing conduit including CI/MS/ PVC sunk boxes for mounting of 3 pin modular switch socket outlet 15/20 Amp on independent board with frame plate sheet cover of adequate size and making good disturbed surfaces with CM (1:4) to match with the existing surface complete all as specified and directed.
M&L for point wiring with 4 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable 1100 volts grade single core conforming to IS-694-1990 and including one run of continous earth wire to common earth and connected to earth with 4 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable draw in existing conduit including CI/MS/ PVC sunk boxes for mounting of 3 pin modular switch socket outlet 15/20 Amp on independent board with frame plate sheet cover of adequate size and making good disturbed surfaces with CM (1:4) to match with the existing surface complete all as specified and directed by Engr-in-Charge. Make : Havells/Polycab/RR cables or equivalent.
S&F 5 pin switch socket combination outlet flush 5 pin type 5 amps independent board complete all as specified and directed.
S&F switch socket combination outlet 2 in 1, 3 pin, flush piano type universal 15 amps controlled by one switch on independent board complete all as specified and directed.
S & F switch piano type univeresal for light, fan points complete all as specified and directed.
Fixing only in repair switch piano type univeresal for light, fan points complete all as specified and directed.
Supply and fixing MCB Distribution board , 240 volts single pole and neutral double door, sheet steel, enclosure powder coated with 200Amps rated busbar with neutral link, 8 ways, SPN QVE Serics , fixed on wall duly grouted in solid block wall or on wooden board with electrical connection complete all as specified and directed.
Supply and fix MCB Distribution board , 415 volts Triple pole and neutral double door, sheet steel, enclosure powder coated with 200Amps rated busbar with neutral link, 4 ways, TPN QVE Serics , fixed on wall duly grouted in solid block wall or on wooden board with electrical connection complete all as specified and directed.
Supply and fix MCB Distribution board , 415 volts Triple pole and neutral double door, sheet steel, enclosure powder coated with 200Amps rated busbar with neutral link,6 ways, TPN QVE Serics , fixed on wall duly grouted in solid block wall or on wooden board with electrical connection complete all as specified and directed.
S&F MCB TPN 415V, 10KA, 'C' Series of 40 to 100 amp complete all as specified and directed.
S&F MCB SPN 240V, 10 KA, 'C' Series of 32 amps complete all as specified and directed.
S&F MCB SPN 240V, 10 KA, 'B' Series of 40 to 63 amps complete all as specified and directed.
S&F MCB TPN 240V, 10 KA, 'C' Series of 16 to 32 amps complete all as specified and directed.
S&F MCB SP 240V, 10 KA, 'C' Series and current carrying capacity in the MCB DB complete with connection, testing and commissioning of single pole size 06 to 32 amp complete all as specified and directed.
M&L for submain wiring with PVC insulated unsheathed copper conductor FRLS multi stranded, single core 1100V grade 2x4.0 sqmm complete drawn in and includindg medium grade rigid non-metallic PVC conduit and its accessories along with 1x2.5 sqmm PVC insulated unsheathed copper conductor multi sranded single core copper cable for continuous earth wire and duly connected to common earth all as specified and directed.
All as per item No.22 above but grade 4 x 6.0 sqmm and earth wire size of 2x 4.0 sqmm.
All as per item No.22 above but grade 4 x 10 sqmm and earth wire size of 2x 6.0 sqmm.
M&L for submain wiring with XLPE insulated amoured heavy electric cable with aluminium conductor 1100 volt grade 16 sqmm 4 core complete drawn in and includindg medium grade rigid non-metallic PVC conduit and its accessories complete all as specified and directed.
M&L for submain wiring with XLPE insulated amoured heavy electric cable with aluminium conductor 1100 volt grade 25 sqmm 4 core complete drawn in and includindg medium grade rigid non-metallic PVC conduit and its accessories complete all as specified and directed.
M&L for submain wiring with XLPE insulated amoured heavy electric cable with aluminium conductor 1100 volt grade 35 sqmm 3.5 core complete drawn in and includindg medium grade rigid non-metallic PVC conduit and its accessories all as specified and directed Engr in Charge.
M&L for point wiring with 4 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable 1100 volts grade single core conforming to IS-694-1990 and including one run of continous earth wire to common earth and connected to earth with 2.5 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable draw in PVC casing caping including CI/MS/ PVC sunk boxes for mounting of 3 pin switch socket outlet 15/20 Amp on independent board with frame plate sheet cover of adequate size and making good disturbed surfaces with CM (1:4) to match with the existing surface complete all as specified and directed by Engr-in-Charge.
M&L for point wiring with two single core 4 Sq.mm size multistranded copper conductor PVC insulated cables and one single core 2.5 Sq.mm size green colour PVC insulated,multistranded copper conductor PVC cable as earth continuity conductor,1100 volts grade, complete drawn in and including rigid PVC CONDUIT and conduit accessories,confirming to IS specifications,concealed in wall/ ceiling /trusses with suitable clamps, screws etc., including 1.22 mm thick MS terminal boxes with 3 mm thick plastic laminated sheet top cover fixed with cadmium plated iron screws for mounting socket outlet 15 Amps multi purpose on independent board ches, sockets, fan regulators etc.,including connecting up and testing, complete all as specified and as directed.
M&L for Sub main wiring with two runs of single core PVC FRLS insulated cable with copper conductor multistranded 1100 volts grade 4.0 sqmm through and including with suitable size of PVC casing caping and its accessories,on wall surface along with fixing arrangement etc including one runs of 2.5 sqmm PVC insulated multistranded copper earth contuinuity conductor and connected to common earth dolly complete all as specified.
Supply and fix switch socket combination 3 Pin 16 Amp, flush type, ISI marked, complete all as specified and directed.
Supply and fix single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB, 20 Amps complete with one all as specified and directed.
Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2.of capacity 1.5 TR complete all as specified & directed. Make: Blue star, Model IC518DBTU or equivalent in voltas / Daikin
Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2.of capacity 2 TR complete all as specified & directed. Make: Blue star, Model IC524DBTU or equivalent in voltas / Daikin
Supply & Fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 170 volts to 250 volts with out put voltage at stablized at 230 volts with accuracy of +/- 2.50% and of capacity 4 KVA complete all as specified and directed.
Supply & Fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 170 volts to 250 volts with out put voltage at stablized at 230 volts with accuracy of +/- 2.50% and of capacity 5 KVA complete all as specified and directed.
Supply and fix electric water heater, storage type steel body with copper inner tank and heating element upto 2 kW capacity 25 litre, BEE 5 star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece,inlet outlet pipes etc complete all as specified & directed. Make: Racold or equvalent make as specified.
Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) SP of 20 Amps current rating including with connection, testing and commissioning complete all as specified and directed.
Supply & Fix Bib taps, cast copper alloy with crutch or butterfly handle, screwed for iron pipe of 15 mm or for brass ferrule and fixed complete all as specified & directed.
Supply & Fix in galvanized iron tubing 15 mm dia medium grade ,ISI marked with all fitting and fixed on walls complete as specified.
M/S. B G GAONKAR
K.G.SHANKER
ANKIT SHIP REPAIRERS AND SUPPLIERS
BROTECH
N P ENGINEERINGS
SRI GURUPRASAD INFRATECH
HARSHITA MARINE SERVICES
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .