Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹79.6 LAdmitted-Finance | ₹79.6 L | L1 | Admitted-Finance |
| 2 | L2₹1.0 CrAdmitted-Finance FF AB32 DHANLAXMI COMLEX NEAR AIRPORT CIRCLE OPP SBI BANK AIRPORT KARELIBAUG VADODARA GUJARAT 390022 UDYAM GJ 24 0022566 24AACFW0734B1ZR R M MSME STATUS AS VERIFIED | VADODARA | GUJARAT | 390022 | ₹1.0 Cr | L2 | Admitted-Finance |
| 3 | L3₹1.2 CrAdmitted-Finance | ₹1.2 Cr | L3 | Admitted-Finance |
| 4 | L4₹1.3 CrAdmitted-Finance | ₹1.3 Cr | L4 | Admitted-Finance |
| 5 | L5₹1.3 CrAdmitted-Finance | ₹1.3 Cr | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | SARAF ELECTRICALS L3 | B.K. ELECTRICALS L4 | FLASHCUNSULTANT & CONTRACTOR L5 | TRINITY ENGINEERS L1 | WISDOM TECHNO SOLUTIONS L2 |
|---|---|---|---|---|---|---|---|---|
| 1.00Design, manufacture, testing at works, supply at site, installation, testing and commissioning of 415V Power distribution panel having enclosure of 2 mm thick CRCA MS sheet duly powder coated,double door sutiable for outdoor duty, 2 mm thick CRCA MS sheet duly powder canopy conforming to relevant IS/IEC and as per tender specifications. Panels shall be provided with Moulded Case Circuit Breakers (MCCBs) and Miniature Circuit Breakers (MCBs) as per given feeders configuration. TheMCCBs shall be provided with advanced microprocessor based protection releases. The Bus bar (TPN) shall made of aluminium conductor of uniform cross section throughout the length of the panel and designed to withstand short circuit current. The MCCB switchgears shall have adjustable time and over current (minimum 40% - 100%), short circuit, earth fault (minimum 20%) settings. The feeders configuration shall be under. | ||||||||
| 1.10 | Power distribution panel No. 1: The incomer and outgoing feeders configurations shall be as under.
Incomer: 4Pole, 800A, AC-23A, mannual onload transfer switch, along with 3 Pole 800 A MCCB (Ics ≥ 50 kA) -- 1 set.
Outgoings: (1) 630 A TP MCCBs (Ics ≥ 50 kA) - 1 No.
(2) 250 A TP MCCBs (Ics ≥ 50 kA) - 4 Nos.
(3) 160 A TP MCCBs (Ics ≥ 50 kA) - 3 Nos.
(4) 100 A TP MCCBs (Ics ≥ 50 kA) - 2 Nos. | 1 | No. | 8,94,500 ₹8.9 L | 6,42,755 ₹6.4 L | 11,00,000 ₹11 L | 5,72,994 ₹5.7 L | 8,98,750 ₹9.0 L |
| 1.20 | Power distribution panel No. 2: The incomer and outgoing feeders configurations shall be as under.
Incomer: 3 Pole 250 A MCCB (Ics ≥ 50 kA) -- 01 No.
Outgoings: 160 A TP MCCBs (Ics ≥ 50 kA) - 2 Nos.
One of the above 160 A MCCB shall be feeding to following MCB outgoing feeders:
(1) C-Curve 25 A SP MCB (Ics ≥ 10 kA) - 15 Nos.
(2) C-Curve 50 A SP MCB (Ics ≥ 10 kA) - 9 Nos.
(3) C-Curve 63 A SP MCB (Ics ≥ 10 kA) - 6 Nos.
(4) C-Curve 63 A 3P MCB (Ics ≥ 10 kA) - 1 Nos.
(5)C-Curve 32 A 3P MCB (Ics ≥ 10 kA) - 1 Nos. | 1 | No. | 3,17,000 ₹3.2 L | 3,25,680 ₹3.3 L | 3,10,000 ₹3.1 L | 2,39,290 ₹2.4 L | 4,15,921 ₹4.2 L |
| 1.30 | Power distribution panel No. 3 : The incomer and outgoing feeders configurations shall be as under.
Incomer: 3 Pole 630 A MCCB (Ics ≥ 50 kA) -- 01 No.
Outgoings: (1) 400 A TP MCCBs (Ics ≥ 50 kA) - 2 Nos.
(2) 250 A TP MCCBs (Ics ≥ 50 kA) - 2 Nos.
(3) 160 A TP MCCBs (Ics ≥ 50 kA) - 3 Nos.
(4)100A TP MCCBs (Ics ≥ 50 kA) - 4 Nos. | 1 | No. | 7,00,500 ₹7.0 L | 8,75,265 ₹8.8 L | 10,70,000 ₹10.7 L | 4,50,534 ₹4.5 L | 8,74,718 ₹8.7 L |
| 1.40 | Power distribution panel No. 4: The incomer and outgoing feeders configurations shall be as under.
Incomer: 3 Pole 400 A MCCB (Ics ≥ 50 kA) -- 01 No.
Outgoings: (1) 250 A TP MCCBs (Ics ≥ 50 kA) - 1 No
(2) 100A TP MCCBs (Ics ≥ 50 kA) - 2 Nos.
(3) 250 A TP MCCB (Ics ≥ 50 kA) - 1 No.
The above 250 A MCCB shall be feeding to following MCB outgoing feeders:
(a) C-Curve 63 A SP MCB (Ics ≥ 10 kA) - 18 Nos. | 1 | No. | 4,27,500 ₹4.3 L | 4,47,810 ₹4.5 L | 5,25,000 ₹5.3 L | 2,62,251 ₹2.6 L | 4,90,521 ₹4.9 L |
| 2.00Design, manufacture, testing at works, supply at site, installation, testing and commissioning of 415 V, Motor Control Centers (MCC)Panel having enclosure of 2 mm thick CRCA MS sheet duly powder coated, double door, outdoor duty,conforming to relevant IS/IEC and as per tender specifications. Panels shall be provided with Moulded Case Circuit Breakers (MCCBs), soft starter with Direct online(DOL) bypasss, Direct online starters, Star- Delta starters, current sensing type single phase preventer, Miniature Circuit Breakers (MCBs) as per given feeders configuration. All type of motor starters shall be Type-II co-ordinated as per OEM recommendation.TheMCCBs shall be provided with advanced microprocessor based protection releases. The Bus bar (TPN) shall made of aluminium conductor of uniform cross section throughout the length of the panel and designed to withstand short circuit current. The MCCB switchgears shall have adjustable time and over current (minimum 40% - 100%), short circuit, earth fault (minimum 20%) settings. The feeders configuration shall be under. | ||||||||
| 2.10 | MCC panel No. 1: The incomer and outgoing feeders configurations shall be as under.
Incomer: 3 Pole 250 A MCCB (Ics ≥ 50 kA) -- 01 No.
Outgoings:(1) 10 HP STAR -DELTA :- 2 Nos.
(2) 7.5 HP D.O.L. starter :-5 Nos.
(3) 5 HP D.O.L. starter :-4 Nos.
(4) 40 A TP MCCBs (Ics ≥ 50 kA) - 2 Nos. | 1 | No. | 7,37,500 ₹7.4 L | 7,46,350 ₹7.5 L | 5,88,000 ₹5.9 L | 5,36,671 ₹5.4 L | 6,56,022 ₹6.6 L |
| 2.20 | MCC panel No. 2: The incomer and outgoing feeders configurations shall be as under.
Incomer: 3 Pole 400 A MCCB (Ics ≥ 50 kA) -- 01 No.
Outgoings: (1) 40 HP Soft starter with DOL bypass:- 5 Nos.
(2) 100 A TP MCCBs (Ics ≥ 50 kA) - 3 Nos. | 2 | Nos. | 13,26,600 ₹26.5 L | 15,87,690 ₹31.8 L | 14,85,000 ₹29.7 L | 7,62,807 ₹15.3 L | 10,38,823 ₹20.8 L |
| 2.30 | MCC panel No. 3: The incomer and outgoing feeders configurations shall be as under.
Incomer: 3 Pole 160 A MCCB (Ics ≥ 50 kA) -- 01 No.
Outgoings:(1) 7.5 HP D.O.L. starter :-4 Nos.
(2) 5 HP D.O.L. starter :- 2 Nos.
(3) 40 A TP MCCBs (Ics ≥ 50 kA) - 3 Nos. | 1 | No. | 4,87,500 ₹4.9 L | 5,08,875 ₹5.1 L | 5,08,000 ₹5.1 L | 2,86,743 ₹2.9 L | 4,78,366 ₹4.8 L |
| 2.40 | MCC panel No. 4: The incomer and outgoing feeders configurations shall be as under.
Incomer: 3 Pole 400 A MCCB (Ics ≥ 50 kA) -- 01 No.
Outgoings:(1) 40 HP soft starter with DOL bypass :- 5 Nos.
(2) 250 A TP MCCBs (Ics ≥ 50 kA) - 1 No.
(3) 160 A TP MCCBs (Ics ≥ 50 kA) - 2 Nos.
(4)100 A TP MCCBs (Ics ≥ 50 kA) - 3 Nos.. | 1 | No. | 14,69,000 ₹14.7 L | 18,59,090 ₹18.6 L | 17,00,000 ₹17 L | 8,53,122 ₹8.5 L | 11,16,737 ₹11.2 L |
Tender Value
₹1.1 Cr
EMD Value
₹2.2 L
Closing Date
2 Dec 2025, 3:30 pmClosed
Chief Engineer, RRCAT, Indore
Office of Chief Engineer, RRCAT, Indore
Upgradation of Power control centers (PCC) and Motor control centers (MCC) at RRCAT, Indore
2025_RRCAT_885521_1
RRCAT/E/2025/15
Open Tender
Electrical Works
RRCAT
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹2.2 L
3 Mar 2026
14 Nov 2025
5 Dec 2025
16 Nov 2025
2 Dec 2025
16 Nov 2025
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Document
1.33 MB
Document
0.16 MB
Document
0.60 MB
Document
0.10 MB
Document
0.45 MB
Document
0.21 MB
Document
0.23 MB
Document
4.67 MB
Document
0.12 MB
Document
0.16 MB
Document
2.15 MB
Document
0.07 MB
Document
0.27 MB
Document
0.22 MB
Document
0.23 MB
Document
0.21 MB
BOQ
BOQ • 0.34 MB
Download all tender documents and submit your bid