Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹47.0 LAccepted-Finance | ₹47.0 L | L1 | Accepted-Finance Reasonable |
| 2 | L2₹49.2 L+₹2.2 L (4.73%)Accepted-Finance | ₹49.2 L+₹2.2 L (4.73%) | L2 | Accepted-Finance Reasonable |
| 3 | L3₹51.5 L+₹4.5 L (9.68%)Accepted-Finance | ₹51.5 L+₹4.5 L (9.68%) | L3 | Accepted-Finance Reasonable |
| Sl No | Description | Qty | Unit | JP Infratech H2 | Barraq Enterprises H1 | JASMEET SINGH H3 |
|---|---|---|---|---|---|---|
| 1.00 | 1 incomer + 3 outgoing set of 11 kV VCBs Panel Board (12 kV, VCB of 1250A, 26.3 kA for 3s withdrawable cassette type, IEC 62271-100:2012 of LK / Schneider / ABB / CG make) SCADA compatible with O/C, E/F numerical relays with mandatory - 8DOs & 8 DIs, inrush blocking feature, sensitive earth fault element, compliance with IEC61850 , electrical reset master trip relay, Mimic Diagram, Digital Voltmeter, Digital Ammeter, minimum 9 Annunciation Windows with annunciation relays, mandatorily without conventional 3-phase Tri-vector meters. | 2 | (1+3) Set | 21,70,000 ₹43,40,000 | 22,55,951 ₹45,11,902 | 21,38,500 ₹42,77,000 Lowest |
| 2.00 | DC Battery Bank 30 V,100 AH , of 15 No. cells of 2 V each, sealed maintenance free VRLA type, High impact Polyprophelene copolymer container, flame retardant. | 1 | Nos. | 1,20,000 ₹1,20,000 | 60,659.38 ₹60,659.38 | 60,000 ₹60,000 Lowest |
| 3.00 | 30 V, 40 Amp. Float-cum-Boost Battery Charger compatible for VRLA battery bank with full wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply as per technical specifications, approved drawings and scope of works. | 1 | Nos. | 75,000 ₹75,000 | 62,103.61 ₹62,103.61 Lowest | 1,00,000 ₹1,00,000 |
| 4.00 | 11 kV 3-Core XLPE 300 mm² armoured, FRLS | 80 | Mtr | 1,600 ₹1,28,000 | 3,076 ₹2,46,080 | 1,100 ₹88,000 Lowest |
| 5.00 | 11 kV Indoor Heat Shrinkable Cable Termination Kits | 2 | Set | 4,500 ₹9,000 | 4,332.81 ₹8,665.62 Lowest | 9,000 ₹18,000 |
| 6.00 | 11 kV Outdoor Heat Shrinkable Cable Termination Kits | 2 | Set | 4,500 ₹9,000 | 4,332.81 ₹8,665.62 Lowest | 9,000 ₹18,000 |
| 7.00 | 11 KV Isolator with Earthing Blade | 2 | Nos. | 39,000 ₹78,000 | 47,660 ₹95,320 | 19,000 ₹38,000 Lowest |
| 8.00 | 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suited for number of control panels, nos of VCB kiosk panel, having 20% spare outgoing feeders, mounting arrangements etc as per technical specifications, approved drawings and scope of works. ( All switchgear used shall be of LK/Schneider/ABB make) | 2 | No.s | 80,000 ₹1,60,000 | 79,046.96 ₹1,58,093.92 | 49,000 ₹98,000 Lowest |
Tender Value
₹56.3 L
EMD Value
₹1.1 L
Closing Date
10 Aug 2026, 4:00 pmClosed
Executive Engineer, STD-II, JPDCL, Jammu
Office of Executive Engineer, STD-II, JPDCL, Jammu
Installation of 2 no. VCB Panel at R/stn Boria
2026_PDD_316988_1
STD-II/Tenders/2026-27/14
Open Tender
Electrical Works
Turn-key
120 days
Boria
Please refer Tender documents.
4 documents required · 4 mandatory
₹1,000
Executive Engineer, STD-II, JPDCL, Jammu
₹1.1 L
5 Sept 2026
20 Jul 2026
12 Aug 2026
20 Jul 2026
10 Aug 2026
20 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | 1 incomer + 3 outgoing set of 11 kV VCBs Panel Board (12 kV, VCB of 1250A, 26.3 kA for 3s withdrawable cassette type, IEC 62271-100:2012 of LK / Schneider / ABB / CG make) SCADA compatible with O/C, E/F numerical relays with mandatory - 8DOs & 8 DIs, inrush blocking feature, sensitive earth fault element, compliance with IEC61850 , electrical reset master trip relay, Mimic Diagram, Digital Voltmeter, Digital Ammeter, minimum 9 Annunciation Windows with annunciation relays, mandatorily without conventional 3-phase Tri-vector meters. | 2 | (1+3) Set | - | - |
| 2 | DC Battery Bank 30 V,100 AH , of 15 No. cells of 2 V each, sealed maintenance free VRLA type, High impact Polyprophelene copolymer container, flame retardant. | 1 | Nos. | - | - |
| 3 | 30 V, 40 Amp. Float-cum-Boost Battery Charger compatible for VRLA battery bank with full wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply as per technical specifications, approved drawings and scope of works. | 1 | Nos. | - | - |
| 4 | 11 kV 3-Core XLPE 300 mm² armoured, FRLS | 80 | Mtr | - | - |
| 5 | 11 kV Indoor Heat Shrinkable Cable Termination Kits | 2 | Set | - | - |
| 6 | 11 kV Outdoor Heat Shrinkable Cable Termination Kits | 2 | Set | - | - |
| 7 | 11 KV Isolator with Earthing Blade | 2 | Nos. | - | - |
| 8 | 415 V, ACDB along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 200 Amps TPN switch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suited for number of control panels, nos of VCB kiosk panel, having 20% spare outgoing feeders, mounting arrangements etc as per technical specifications, approved drawings and scope of works. ( All switchgear used shall be of LK/Schneider/ABB make) | 2 | No.s | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.51 MB
SBDBoria.pdf
Tender Documents • 0.76 MB
BOQ_1036582.xls
BOQ • 0.38 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .