Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹9.6 LAccepted-AOC 268 KARGALI BAZAR BERMO BOKARO 829104 JHARKHAND | BOKARO | JHARKHAND | 829104 | L-1 | Accepted-AOC Deposited performance and additional performance security. | |
| 2 | Rejected-Technical 268 KARGALI BAZAR BERMO BOKARO 829104 JHARKHAND | BOKARO | JHARKHAND | 829104 | - | Rejected-Technical Not Evaluated | |
| 3 | Rejected-Technical 00 KIWADI SAFEDABAD BARABANKI BARABANKI UTTAR PRADESH 225001 | BARABANKI | UTTAR PRADESH | 225001 | - | Rejected-Technical Not Evaluated | |
| 4 | Rejected-Technical JANTA NAGAR PO BOKARO THERMAL DIST BOKARO JHARKHAND PIN 829107 | BOKARO | JHARKHAND | 829107 | - | Rejected-Technical Not Evaluated |
Tender Value
₹19.2 L
EMD Value
₹24,100
Closing Date
1 Oct 2024, 11:00 amClosed
SO(EnM), BnK
GM Office, BnK Area, Bermo, Bokaro, Jharkhand.
Supply and installation of Isolation transformer, SPD and lightening arrestor with insulated copper strip and earthing for different weighbridges at AKK OCP and Bokaro colliery under BnK Area
2024_CCL_317708_3
SO(EnM)/e-tender/24-25/16
Open Tender
Electrical and Maintenance Works
Item Rate
30 days
AKKOCP and Bokaro Colliery
As per NIT
2 documents required · 2 mandatory
₹24,100
11 Dec 2024
20 Sept 2024
3 Oct 2024
20 Sept 2024
1 Oct 2024
21 Sept 2024
20 Sept 2024 - 27 Sept 2024
Amount
Supply and Providing of SPD, LC30: for protection of load cells, Total Nos.04 for each weighbridge for load cells Pole 1P+N
Supply and Providing of SPD MA15: SPD on 230/440V AC side to protect the electronic weight indicator & computer. 01 Nos for each weighbridge, Rated voltage 230/440V, Pole 3P+N, Imax-20KA.
Supply and Providing of SPD CAT6 for protection of RS232 port between Digitizer & PC
Input Voltage-0-415-440VC(Isolation transformer), Shield1- Copper Shield between primary and each secondary with ground terminal. Output Voltage-0-230-250-415VAC, output current-3.5A, VA rating-7500VA, Shield2- Copper shield after the outer layer of secondary connected to transformer mounting, Winding Material-Copper, Dielectric test voltage between winding and shield- 10KV, Core material-CRNO stamping, Mounting-foot mount with L Clamp.
Earthing with copper earth plate 600mm x 600mm x 3mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7metre long etc with charcoal/ coke and salt as required.
Supply and laying 25mm x 5mm copper strip at 0.50 metre below ground as strip earth electrode including connection/terminating with G.I nut, bolt , spring, washer etc as required.(jointing shall be done by overlapping and with 02 set of G.I nut bolt & spring washer spaced at 50mm)
Supply installation of Lightning protection system ESE type as per DGMS (Tech) Cir. No. 07 dt. 27.10.2008 & 10 of 23.06.2020 Advanced Early Streamer Emission type Lightning Protection System The lightning protection system shall be advanced type which is designed to send upward streamer earlier than the other surrounding metallic points, attract lighting to a preferred point and safety convey the lighting energy to ground with a Predetermined route. Lighting Air terminal with Adaptor: Air terminal designed and tested to NFC17 AND UNE-21186, Air radius minimum 60 Mtrs with stainless steel design suitable for all weather conditions. Air terminal made of non-corrosive materials, utilize advance and sustainable technologies. Provide complete protection by capturing dangerous lighting discharges and safely channelling it to earth. Test certificate will be provide as per Standard NFC17 and UNE-21186 from NABL or internationally recognized laboratory Down Cable / Conductor: High Voltage Multi copper insulated cable of minimum 50sq.mm cross section for lighting current dissipation to the earthing system with necessary accessories, Down cable / conductor should be in single length approx 90 Mtr, From the Air terminal to the earthpit. Electronic Lightning Strike Counter - Lighting strike recorder counter shall be weather proof type it should have six digits event count. Should have capacity to count smallest strike, it should be a voltage sensing type
Supply and complete connecting re-wiring with 4 sqmm fire proof 1100 volt wire with all accessories like lugs, clips and washer etc and fixing with conduit pipe.
Total impact of GST for the purpose of CTC
Y K ENTERPRISES
M/S KUMAR ENTERPRISES
M/s Kiran Electrical works
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .