| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹54.3 LAccepted-AOC 1 2 GR FLOOR VITHALKUNJ NO 3 V P ROAD ANDHERI WEST MUMBAI 400 058 | MUMBAI SUBURBAN | MAHARASHTRA | 400058 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹65.5 L+₹8.7 L (15.3%)Rejected-Finance | L2 | Rejected-Finance Other than being lowest | |
| 3 | L3₹68.5 L+₹11.7 L (20.6%)Rejected-Finance 1202 SAI PROVISO DHNISHT PLOT NO 72 73 SECTOR 20 KOPARKHAIRANE NAVI MUMBAI | THANE | MAHARASHTRA | 400601 | L3 | Rejected-Finance Other than being lowest | |
| 4 | L4₹69.4 L+₹12.5 L (22.1%)Rejected-Finance PLOT NO 1134 1196 MORIVALI VILLAGE TAL AMBARNATH DIST THANE AMBERNATH 421505 | AMBERNATH | THANE | MAHARASHTRA | 421505 | L4 | Rejected-Finance Other than being lowest | |
| 5 | L5₹1.6 Cr+₹1.1 Cr (190.3%)Rejected-Finance | L5 | Rejected-Finance Other than being lowest |
Tender Value
Refer Docs
EMD Value
₹1.4 L
Closing Date
1 Mar 2022, 6:00 pmClosed
CWE (NW) Mumbai
Commander Works Engineer NW Dr Homi Bhabha Road Navy Nagar Colaba Mumbai 05
REPAIR MAINTENANCE OF CANVAS HOSE RUBBER HOSE NOZZLE FIRE ALARM SYSTEM AND CONNECTED ACCESSORIES AT OLD AND NEW NAVY NAGAR AREA JYESTA DHANISTA NOFRA AREA WNC O MESS AND ROBERT ROAD COMPLEX UNDER GE NW NAVY NAGAR COLABA MUMBAI
2022_MES_503724_1
8272/CWE(NW)MUMBAI/E8
Open Tender
Civil Works
Item Rate
330 days
GE (NW) NAVY NAGAR
Class C
7 documents required · 7 mandatory
₹1,000
Yes
GE (NW) Navy Nagar
₹1.4 L
Yes
31 Mar 2022
25 Jan 2022
3 Mar 2022
25 Jan 2022
1 Mar 2022
15 Feb 2022
25 Jan 2022 - 12 Feb 2022
Amount
Repair/Routine maintenance including carrying out daily check of fire alarm/fire fighting system complete with electronic control panel consisting of 16 zones in 08 (Eight) Buildings Dhanush, Vrishabh, Tula, Makar, Mesh, "G" block, 'H' block and Kumbh (G+14 floors) ie 15 stories including personnel to attend the fire alarm system faults, testing, checking and replacement of unserviceable components ie nuts, bolts, washers etc other than mentioned in schedule here-in after. The fire alarm system consisting the following :- (a) Indicator (b) Electronic hooter (c) Manual call point (d) Smoke detector (e) Heat detector (f) Electronic fire control panel (g) Main/Zone cards (h) Battery of Fire panel DC supply (J) All wiring and cable connections Note :- Contractor shall provide adequate skilled man power for testing of fire fighting system of buildings as per schedule to be issued by the user section. The cost of testing shall be deemed to be included in the item rate.
All as above item No 1 but 16 zones in 2 (Two) Buildings Jyesta & Dhanista (G+15 floors) ie 16 stories complete all as specified and directed.
All as per item No 1 above but 08 zones in 05 (Five) Buildings (G+6) G block, F1 block, AQ block, AR Block, CWE Complex (G+5) and 200 Sailors accn (G+6 floors) ie 07 stories complete all as specified and directed.
All as per item No 1 above but 20 zones in 02 (Two) Buildings i.e. Mulla Auditorium and SHO buildings (G+1 floors) ie 02 stories complete all as specified and directed.
All as per item No. 1 above but 16 zones in 02 (Two) Buildings Meena, Swati (G+13 floors) ie 13 stories complete all as specified and directed.
All as above item No 1 but 17 zones in 4 (Four) Buildings Kanya, Chitra, Anuradha & Alaknanda (G+13 floors) ie 15 stories and 01 (One) Buildings Archana (G+15 floors) complete all as specified and directed.
All as per item No 1 above but 15 zones in 04 (Four) Buildings Bharani, Saravana, Vidya & Vijaya (G+12 floors) ie 13 stories complete all as specified and directed.
All as per item No 1 above but 12 zones in 04 (Four) Buildings Revati, Rohini, Karthikeya & Gemini (G+9 floors) ie 10 stories complete all as specified and directed.
Repair/Routine maintenance including carrying out daily check of fire fighting system 09 zone complete 04 (Four) Buildings WNC Mess main bldg, Annex bldg, Hemadri and transist bldg (G+07 floors) ie 08 stories 04 (Four) Buildings Narmada, Tapti, Kaveri, Hoogly and Vishkarma bldg (G+06 floors) ie 07 stories including attending system faults, testing, checking including replacement of unserviceable components ie nuts, bolts, washers etc other than mentioned in schedule “A” here-in after complete all as specified and directed
Supply and replacement, installation, testing & commissioning of micro processor based 2 wire fault tolerant loop, required loop net workable type 2 loop (each loop accessing maximum 99 detectors and 99 modules) fire alarm/detection control panel. The panel shall be able to give location of all fire/fault signal with address. The panel shall have rectifier, loop cards, 80 character LCD unit to indicate Fire/Fault signal with address. The panel shall have a built in power supply and battery charger alongwith maintenance free 7.2 AH, 2x12 volt SMF lead acid batteries capable of running for a minimum of 48 hours with battery charger complete as required and as per specifications duly approved by EN 54 complete including of all 15 Amp power point connection from meter room to fire control panel all as specified and directed by Engr-in-Charge. Make :- Bosch/Honey well/Schneider
Supply & fix in repair detectors Complying with and type certified to EN - 45 Addressable type multisensor detector with heat and smoke combination complete all as specified and directed. Make :- Schneider / Honey Well / Bosch
Supply and fix Beam Master detector with Transmitter and receiver complete all as specified and directed. Make : Apollo/ Honey well/ System Sencor
Supply & fix in repair Maintenance free battery duly charged 12 V 7.2 AH complete all as specified and directed Make :- EXIDE / TATA Green / Amaron
Supply fix in replacement, Installation,Testing & Commissioning of Addressable electronic sounder cum strobe complete all as specified and directed. Make :- Schneider / Honey Well / Bosch
Supply,replacement, Installation,Testing & Commissioning of Addressable Type Manual Call Point with Mounting Base as required conforming (UL's Latest Edition Approved and NFPA compliant / VDS or LPCB tested and EN54 compliant) complete all as specified and directed. Make :- Schneider / Honey Well / Bosch
Supply and fixing in repair PVC insulated PVC sheathed armoured copper conductor cable of size 4Core x 1.5 Sqmm including fixing on walls with saddles complete all as specified and directed.
Supply, laying, jointing and testing in replacement of PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, conforming to IS 694 6 Core 0.5 sqmm including making necessary connection, with busbar/MCCB/DB's & testing complete all as specified and directed.
Material and labour for factory fabricated MS fire cabinet box as per Existing design made out flat CRCA of appropriate size and thickness 2 mm all as directed including and applying two coats of synthetic enamel paint over a coat of red oxide primer on panel fitted inside bldg on each floor by approved colour & fixed on wall with necessary nuts/bolts or welding to existing MS pipe by supporting angle complete all as specified & directed.
Supply & fix in repair rubber hose pipe 30 mtr,20mm dia plain 2 ply rayon confirming IS-12585 braided high pressure complete all as specified and directed. Make:-Minimax / Safex /DUNLOP
Supply & fix in repair canvas fire hose 63mm bore 15 m long confirming to IS 636-1988 having male/female brass coupling both end complete all as specified and directed. Make:-Minimax/Safex/DUNLOP
Supply & fix in repair Stainless steel Nozzle 25 mm bore suitable for 63mm dia canvas pipe complete all as specified and directed. Make:-Minimax/Safex/DUNLOP
Supply & fix in repair hose Reel drum suitable for 30 mtrs X 20 mm dia rubber hose pipe complete all as specified and directed. Make:-Minimax/Safex/DUNLOP / Jyothi
Supply & fix in repair 100 mm dia ERW Medium grade MS pipe confirming IS-1239 and applying two coats of synthetic enamel paint over a coat of red oxide primer to pipe including supporting, brackets welding, necessary PCC support as required at site complete all as specified and directed.
Supply & fix in repair 150 mm dia ERW Medium grade MS pipe confirming IS-1239 and applying two coats of synthetic enamel paint over a coat of red oxide primer to pipe including supporting, brackets welding, necessary PCC support as required at site complete all as specified and directed.
Supply & fix in repair gun metal Two way fire brigade inlet conection with adaptor of size 80 mm dia X 63 mm dia complete all as specified and directed. Make :- Minimax / Safex / DUNLOP
Supply & fix in repairs Branch pipe gun metal 63mm instantaneous inlet, made threaded outlet, 15mm bore nozzle complete all as specified and directed. Make :- Minimax / Safex / DUNLOP
Supply & fix in repair twin outlet hydrant valve 100mm having 65mm outlet with lock pin wheel complete all as specified and directed. Make:-Minimax/Safex/DUNLOP
Supply & fix in repair single outlet hydrant valve 100mm having 65mm outlet with lock pin wheel complete all as specified and directed. Make:-Minimax/Safex/DUNLOP
Supply & fix in repair sluice valve 150mm size both ends flayed with high tensile stainless steel spindle, I body as per IS-14846, ISI Marked,PN-1.6 including all joints with rubber or fibre board, nuts, bolts, washers complete all as specified and directed.
Supply & fix in repair Sluice Valve 100mm size both ends flayed with high tensile brass spindle body, as per IS-14846, ISI Marked, PN 1.6 including all joints with rubber or fibre board, nuts, bolts, washers complete all as specified and directed.
Supply and fix in repair Foot valve 150 mm dia ball type10/15Kg/sqcm (MODEL B-5) of (ISI marked) in position at location including Material and labour for making flanged joints and repair and making good to existing PCC surface, new nuts, bolts and washers of suitable size complete all as specified and directed.
M& L for Disconnecting motor from pump of any Make, model and remove Bearing using bearing puller gear and fix new bearings at DE /NDE including necessary greasing ,check for proper shaft alignments such that no vibration produce during opertion of following capacity Motors.
(a) Pump coupled with 75 HP motor (Bearing size 6313-ZZ & 6312ZZ Make SFC/NBC/SKF)
(b) Pump coupled with 60 HP motor (Bearing size 6312 ZZ & 6311ZZ Make SFC/NBC/SKF)
(c) Pump coupled with up to 15 HP motor (Bearing size 6307 ZZ & 6309ZZ Make SFC/NBC/SKF)
Supply and fixing self lubricated asbestos non metallic and non graphite gland packing of sizes 8 to 12 mm complete all as specified and directed Make : Champion or techno and commercial equivalent
Material and labour scrapping of paint complete pump and motor, base frame and accessories complete including making new synthetic enamel paint of two coats over a coat of red oxide primer of motor of capacity 15 HP to 75 HP complete all as specified and directed.
Supply and fixing in repair fabrication of Iron frames size and thickness as per existing on site including nut bolts, washers , two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
Supply and fixing in repair rubber vibration pads heavy duty for base frame as per sample suitable for the following size of pumpsets complete all as specified and directed.
Demolition of Exisiting concrete supporting block of pumps and motor exceeding 15cm of thickness above and below ground level all specfied and directed by Engineer-in-charge
Material and labour cement concrete 1:2:4, type B-2 (using 40 mm graded stone aggregate) as in support of Base frame with MS bolts placed in concrete and hardstanding finishing even and fair without using extra cement all as specified. Note: Location of bolts and size of bolts should match the previous one
Supply and laying in replacement of PVC insulated single core stranded copper unamoured power cable of sizes given below including HDPE pipe of suitable size fixing on walls with saddles :-
Material and labour for Disconnecting motor power cables of various sizes from electrical motor of different capacities and decoupling from the pump sets,removing and taking down carefully and transporting to authorised workshop ,Dismantaling stator and rotor carefully and rewinding stator assembly with supper enamelled copper winding wire of suitable gauge matching to existing gauge and cleaning of slots ,core with carbon tetra chloride solution and apply two coats of insulation varnish and keep stator assembly in heating chamber to improve insulation strength ,reassemble motor completey and transporation to site ,coupling pump to motor and check for proper shaft alignments such that no vibratiobn produce during opertioncoupling to pump with exact alingment, connect power cables to motor and testing of following capacity motor complete all as specified and directed.
(c) up to 15 HP
Supply and fix in repair Star delta starter with Sheet metal enclosure company made, suitable for 75 HP/55 KW Pump set having contactor of size 65A, over load relay ranging from 45A to 65 Amp complete all as specified and directed.
Supply and fix in repair Star delta starter with Sheet metal enclosure company made, suitable for 60 HP/45 KW Pump set having contactor of size 50A, over load relay ranging from 45A to 65 Amp complete all as specified and directed.
Supply and fix in repair Star delta starter with Sheet metal enclosure company made, suitable for 15 HP/11 KW Pump set having contactor of size 25A, over load relay ranging from 12A to 18 Amp complete all as specified and directed.
Construction of brick masonery valve chamber in repair of size 1.2 x 1.2 x 1.2 M (internal dimension) (above GL 0.30 mtr) suitable for fixing of sluice valves, 15cm thick foundation using PCC 1:4:8 type D-2 over 15cm thick hardcore of broken stone, 23cm thick brick walls built in cement and sand mortar 1:4, 15mm thick internal and external plaster including top of floor in cement and sand mortar 1:3, 15mm thick, finished even and smooth, without using extra cement, 5 mm thick plate cover on 50mm x 50mm x 6mm MS angle frame embeded in PCC 1:2:4 type B-1coping, having rectangular, hinged, opening of size 150 x 100mm with locking arrangements ,hold fasts, etc, applying one coat of red oxide primer and two coats of synthetic enamel paint to all steel surfaces and earth work in any type of soil including disposal of debris outside MoD land complete all as specified and directed.
Supply and fixing PVC water storage Tank 5000 ltr capacity 3 layers , ISI marked, hosting and fixing in position at any location removing existing tank disconnecting all incoming & out going connection , provision of new tank fittings and float valve & connecting it at existing position up to 50 mm GI Pipe connection complete all as specified and directed.
Supply and fixing PVC water storage Tank 3000 ltr capacity 3 layers, ISI marked,hosting and fixing in position at any location removing existing tank disconnecting all incoming & out going connection , provision of new tank fittings and float valve & connecting it at existing position up to 50 mm GI Pipe connection complete all as specified and directed.
Shetty Construction Co
ASHOK ENTERPRISES
shakti engineering and electrical works
Hardik Engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .