| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹23.7 LAdmitted-Finance GSTIN: 07BNSPK7205D1ZY | -0.75% | ₹23.7 L | L1 | Admitted-Finance |
| 2 | L2₹25.0 LAdmitted-Finance GSTIN: 07AAMPJ9077E1ZD | +4.80% | ₹25.0 L | L2 | Admitted-Finance |
Tender Value
₹23.9 L
EMD Value
₹47,752
Closing Date
25 Mar 2026, 3:30 pmClosed
Executive Engineer (E ) BM-II
BM-II (E) Division, Gyan Mandir office Complex, Tees January Lane, New Delhi - 110011
Augmentation of Existing VRV System (160 HP Capacity) by Addition of 20 HP Outdoor Unit at ED Office installed at B-Block ED Office, New Delhi under BM-II Division
2026_NDMC_288763_1
117/EE(E)BM-II/2025-26
Open Tender
Electrical Works
30 days
ED Office installed at B-Block ED Office
As per NIT
2 documents required · 2 mandatory
₹0
₹47,752
4 May 2026
17 Mar 2026
25 Mar 2026
17 Mar 2026
25 Mar 2026
17 Mar 2026
Supply of Modular Type outdoor units, equipped with Highly Efficient Scroll, all Inverter Compressor(s), special heat exchanger, Y- branch as required, outdoor unit support, auto check function for connection error, auto address setting, Refrigerant temperature control and capacity as mentioned below. VRV/VRF System shall be suitable for working on 48 °C ambient temperature, Refrigerant R 410A. The unit price shall be inclusive of full charge of Refrigerant Gas & Oil, Freight, Insurance etc. as applicable in INR. having the unit shall have feature to automatically modulate the evaporative temperature between 6 deg C to 11 deg C with respect to load for better comfort and energy efficiency. The fan static pressure of the outdoor unit shall be more than 75 Pa to avoid hot air recirculation. The PCB Chamber of the outdoor unit should be refrigerant cool.Outdoor Units. For Cooling or Heating or Both Make : LG 20 HP Outdoor Unit
Lifting Shifting Installation, Testing & Commissioning of air cooled variable refrigerant flow modular type condensing units, each comprising of 100% inverter scroll compressors, full charge of refrigerant gas (R- 410a), lubricating oil and all accessories as per the specifications. The condensing units shall be suitable to work in both cooling and Heating mode. The condensing units shall be suitable for operation on 415 ± 10% volts, 50Hz, 3 phase AC power supply and the condensing units shall be of following capacities.
Supplying, Installation, Testing and Commissioning of Y/T/Multi Joints. Joints shall be of same Original Equipment Manufacturer (OEM) make as of ODUs and IDUs Indoor Units
Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : (a) 34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm
(b) 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm
Supplying and installation following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastner etc as required. 225 mm width X 50 mm depth X 1.6 mm thickness
Supply & fixing of Condensate Drain Piping 25mm dia
Supply & Charging of R-410A/R-32A gas in the existing VRV AC units, it should also be CFC free as well as ecofriendly or suitable to existing units i/c leakage testing removing the leakage, N2 pressure testing, flushing the complete system, vacuuming and gas charging complete as required
Control & Transmission Wiring-Supply,installation,testing and commissioning of control cum transmission wiring of 2 core x 1.5 sqmm copper in suitable PVC conduits between indoor and out door unit & outdoor units to central remotes controllers etc complete as required.
Providing and constructing a RCC plinth suitable for installation of one number 20 HP VRV outdoor unit, complete in all respects. The plinth shall be constructed at the approved location as per manufacturer’s installation guidelines and site conditions, with minimum size not less than 1500 mm × 800 mm × 300 mm (or as required to fully accommodate the VRV unit base frame) and a minimum height of 300 mm above finished floor level to protect the equipment from water stagnation, dust, and minor flooding. The plinth shall be constructed using M20 grade concrete (1:1.5:3 nominal mix or design mix) with proper shuttering, compaction, and curing. Necessary reinforcement steel (minimum 8 mm dia TMT bars) shall be provided in both directions at suitable spacing to prevent cracking and ensure adequate load-bearing capacity for the VRV unit. The top surface of the plinth shall be finished smooth and level, with chamfered edges, ensuring perfect alignment and stability of the equipment. Provision shall be made for holding-down bolts / anchor bolts or inserts as per the VRV unit base frame, along with necessary sleeves/openings for refrigerant piping, drain pipes, and electrical conduits where required. The work shall be carried out as per standard engineering practices, relevant IS codes, and to the satisfaction of the Engineer-in-Charge.
SITC of Weather proof box with MCCBs of suitable ratings near the outdoor units for isolations for VRV Outdoor Units.(125 Amps)
With the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 4 X 25 sq. mm
Supply, installation, configuration, testing, and commissioning of all hardware, software, and accessories required for integration of the newly installed 20 HP VRV outdoor unit with the existing VRV control system complete in all respects. The scope includes addressing and communication setup of the new outdoor unit and associated existing indoor units, configuration of control parameters, communication wiring, and system synchronization to ensure seamless operation with the existing VRV network Necessary address setting, dip switch configuration, software programming, parameter mapping, and system logic updates shall be carried out strictly as per OEM guidelines including checking error logs, communication stability, and operational interlocks as per the directions of Engineer-in-Charge.
SITC of LG LGMV reset controller with display suitable for monitoring, diagnostics, and reset of a 180 HP LG (VRV) air-conditioning system, complete in all respects. The controller shall be an original LG OEM device, compatible with the installed LG VRV outdoor units and associated indoor units, and shall be capable of real-time monitoring of system operating parameters, fault codes, and communication status. The controller shall provide a clear display interface for viewing system data and allow authorized service personnel to perform fault diagnosis and system reset functions as per LG guidelines. The scope of work includes supply of the LGMV controller, necessary communication cables, connectors, mounting accessories, proper termination, addressing, and configuration of the device with the existing VRV control network. The item also includes software configuration, OEM commissioning support, system testing, verification of proper communication with the VRV system, and demonstration of reset and monitoring functions to the Engineer-in-Charge. All works shall be carried out strictly in accordance with LG installation manuals, ensuring continuity of OEM warranty. The item is complete with all materials, labour, tools, software activation, and testing required for satisfactory operation as per the directions of Engineer in charge
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.92 MB
BOQ_383075.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid