Loading…
Loading…
Tender Value
₹43.6 L
EMD Value
₹87,280
Closing Date
2 Sept 2026, 6:00 pm
Sh Hans Ram Meena, IDSE
GE Kapurthala
Certain special repairs and minor works in the AoR of AGE E/M at Mil Stn Kapurthala under GE Kapurthala
2026_MES_784154_1
8171/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Kapurthala
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE Kapurthala
₹87,280
12 Aug 2026
12 Aug 2026
4 Sept 2026
12 Aug 2026
2 Sept 2026
26 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for point wiring complete with 1.5 Sqmm single core multistranded copper conductor PVC (FR) insulated cable in PVC concealed conduit of size 19/20 mm (ISI Marked) including PVC accessories (concealed in wall and surface in ceiling complete including cutting chasing & making good to disturbed surface etc including pressed steel terminal boxes (sunk in wall) with 3 mm thick plastic laminated sheet top cover with 1.5 Sqmm insulated un-sheathed PVC insulated copper conductor common earth and connecting to earth dolly for :- (a) One socket outlet 3 Pin, 5 Amp on independent board | 115 | Per Point | - | - |
| 2 | S&F of switch piano flush type single pole one way 6 Amp (ISI Marked) | 115 | Each | - | - |
| 3 | S&F of socket out let 2 in 1, 3 pin 5 Amp flush type (ISI Marked) | 65 | Each | - | - |
| 4 | S&F of ceiling fans complete with blades, down rods and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CMM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) and connecting up and including provision of twisted three core PVC insulated flexible cord of 0.75 Sqmm copper conductor of required length from ceiling rose/connector to fan complete all as specified and directed. | 50 | Each | - | - |
| 5 | S&F of stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc; as reqd | 50 | Each | - | - |
| 6 | Supply, Installation and testing of desert cooler electric driven (Single phase) as per followoing specification:-
Size of Desert Cooler:- L x b x h 660 x 660 x 825 mm (26" x 26" x 32.5") Approx
Body:- (i) steel body top cover and pillars of 18 SWG (1.20 mm) thick GI sheet
(ii) Side panels of 20 SWG (1.00 mm) GI Sheet
(iii) Tank height 7" made of 18 SWG (1.20 mm) GI Sheet
(iv) Front grill and directional grill of GI sheet.
(v) Including required iron stand made up of 40 mm angle iron as directed.
Fan Motor:- (i) Exhaust fan motor should be copper winding, 500 mm sweep cooler fan, double ball bearing, three speed (High/Medium/Low) with methalic blade duly painted with snthetic anti corrosive oven cured paint fitted to body fan motor.
(ii) Input cap 200 watt(approx), speed 1400 RPM, 230 Volts, 50 Hz, air delivery 5000/6000 Cum/Hrs
submersible
Pump Motor:- Input cap 40 watt (Approx), speed 1300 RPM, 230 volts, 50 Hz.
Switches/regulator:- One piano switch and one speed selector switch (Regulator) 04 position for controll of pump motor and fan motor respectively will be provided on the body.
Pads:- Wood wool pads of proper Thickness will be provided in each panel (Set of three).
Drain Plug:- Brass drain plug shlall be provided from pump motor to three panel fitted on the cooler body.
Cord:- Flexible cord PVC shethed and Insulated size 40/0.25 mm (1.5 Sqmm) 3 core (as per IS 94/1977) length 5 Mtr long with three pin 5 Amp ISI marked bakelite plug top shall be provided for power supply to cooler.
Note:- (i) All desert cooler should be fitted on first floor or second floor minium height is 8 mtr
(ii) Contrctor should be provide all sefty material for worker for installation of desert cooler
(iii) Contrator should be submitted 01 year guarntee/waranty of desert fan motor and submersibale pump motor. | 25 | Each | - | - |
| 7 | S&F of digital street light timer panel factory made of rating 40A, conforms to IS/IEC 60947-4-1, provided with Protection Degree IP 54, extended wide band coil, FRLS (Fire retardant low smoke) internal wiring, in-built short-circuit protection, class H insulation including 40Amps TP MCB 'B' Curve, 10 KA, 415V and Time switch with contactore TPN 40 A, 'C' curve, 10 KA, 415V including selector switch complete all as required. | 12 | Each | - | - |
| 8 | Supply and installed desert cooler electric driven (single phase), having nominal air flow capacity of 4000 Cum per hour (or nearest size) with following specifications :-.
Body:- (i) PVC body with tank capacity min 75 ltr Inclding Iron stand made of 40 mm angle iron as required.
Fan Motor:- (i) Exhaust fan motor should be copper winding, min 300 mm sweep cooler fan, double ball bearing, three speed (High/Medium/Low) with PVC/methalic blade duly painted with snthetic anti corrosive oven cured paint fitted to body fan motor make from GP-I of PS will be applicable.
(ii) Input capacity 200 watt(approx), speed 1400 RPM, 230 Volts, 50 Hz, air delivery 4000 Cum/Hrs
Submersible Pump Motor:- Input cap 40 watt (Approx), speed 1300 RPM, 230 volts, 50 Hz.
Switches/Regulator:- One switch and one speed selector switch (Regulator) 04 position for controll of pump motor and fan motor respectively will be provided on the body.
Pads:- High density honey comb cooling pads of proper thickness will be provided in each panel (Set of three).
Drain Plug:- Drain plug shlall be provided from pump motor to three panel fitted on the cooler body along with 01 nos of float valve.
Cord:- Flexible cord PVC shethed and Insulated size 40/0.25 mm (1.5 Sqmm) 3 core (as per IS 694/1977) length 5 Mtr long with three pin 5 Amp ISI marked bakelite plug top shall be provided for power supply to cooler.
Note:- (i) All desert cooler should be fitted on first floor or second floor minium height is 8 mtr
(ii) Contrctor should be provide all sefty material for worker for installation of desert cooler
(iii) Contrator should be submitted 01 year guarntee/waranty of desert fan motor and submersibale pump motor. | 40 | Each | - | - |
| 9 | S&F of electric water heater stoarage type steel/ABS body with mettalic inner tank & heating element upto 2KW capacity 25Ltr, BEE 5 Star rated AC 230 volts, 50 Hz vertical type including M&L for grouting four Nos rack bolt to holding water heater on wall including making good and match existing surfaces complete with all accessories such as safety valve, thermostate, NRV, steel braided connection piece of 450 mm long complete all as specified and directed by Engr-in-Charge. | 36 | Each | - | - |
| 10 | M&L for sub main wiring with two runs of single core PVC insulated FRLSH, unsheathed copper condutor, multi stranded cable of size 2.5 Sqmm 1100 volts grade drawn PVC surface conduit of size 19/20 mm (ISI marked) including PVC accessories complete incl cutting and chasing and making good etc; including one run of 2.5 Sqmm single core copper conductor multi-stranded PVC insulated, unsheathed cable as earth wire continuity conductor complete all as specified and directed by Engineer-in-Charge.
Note:- Two run of 2.50 Sqmm cable one run of 2.50 Sqmm cable as earth continuity conductor and one run of PVC conduit shall be measured & paid as one unit.) | 360 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
BOQ_878602.xls
BOQ • 0.63 MB
TENDER.pdf
Tender Documents • 1.53 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].