Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance UC I USHA PARK HARI NAGAR NEW DELHI 64 | NEW DELHI | DELHI | 110001 | Admitted-Finance |
Tender Value
₹1.4 L
EMD Value
₹2,850
Closing Date
13 Oct 2021, 11:00 amClosed
EEE-III/RZ/NZ
EEE-III/RZ/NZ
Improvement of Electrical Installation, fans and other allied works in Central Homeopathic Store MPNS Polyclinic in Lala Hansraj Gupta Health Complex,Sector-7 Rohini under Rohini Zone
2021_NDMC_90680_1
EEE-III/RZ/NZ/TC/2021-22/8.1
Open Tender
Electrical Works
Item Rate
30 days
EEE-III/RZ/NZ
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
₹2,850
Yes
14 Oct 2021
7 Oct 2021
14 Oct 2021
7 Oct 2021
13 Oct 2021
7 Oct 2021
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group-C
Rewiring for light point/fan point/exahust point/call bell point with1.5SQmm FRLS PVC insulated copper conducter S/c cable and1.5 sq.mm.FRLS PVC insulated copper conductor S/C cable as earth wire in existing surface/recessed steel /PVCconduit,i/c dismentling asrequired. Group-C
S&D following sizes of FRLS PVC insulated copper conductor,S/C cable in the existying surface/recessed steel/pvc conduit as reqd. a) 3x2.5 sq.mm
b) 6x2.5 sq.mm
c) 3x4 Sqmm.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. A)20 mm
Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. A) 5/6 amps switch
b) 3 pin 5/6 amp socket outlet
c) 15/16 amp switch
d) 6 pin 15/16 amp socket outlet
S & F metal box of following size (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front i/c painting etc. as reqd. a) 180mm. X 100 mm.x 60 mm.deep
b) 250mm. X 300 mm.x 60 mm.deep
Supplying and fixing brass batten/ angle holder including connection etc.as reqd.
Installation of exhaust fan in the existing opening,including making good the damage,connection,testing & commissioning etc.as reqd. a) Upto 450 mm sweep
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts,10 KA "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. A) Single pole
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
S/I/T/C of 1200 mm sweep,BEE 5 Star rated,ceiling fan with Brush Less Direct Current (BLDC) Motor,class of insulation : B,3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding,Power Factor not less than 0.9,Service Value (CMM/W) minimum 6.85,Air delivery minimum 215 CMM,350 RPM (tolerance as per IS:374-2019),THD less than 10%,remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers,temperature rise=75 degree C (max.),insulation resistance more than 2 mega ohm,suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as reqd.
S&F phenolic laminated sheet 3mm thick i/c cutting as required.
Supply of 12" (300 mm) sweep 1400 rpm exhaust fan heavy duty complete with shutter,blade etc.as reqd.
S/I/T/C of LED type luminaire 20 Watt rating complete with Extruded Aluminium Batten prewired with high efficient LEDs with the following:- (a) Total system wattage 20 watt ±5%.(b) Luminous efficacy lumens/watt ≥95.( c) Power Factor ≥ 0.95.
S/I/T/C of surface mounting CRCA housing 36 W LED luminaire with acrylic cover diffuser with following specifications i/c fixing on existing wall/surface with connections as reqd. (a) Total system wattage 36 Watt ±5%.(b) Luminous efficacy ≥95 lumens/watt.( c) Power Factor ≥ 0.95.
Supply of 9/10 watt LED lamp suitable for B22 holder complete as reqd.
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .