| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.3 LAccepted-AOC | L1 | Accepted-AOC Work order issued | |
| 2 | L2₹9.4 L+₹1.1 L (13.3%)Rejected-Finance NO 1055 MAIN ROAD ODIAMPET VILLIANUR PUDUCHERRY 605110 | CUDDALORE | TAMIL NADU | 605110 | L2 | Rejected-Finance Unsuccessful tenderer | |
| 3 | Not Admitted-Fee/PreQual/Technical NO 50 III CROSS STREET VELNURUGAN NAGAR KOSAPALAYAM PUDUCHERRY 605 013 | PONDICHERRY | PUDUCHERRY | 605013 | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹11.1 L
EMD Value
₹22,170
Closing Date
22 Dec 2022, 4:00 pmClosed
Executive Engineer
Buildings and Roads Division, Public Works Department, Karaikal
Providing internal electrification and electrical fittings in the first floor of the Government Scheduled Caste Boys Hostel at Keezhakasakudy, Karaikal.
2022_PWDC3_11572_1
20/PW/BRK/KKL/2022-23
Open Tender
Electrical Works
Item Rate
60 days
Govt SC Boys Hostel, Keezhakasakudy
Please refer Tender documents.
2 documents required · 2 mandatory
₹525
₹22,170
27 Jan 2023
14 Dec 2022
23 Dec 2022
14 Dec 2022
22 Dec 2022
14 Dec 2022
Amount
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required - 25mm
Supplying and fixing metal box of following sizes (nominal size) on surface or inrecess with suitable size of phenolic laminated sheet cover in front including painting etc.as required - 200 mm x 150 mm x 60 mm
Supplying and fixing following size / modules, GI box along with modular base & cover plate for modular switches in recess etc. as required - 3 module (100mm x 75mm)
Supplying and fixing following size / modules , GI box along with modular base & cover plate for modular switches in recess etc. as required - 4 module (125 mm x 75 mm)
Supplying and fixing following size / modules , GI box along with modular base & cover plate for modular switches in recess etc. as required - 8 module (125 mm x 125 mm)
Supplying and fixing following size / modules , GI box along with modular base & cover plate for modular switches in recess etc. as required - 12 module (125 mm x 125 mm)
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box / wooden block including connection etc as required
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required - 2 X 2.5 sq.mm + 1 x 2.5 sq.mm earth
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required - 2 X 4 sq.mm + 1 x 4 sq.mm earth wire
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required - 4 X 6 sq.mm + 2 x 6 sq.mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor single core cable in the existing surface / recessed steel / PVC conduit as required - 1 X 1.5 Sq mm
Supplying and fixing of following ways surface / recess mounting, vertical type, 415 V, TPN MCB districbution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common netural link, earth bar, din bar for mounting MCB'S (but without MCB's and incomer) as required. (note: Vertical type MCCB TPDB is normally used where 3 phase outlets are required - 8 way, double door.
Supplying and fixing following way , horizontal type three pole and neutral , sheet steel , MCB distribution board , 415 V, on surface / recess , complete with tinned copper bus bar , neutral bus bar , earth bar , din bar, Interconnections , powder painted including earthing etc. as required (but without MCB / RCCB / Isolator ) 4way (4+12) , double door
Supplying and fixing 5 A to 32 A rating , 240/415 V, 10 kA, "C" curve , miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections , testing and commissioning etc .as required. - Single Pole
Supplying and fixing 5 A to 32 A rating , 240/415 V, 10 kA, "C" curve , miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections , testing and commissioning etc .as required. - Triple Pole
Supplying and fixing 5 A to 32 A rating , 240/415 V, 10 kA, "C" curve , miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections , testing and commissioning etc .as required. - Triple pole and neutral
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required - 5/6 A switch
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required - 3 pin 5/6 A socket outlet
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess , including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/6 A modular switch , connections etc , as required
Supplying and fixing brass batten / angle holder including per connection etc.as required
Supply of AC Exhaust Fan 375mm (15'') Sweep (Light Duty)
Supply of 80W LED Focus Light Fitting (Philips / Havells)
Supply and fixing of wall mount bracket of 50 mm dia GI pipe suitable for SVL / MH fittings with clamp, bolts and nuts as required
Fixing testing and commissioning of Sodium vapour / Mercury vapour / Metal halide street light fittings on existing poles as required
Installation , testing and commissioning of ceiling fan , including wiring the down rods of standard length (upto 30 cm) with 1.5 sq.mm FRLS PVC insulated , copper conductor , single core cable , including providing and fixing phenolic laminated sheet cover on the fan box etc as required
Installation of exhaust fan in the existing opening, including making good the damage , connection , testing , commissioning etc. as required - Upto 450 mm sweep
Supply and fixing of 20 - 24W LED tube light fitting. Make:- Philips / Havells / Wipro.
supplying of 4x50 sq. mm armoured aluminium UG cable ;1.1 KV grade at site Make : Polycab/ Finolex/ Havels.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required - 4X50 sq.mm (35 mm).
Supplying energy efficient 5 star 1200mm sweep AC ceiling fan complete with all accessorie like down rod canopy etc with making necessary connection cable as required etc., (Make : Orient/ Usha/ Crompton/ Havells or Equivalent.)
Making earth pit of G.I. pipe for earthing in earth pit with 40mm dia. G.I. pipe medium class of length 3.05m perforated with 46 Nos of 12mm dia. holes, pipe lowered in bore holes of 150mm dia. and filled in with charcoal and salt in alternative layer of 300mm, the top of G.I. pipe shall be clamped. Earth pit shall be provided with 60cm dia precast ring with 60cm depth alround,covered with R.C.C. precast slab etc. as per I.E. standards.
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface / recessed conduit / submain wiring / cable as required
Rajavel Electro Mechanical Works
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .