| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.4 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹37.4 L+₹6.0 L (19.1%)Rejected-AOC | L2 | Rejected-AOC Other than lowest bidder | |
| 3 | L3₹42.6 L+₹11.2 L (35.8%)Rejected-AOC | L3 | Rejected-AOC Other than lowest bidder | |
| 4 | L4₹46.0 L+₹14.6 L (46.5%)Rejected-AOC | L4 | Rejected-AOC Other than lowest bidder | |
| 5 | L5₹55.2 L+₹23.8 L (76.0%)Rejected-AOC 1ST FLOOR RAGHUNATH MARKET NEAR TELEPHONE EXCHANGE PATHANKOT 145001 | PATHANKOT | PUNJAB | 145001 | L5 | Rejected-AOC Other than lowest bidder |
Tender Value
₹50 L
EMD Value
₹1 L
Closing Date
29 Aug 2023, 6:00 pmClosed
Lt Col Sanjeeva Kumar, Offg CWE
Military Engineer Services HQ CWE Jammu
REPLACEMENT OF DISTRIBUTION TRANSFORMER/VCB AND CONNECTED HT DISTRIBUTION NETWORK AT MIRAN SAHIB UNDER GE JAMMU
2023_MES_612057_1
CWEJP-29/2023-24
Open Tender
Civil Works
Item Rate
180 days
GE Jammu
Class D cat b ii
9 documents required · 9 mandatory
₹500
Yes
GE Jammu
₹1 L
Yes
14 Dec 2023
3 Aug 2023
31 Aug 2023
3 Aug 2023
29 Aug 2023
17 Aug 2023
Amount
Material and labour for disconnecting Transformer 11/0.433 KV of capacity 250 KVA to 400 KVA, removal of incoming & outgoing electric connection and taking down carefully from four pole/two pole structure/platform, shifting to workshop draining out transformer oil, opening of top frame taking out the core from the tank, dismantling core into the parts cleaning the tank and removing out the dust particles refixing the same after necessary realignment and heat treatment, connecting all the electric connections and making the Transformer absolutely leak proof, refilling the Transformer oil, testing the Transformer at workshop, transporting back to site and fixing to position as directed, making all electrical and earth lead connection commissioning and testing of Transformer on load at least for 12 hours, re-installing the transformer and making connection complete, all as specified and directed by Engr-in-Charge.
Srl item No 1 Contd … Note: (i) Transportation of Transformer shall be included in the quoted rate only. (ii) Cost of glass Sleeves/ ebonite sleeves insulating material tapes etc shall be included in the quoted rate only. (iii) Rewinding of HT/LT coils, cork sheet for top cover gasket, new brushing bush rod tap changer gear shall be measured and paid for separately under relvant item.
Material and labour for disconnecting Transformer 11/0.433 KV of capacity 50 KVA to 200 KVA, removal of incoming & outgoing electric connection and taking down Carefully from four pole/two pole structure/platform, shifting to workshop draining out transformer oil, opening of top frame taking out the core from the tank, dismantling core into the parts cleaning the tank and removing out the dust particles refixing the same after necessary realignment and heat treatment, connecting all the electric connections and making the Transformer absolutely leak proof, refilling the Transformer oil, testing the Transformer at workshop, transporting back to site and fixing to position as directed, making all electrical and earth lead connection commissioning and testing of Transformer on load at least for 12 hours, re-installing the transformer and making connection complete, all as specified and directed by Engr-in-Charge.
Srl item No 2 Contd … Note: (i) Transportation of Transformer shall be included in the quoted rate only. (ii) Cost of glass Sleeves/ ebonite sleeves insulating material tapes etc shall be included in the quoted rate only. (iii) Rewinding of HT/LT coils, cork sheet for top cover gasket, new brushing bush rod tap changer gear shall be measured and paid for separately under relvant item.
Material and labour for rewinding of HT coils Transformer 50 to 400 KVA with super enamelled double paper wound copper winding wire of existing size and number of turns alongwith insulating material like paper insulation cotton tape, bamboo strip, emery paper packing, varnishing etc, demoisturing by heating and drying etc including primaray testing, ratio testing, no load testing core bolt insulation testing complete, all as specified and directed by Engr-in-Charge. Note: Rewinding and testing of transformer to be carried out through approved firm.
Material and labour for rewinding of LT coils Transformer 50 to 400 KVA with super enamelled double paper wound copper winding wire of existing size and no of turns alongwith insulating material like leathorised paper insulation cotton tape, wooden block packing, varnishing etc, demoisturing by heating and drying etc including primaray testing, ratio testing, no load testing core bolt insulation tesing complete, all as specified and directed by Engr-in-Charge. Note: Rewinding and testing of transformer to be carried out through approved firm.
Material and labour for taking out old LT winding wire and reconditioning of existing LT copper coil with new insulating material, with leathorised paper insulation, cotton tapes, wooden block packing and PVC sleeves, soldering and varnishing, heating, drying and testing of coils for transformer of capacity from 50 to 400 KVA complete, all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement HT brass/gun metal bush connecting rod of suitable length and dia with necessary nuts, washers and bushing packing to prevent oil leaking from the bushes and HT insulators including making necessary connections for transformer capacity from 50 KVA to 400 KVA complete, all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement LT brass/gun metal bush connecting rod of suitable length and dia with necessary nuts, washers and bushes and LT insulators packing to prevent oil leaking from the bushes including making necessary connections for transformer capacity from 50 KVA to 400 KVA complete, all as specified and directed by Engr-in-Charge.
Supply and fixing silica gel breather assembly of metallic body for 11 KV transformer of capacity from 50 KVA to 400 KVA complete, all as specified and directed by Engr-in-Charge.
Supply and fixing cork sheet gasket of 6mm thick cut to size/Shape for top cover of 11 KV transformer of capacity up to 400 KVA complete, all as specified and directed by Engr-in-Charge.
Dehydration, filtration of step down (11/0.415 KV) transformer oil of various cap of transformers on running condition of transformer, dielectric strength not less than 60 KV in 2.5 mm gap (RMS) complete, all as specified and directed by Engr-in-Charge. Notes :- (i) Dehydration and filtration can be carried out at site by bringing filtration machine or other wise the same shall be got done from the manufacturing workshop of transformers. (ii) Testing oil shall be carried out before filtration and after filtration of insulating oil. (iii) Rates of dehydration machine used shall be included in the rate quoted.
Supply, heating and filling of transformer insulating oil HV grade having dielectric strength not less than 60 KV (RMS) at 2.5 mm gap high velocity in transformer complete, all as specified and directed by Engr-in-Charge.
Material and labour for painting of transformer externally with two coat of spray painting with heat resistance/smoke grey heat resistance synthetic enamelled paint after cleaning rusted surface thoroughly with thinner and scrapper and preparing the surface to required standard including writing and marking such as MES No, SM No, Capacity, location of area feed, Date of oil filling on the body of transformer capacity upto 500 KVA complete, all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of aluminium strip of size 25x3 mm with saddles and fixing screws on porcelain insulator/spacer fixed at every 1 mtr length as lightening conductor for lightening arresters on HT poles/Transformer including necessary nut & bolts complete, all as specified and directed by Engr-in-Charge.
Supply, laying, testing and commissioning HT underground cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured electric power cables (heavy duty) with aluminium stranded conductor served with an inner sheathing of PVC tape armoured with galvanized steel strip and overall PVC sheathed 11000 volts grade (earthed) of cross sectional area of size 120 sq mm 3 core complete, all as specified and directed by Engr-in-Charge. Note: Excavation, earthwork and GI Tubing shall be measured and paid seperately under respective items.
Supply, laying, testing and commissioning HT underground cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured electric power cables (heavy duty) with aluminium stranded conductor served with an inner sheathing of PVC tape armoured with galvanized steel strip and overall PVC sheathed 11000 volts grade (earthed) of cross sectional area of size 95 sq mm 3 core complete, all as specified and directed by Engr-in-Charge. Note: Excavation, earthwork and GI Tubing shall be measured and paid seperately under respective items.
Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrinkable end type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120 Sqmm and jointing materials for making joints and testing complete, all as specified and directed by Engr-in-Charge.
Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrinkable end type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120 Sqmm and jointing materials for making joints and testing complete, all as specified and directed by Engr-in-Charge.
Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrinkable end type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 Sqmm and jointing materials for making joints and testing complete, all as specified and directed by Engr-in-Charge.
Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrinkable end type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 Sqmm and jointing materials for making joints and testing complete, all as specified and directed by Engr-in-Charge.
Supply and erection in vertical position Steel tubular swaged poles erected truly vertical or planted as strut complete with 300x300x6 mm thick mild steel base plate continuously welded at bottom of pole and MS sheet 2 mm thick plug welded at top, B-118 finial taper cap,bolts,nuts & screws, poles made out of ERW MS tubing conforming to IS 2713 Part-II. Type 410-SP-55 (11.00 metres long) including drilling of holes of required size for fixing of cross arms, painting the exposed surfacs of pole with two coats of aluminium paint over a coat of zinc chrome primer and two coats of black bitumenous paint internally & portion embedded in concrete, making five black and white alternate strips 30 cm upto 1.5mtr height from top of coping in strips and marking pole No. with black paint at suitable height including dismantling of existing pole & making good complete all as specified and directed. Note: Excavation and earth work, PCC in foundation shall be measured and paid for separetely.
Supply and fixing in replacement switch air break gang operated triple pole mechanically operated from ground level, mounted on insulators and steel frame (12 insulator type) outdoor type suitable for vertical installation single break provided with locking arrangement consisting of MS channel, HT post top insulator with drop out fuses operating rod 25mm bore GI pipe medium grade confirming to relevant IS, current rating 200 Amp and voltage 11 KV including jumpering, lead of wire/cable as directed at site including dismantling existing/unserviceable air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism and removing from site, complete all as specified and as directed.
Supply and fixing in replacement Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp,11000 Volts grade conforming to IS-3070 part-I, complete, all as specified and directed by Engr-in-Charge.
Supply and fixing in replacment of ACSR conductor of required size for Over head lines on poles including streching, tightining of poles insulator with winding wire of suitable size with insulator/streching of ACSR conductor including dismantling of unserviceable ACSR Conductor of any size from existing over head lines complete, all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement Stay assembly with accessories and GI stay rod 16 mm dia 1900 mm long, stay wire 7/4 mm stranded galvanised including mild steel stay plate 300 mm x 300 mm x 6 mm and galvanised thimble, galvanised steel 14 mm dia 400 mm long stay bow and GI nuts, washers including loop type insulator vitreous porcelain white, brown or green big size withoverall dimensions 90 mm x 140 mm clearance of hole 25.5 mm complete all as specified and shown in electrical plate No 01 of SSR Part - I including dismantling of unserviceable stay assembly complete, all as specified and directed by Engr-in-Charge. Note: Excavation, stay clamps and concrete work etc will be measured and paid separately..
Material and labour for loop type insulator, porcelain, vitreous, white, brown or green, small size with over all dimensions 65x90mm, clearance hole 16mm cmplete all as specified.
Material and labour for galvanised stay wire 7/4 mm, for HT/LT lines on steel tubular poles,streaching without kinks and bends including binding wire including taking down old unsv galvanised stay wire complete all as specified.
Supply and fixing in replacementof Disc type, insulator, porcelain, vitreous, white, brown or green, 145 mm high and 255 mm dia ball and socket type for working pressure 11000 volts complete Single disc assembly for tension with tension clamps for conductors complete, all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of Insulator Pin type, porcelain, vitreous, white,brown or green including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade complete, all as specified and directed by Engr-in-Charge.
Material and labour for Calibration of digital/IDMT protective relays of 11 KV panel (VCBs), testing of 11 KV control and relay panel includes main protection relay. Backup protection(O/C &E/F) relay for all features like inverse O/C, Inverse E/F, high set O/C, high set E/F etc along with pickup & dropoff volts for all auxillary relays like master trip, trip circuit supervision, checking and testing of wiring connections at all terminal points/ at relays, inspecting wiring for any open circuit, short circuit & damaged insulation, and preparation inspection data sheet of existing feeder re-programming input data into relays (OCHS,EFHS, OCLS, EFLS, CTR, TDS etc) complete testing by injecting current in CT primary and measure secondary current at 11 KV , control and relay panel for metering in service through current injection in CT primary and ratio and including complete polarity test complete, all as specified and directed by Engr-in-Charge. Note: All testing shall be carried out in presence of Engr-in-Charge and test certificate shall be provided.
Supply in replacement of indicator lamp assembly in different colour as directed complete of VCB panel 24/36/110 Volts of existing size complete, all as specified and directed by Engr-in-Charge.
Supply and fixing digital meter showing Amps, Volts complete for 11 KV VCB control panel complete, all as specified and directed by Engr-in-Charge.
Supply and fixing Ampere meter analog type of size 50x50 mm, range from 0-100 for 11 KV control panel complete, all as specified and directed by Engr-in-Charge.
Supply and fixing Volt meter analog type of size 50x50 mm, range from 0-40KV, for 11 KV control panel complete, all as specified and directed by Engr-in-Charge.
Maintenance and complete servicing of HT VCBs including de-assembling of operating machanism parts, well cleaning with chemical CRC 226, replacing unserviceable parts and accessories like spring, gasket, coils, nuts, bolts and washers etc oiling and greasing of moving parts, re-assembling, fine setting of mechanism, well cleaning and de-carbonizing of arc control pot, fixed and moving contact including checking, testing, tripping check of HT VCBs making perfect operation in manual and electric mode including maintenance and well cleaning the complete panel board bus bars, de-carbonizing all joints, bus bar, CTs metal parts, replacing unserviceable parts and components etc complete, all as specified and directed by Engr-in-Charge. Note : (i) Spare parts will be measured and paid seperately as supply only under respective items. (ii) The labour charges deemed to be included in the unit rate quoted for this items.
Supply only Spring charging motor as per existing brand complete, all as specified and directed by Engr-in-Charge.
Supply only Closing coil 30 Volts DC complete, all as specified and directed by Engr-in-Charge.
Supply only Tripping coil 30 Volts complete, all as specified and directed by Engr-in-Charge.
Supply only Vaccum interupter for existing VCB complete, all as specified and directed by Engr-in-Charge.
Supply only Control wiring kit for metering, motor charging, indicator lamps and relays etc. complete, all as specified and directed by Engr-in-Charge.
Supply only Motor charged mechanism assembly with close/trip coil & charging handle of existing size and capacity complete, all as specified and directed by Engr-in-Charge.
Supply only Manual charging handle for VCB 11 KV complete, all as specified and directed by Engr-in-Charge.
Supply only Operating shaft pin for VCB 11 KV complete, all as specified and directed by Engr-in-Charge.
Material and labour in replacement of 11 KV single phase in door Resin cast CT of ratio 400/5-5VA class 1.0 – 5P10 burden 15VA – 15VA insulation level 28 KV/75 KV as per IS-2705 complete, all as specified and as directed by Engr-in-Charge.
Supply and fixing of danger notice plate board of size 250 mm x 200mm for HT 11000 volts system made of 1.6 mm thick steel sheet , vitreous enameled white , with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps ,bolts,nuts of approved size, complete all as specified and as directed by Engr-in-Charge.
Labour for Cutting of tree branches 2 mtr vicinity of the conductor which are touching to the 11/9 mtr Over Head Lines in vertically & horizontally conductor and poles etc, complete clear in a standard Span in between two poles as per SSR Part-1, 19.59 and removing cutting material not exc 50 mtr and depositing where directed at a distance level not exc 3 mtr from starting point. (Note: Pole to pole will be consider as one span of any length and nos of conductor).
Material and labour for preparation of old painted / rusted surfaces of steel tubular poles 11/9 mtrs long type 410 SP-31,55 and applying one coat of synthetic enamel paint up to 1.2 mtr height height in black and white strip of width 30cm each as per exising pattern above the P.C.C coping and two coat of aluminum paint (1st quality) beyond 1.2 mtr height (for the rest of portion) incl cross arms and channel, angle fitted on the pole incl wiriting pole numbers and cutting vegetation growth all around and on the poles up to 1 mtr radius complete all as specified and directed.
Material and labour for earthing complete with galvanized steel plate earth electrode 60cmx60cmx6mm thick surrounded by char coal and salt buried directly in ground vertically in pit of depth not less then 2.25 mtr below ground level with top edge of the earth plate at depth of not less then 1.5 mtr below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth plate electrode connected to galvanised earth lead wire of 4.0mm dia (8 SWG) by means of GI nuts bolts, check nuts and washers and connected to earthling test point drawn through 15mm dia GI pipe for protection of GI earth lead wire including 20mm dia GI pipe for watering GI funnel , PCC earth pit (1:3:6) type C-2 with CI frame and RCC cover all as shown in electrical Plate No 3 on SSR Part-I including testing and dismantling of unserviceable existing earthing any type complete including removing PCC from Site complete, all as specified and as directed by Engr-in-Charge.
Srl item No 48 Contd … Notes :- Cost of following items are deemed to be included in unit rate:- (a) 15 mm nominal bore light grade GI protection pipe 7.5 mtr long for protection of earthing lead from mechanical injury or tempering. (b) Requisite quantity of common salt and charcoal. (c) Testing of earthing. Note : On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge.
Material and labour for earthing complete with Galvanized earth plate electrode 600 mm x 600mm x3.15mm thick buried directly in ground ( earth pit not less than 2.25 mtr below normal ground level ) with top edge plate not less than 1.5 metre below normal ground level and covered with alternate compact layer of comen salt and charcol dust, connected to Galvanized earth strip of size 25x4mm as earthing lead by means of bolts, nuts, chuck nuts and washers of Copper earth lead including PCC pit in PCC 1:2:4 type B-1 RCC cover made out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle and angle iron 40x40x5mm frame, GI medium grade watering pipe 20mm bore and funnel with wire mesh light grade protection pipe 40mm bore up to main board complete as shown on electrical plate No 5 of MES Sch 2009 (Part-I) and connected to earthing test point all as specified and directed by Engr-in-charge.
Srl item No 49 Contd … Notes :- Cost of following items are deemed to be included in unit rate:- (a) 15 mm nominal bore light grade GI protection pipe 7.5 mtr long for protection of earthing lead from mechanical injury or tempering. (b) Requisite quantity of common salt and charcoal. (c) Testing of earthing. Note: On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge.
Material and labour cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts and wasters,welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat of red oxide primer and two coats of aluminum paint including dismantling of cross arms of MS fabricated complete with all accessories viz nut, bolts, washer etc. complete, all as specified and as directed by Engr-in-Charge.
Material and labour for loose filling in substations, under poles, under transformers of hard core broken to gauge not exc 40 mm broken stone/boulders incl leveling and spreading llime stone powder under stones complete, all as specified and directed by Engr-in-Charge.
Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrinkable straight through joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm and jointing materials for making joints and testing complete, all as specified and directed by Engr-in-Charge.
Description all as per Srl item No 52 above but size of cable 120 to 185 sqmm.
Material and labour in replacement of Galvanised steel wire 4.0 mm dia for continuous earth wire/cradle guard for HT overhead line 11/0.415 KV line complete, all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of 11000 Volt Arial bunched conductor having phase conductor of multistranded compacted circular aluminium conductor screen of extruded semi conducting compound extruded XLPE insulated , insulation screen of extruded semi conducting compound over all metellic screen of copper tape extruded PVC type ST-2 sheathed twisted around bare aluminium alloy messenger generally as per IS 7098 Part-II of size 3x95 SQMM + 1x 70 SQMM complete with dead end clamp,suspension clamp, Eye Hook ,welding and cable Jointing Kit as per site requirement with the existing LT disribution system complete, all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of 11000 Volt Arial bunched conductor having phase conductor of multistranded compacted circular aluminium conductor screen of extruded semi conducting compound extruded XLPE insulated , insulation screen of extruded semi conducting compound over all metellic screen of copper tape extruded PVC type ST-2 sheathed twisted around bare aluminium alloy messenger generally as per IS 7098 Part-II of size 3x120 SQMM + 1x 95 SQMM complete with dead end clamp,suspension clamp, Eye Hook ,welding and cable Jointing Kit as per site requirement with the existing LT disribution system complete, all as specified and directed by Engr-in-Charge.
Excavating in trenches, not exceeding 1.5 m wide and exceeding 1.5 m in depth; for foundation, trenches for laying of cable etc. and getting out in any type of soil, complete all as specified and as directed by Engr-in-Charge.
Description all as per srl item No-57 above but depth exceeding 1.5 metres and not exc 3.0 metres.
Returning, filling in (soil) including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick in any type of soil,complete all as specified and as directed by Engr-in-Charge.
Removing excavated material not exceeding. 50m and depositing where directed at a level n exc. 1.5 m above the starting point, complete all as specified and as directed by Engr-in-Charge.
Dry coarse sand as cushioning to under ground cable provided with layer of 8 cms deep before laying the cable and 15 cms deep after laying and stretching the cable, punned to 18 cm thick complete, all as specified and as directed by Engr-in-Charge. NOTE: only punned thickness shall be measured for payment purpose.
Sub class ‘B’ old size well burnt bricks, laid flat with width equal to length of brick in trenches as protection to cable complete all as specified and as directed.
Plain cement concrete 1:4:8 type D-2 using 40mm graded crushed stone aggregates as in pole foundation complete, all as specified and as directed by Engr-in-Charge.
Plain cement concrete 1:3:6 type C-2 using 40mm graded crushed stone aggregates as in stay assembly complete, all as specified and as directed by Engr-in-Charge.
Plain cement concrete 1:2:4 type B-1 using 20mm graded crushed stone aggregates as inr coping of pole and stay assembly complete, all as specified and as directed by Engr-in-Charge.
BMMJ TRADERS AND ENGINEERS
Jiwan Singh
M/S S K Electricals Regd
JCC ENGINEERS PRIVATE LIMITED
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .