| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.6 CrAccepted-AOC STREET NO 11 SECTOR NO 04 TILAK NAGAR SAGAR ROAD BIKANER RAJASTHAN 334001 | BIKANER | RAJASTHAN | 334001 | ₹11.6 Cr | L1 | Accepted-AOC L1 bidder |
| 2 | L2₹13.0 CrRejected-Finance | ₹13.0 Cr | L2 | Rejected-Finance Not L1 |
Tender Value
₹10.3 Cr
EMD Value
₹8.4 L
Closing Date
10 Jun 2022, 6:00 pmClosed
CHIEF ENGINEER
HEADQUARTER CHIEF ENGINEER JAIPUR ZONE JAIPUR
ADDITION ALTN TO EXISTING SECURITY WALL AND PROVN OF 14 X GD POST CUM WATCH TOWERS AT BHARATPUR
2022_MES_514163_1
80820
Open Tender
Civil Works
450 days
Bharatpur
Please refer Tender documents.
8 documents required · 8 mandatory
₹3,000
GE BHARATPUR
₹8.4 L
Yes
2 Jul 2022
17 Mar 2022
17 Jun 2022
17 Mar 2022
10 Jun 2022
28 May 2022
25 Apr 2022 - 30 Apr 2022
Amount
Lump sum price worked out by the contractor for "BUILDING WORKS" as listed in Schedule ‘A’ Part-I representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from page No. 24 (R)
Lump sum price worked out by the contractor for "INTERNAL WATER SUPPLY " as listed in Schedule ‘A’ Part-II representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from page No. 25 (R)
Lump sum price worked out by the contractor for "INTERNAL ELECTRIFICATION" as listed in Schedule ‘A’ Part-III representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from page No. 28 (R)
Lump sum price worked out by the contractor for "ROAD, PATH AND CULVERT etc." as listed in Schedule ‘A’ Part-IV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from page No. 30 (R)
Lump sum price worked out by the contractor for "SEWAGE DISPOSAL" as listed in Schedule ‘A’ Part-V representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from page No. 32 (R)
Lump sum price worked out by the contractor for "EXTERNAL WATER SUPPLY" as listed in Schedule ‘A’ Part-VI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from page No. 33 (R)
Lump sum price worked out by the contractor for "EXTERNAL ELECTRIFICATION " as listed in Schedule ‘A’ Part-VII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from page No. 34 (R)
Lump sum price worked out by the contractor for "SUMMER APPLIANCES" as listed in Schedule ‘A’ Part-VIII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from page No. 35 (R)
Lump sum price worked out by the contractor for "SECURITY WALL AND RETAINING WALL " as listed in Schedule ‘A’ Part-IX representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from page No. 37 (R)
Lump sum price worked out by the contractor for " EXCAVATION & EARTH WORK " as listed in Schedule ‘A’ Part-X representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from page No. 38 (R)
Lump sum price worked out by the contractor for "DEMOLITION/DISMANTLING OF EXISTING BUILDING / STRUCTURE " as listed in Schedule ‘A’ Part-XI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from page No. 39 (R)
Sch 'A' Sec-XII (MISCELLANEOUS ITEMS) Notes: (i) This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under column 5 signifies this fact only. (ii) Excavation and earth work except for the items which categorically includes for same shall be measured and paid separately under SCH A PART-X (Excavation and earthwork schedule).
INTERNAL ELECTRIFICATION:
S&F 09 W LED bulb complete all as specified and directed.
S&F ISI marked MCB for AC supply till 63 A, having breaking capacity Icn = 10 kA, conforming to IS/IEC 60898-1-2002, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters,for following all complete as specifed and directed.
6-32A, SP MCB, C-curve
40A, SPN MCB, C - curve
SEWAGE DISPOSAL
Supply and and fixing of 2000 litres of LLDPE septic tank for 10 users designed to carry sewage and sullage water, excavation in any type of soil , 150mm thick PCC 1:4:8 below foundatioon, vent shaft , connection pipe for inlet and outlet of any dia etc as per manufacturer instruction complete all as specified and as directed.Invert level of the inlet shall be 600 mm below GL. Manufacturer:- Green India faridabad, Kusum anand energy Faridabad, Saifi Enterprises Gautam Budh nagar RD India Gautam Budh nagar, Aggarwal Enterprises Delhi.
Construction of soakage wells of size 1.8 metre dia and 3.0 metre effective depth including excavation in any type of soil complete all as specified and shown on drawing.
EXTERNAL WATER SUPPLY
Supply, laying in trenches, under floor, under road, connecting, jointing and testing ductile iron pressure pipe centrifugally cast ISI marked with socket and spigot ends confirming to IS-8329/2000 standard length of K-7 specification with outside zinc coating of size 100mm dia complete allas specified and directed. Note :- (i) Excavation and earth work will be measured and paid separately. (ii) Th Joints shal be included in the unit rates quoted.
M&L for ductile iron fitting for K-7 pipes, such as bends (any type, radius and angle) tapers any type (straight, bend, increasing, decreasing or double socket etc.) Tee pieces, single branch, "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs upto 200mm dia complete all as specified and directed.
M&L of provision of brick masonry valve pit chamber of 3mm thick MS sheet and angle iron frame of 40x40mm including black bituminous paint and 1200x1200x1000mm size (internal dimensions) including necessary excavation and earth work and frame with cover complete all as shown in drawing and as specified and directed
M&L for boring of holes under road, pavement, hard standing using trenchless technology using suitable tools and machinery for laying of pipe upto 150mm pipe complete all as specified and as directed. Note :(i) Pipe shall be measured and paid seperately. (ii) Depth of boring shall be 0.6 mtr to 0.9 mtr. The width of bore shall be as per site requirement.
EXTERNAL ELECTRIC SUPPLY
Supply and install commissioning and testing factory made and tested (includng CPRI certified) LT panel box (KIOSK) out door type platform mounted suitable for 415 volt , 3 phase, 4 wire , 50 Hz AC supply system all as specified and directed having busbar chamber with insulated Copper bus bars 300 amps rating installed on percelain insulators, the panel shall be dust and vermin proof double door made of 2.00 mm CRCA MS sheet outer & inner 3.15 mm thick and individual compartment for MCCB/MCB & volt/Amps meter and 40 x 40 x 6 mm thick angle iron for base frame work.The complete feeder pillar box should be power coated including internal wiring with PVC insulated solid copper conductor FRLS cables appropriate size but not less than 4 Sqmm. Front opening type with approx for cable entry with double door shutter including locking arrangement as per manufacturers with 2 Keys. The scope of work includes provn of the followings :- (a) Incoming MCCB 4 Pole- 160 Amps 25 KA - 02 No.(For loop in & loop out) (b) Bus bar Copper TPN 300 Amps - 01 Set. (c) Outgoing MCB 4 Pole 25 Amp -2 Nos(1 stand by)
Supply , fixing, commissioning and testing of Diesal Genrator set capacity not less than 40 KVA,415 V,50Hz,3-phase,4 wire system with manual panel including installation and commissioning with following specification:- OUTPUT CAPACITY RATING/ PHASE (i) Nominal Rated Capacity (KVA) - not less than 40 KVA (ii) No of Phase - 3-Phase (B) ENGINE: Make-Cummins/as per approved list in PS ISI Marking to IS :10001 for engine BIS license No, if applicable Type of Engine cooling - Liquid cooled Type of governer - Mechanical Class of governer - As per OEM Number of cylinders (nos) - 6 Rated RPM of Engine (RPM)-1500 Overload capacity for one hour for every 11 hours continuous running at full load (%) -10% Starting voltage (volt) -12 ALTERNATOR :Make-Stamford /as per approved list in PS Rating of AC Generator (KVA) -not less than 40 KVA Power Factor of AC generator - 0.8 Compliance of Alternator to IS:13364(part-1) Type of alternator - Brushless Voltage Regulation Grade - VG 23 Alternator IP Rating- IP 23 Class of Insulation - class H
Supply and install commissioning and testing factory made and tested (includng CPRI certified) LT panel box (KIOSK) out door type platform mounted suitable for 415 volt , 3 phase, 4 wire , 50 Hz AC supply system all as specified and directed having busbar chamber with insulated Copper bus bars 300 amps rating installed on percelain insulators, the panel shall be dust and vermin proof double door made of 2 mm CRCA MS sheet outer & inner 3.15 mm thick and individual compartment for MCCB/MCB & volt/Amps meter and 40 x 40 x 6 mm thick angle iron for base frame work.The complete feeder pillar box should be power coated including internal wiring with PVC insulated solid copper conductor FRLS cables appropriate size but not less than 4 Sqmm. Front opening type with approx for cable entry with double door shutter including locking arrangement as per manufacturers with 2 Keys. The scope of work includes provn of the followings :- (a) Incoming MCCB TPN- 160 Amps 25 KA - 01 No.(For loop in & loop out) (b) Change Over switch 4 pole 200 Amp 415 V-1Nos (c) Bus bar Copper TPN 300 Amps - 01 Set. (d) Outgoing MCCB 4Pole 63 Amp -4 Nos(1 stand by)
Supply, installation and testing of high intensity, Energy saving, long range, multi-functional, auto-swivel LED search light, beam range 600 meter,1x250w, Single, LED light, Efficency > 160 lm/w, PF>0.95, CCT5500K-6500K, Optical grade PMMA-PC lens reflector, anti-UV oxidation, narrow beam 5 degree, die cast LM6 body with air fins, fully powder coated, working voltage 150-290, 50hz, constant current, reflector/lens efficiency > 95%, average lux level at 10 meter - 3000(min) and at 600 meter - 01 (Min) with circle of approx 1 meter,and IP-66, confirming to LM79/LM 80, including installation on disc of revolving mechanism with suitable motor - gear unit and design such to rotate 360 degree continuously over the night in horizontal plane with speed controller (1 to 10 rpm) & R/F buttons and inbuilt push to tilting option upto 45 degree, including seperate wall mounted wired control panel(consist of MCB's, V-meter, Fuse, LED indicators) for smooth & safe operation remotely. The revolving mechanism is to be fully covered with weather & rust proof fiber box with maintenance window/ door including fixing on roof with of 4 nos, foundation holes at bottom as per OEM instructions. Make : Kalin. Cat No. : MRSL-LRFLL-25PC25, or equivalent model of make of SIGMA/Aska/ Point Blank(as approved).
S & F cable route indicator LT with colour code ( BROWN) HT 10cm dia made of cast iron 8mm thick fixed on MS angle iron of size 25x 25x 5mm 60cm long complete including fixing necessary excavation in soft/loose soil embedded in PCC 1 : 2 : 4 type C1 block of size 300 x 200 x 600mm( 30 cm of PCC elevated above ground level) and removal of surplus soil and marked as HT cable / joints on circular cast iron plate with colour code complete all as specified and as directed
Supply, install, test and commissioning factory made THERMOPLASTIC CABLE JUNCTION BOXES IP 66/67 “weather proof”, with terminals for outdoor installation (with knockouts for cable entry) of size 205 x 255 x 112 mm depth with cable entry size of 10-25 sqmm with 4 pole termina capacity 100A each, glands including with flat iron clamps of size 30 x 6mm, nuts and bolts. Make Hansel Cat part No:KF 2525 G or equivalent make in Legrad
M&L for taking out Unsv U/G cable PVC insulated/ armoured/ PVC sheathed Al Conductor, LT cable of any size complete all as specified and directed.. Note: Excavation and earth work measured and paid seperately.
Taking out Old U/S MS junction box complete all as specified and directed..
SECURITY WALL
S & F Concertina coil (on angle iron supports) conforming to IS-4454, IS-513, IS-277 & IS-280, with punched tape concertina coil 600 mm diameter having 50 Nos roung per 6 M length with necessary bolts and GI staples with 09 nos horizontal R.B.T. reinforced barbed wire. stud tied with GI staples and GI clips to retain horizontals, Concertina coil of core wire diameter 2.95 mm, blade thickness 0.50 mm, balde length 12 mm, width of blade 15 mm and spacing of blade 26 mm.(Reinforced barbed tape/ spring core of min tensile strength 165 Kg / Sqmm tape and weight not exceeding 60 gm per running metre. NOTE : -The payment shall be made as per unit weight of sample approved by GE or 60 gm/RM whichever is less.
Dismantling of Barbed wire of any description not otherwise provided for complete all as specified and directed.
COOLING APPLIANCES
Supply, fixing and fabrication and testing desert cooler in GI body sheet with and including cooler fan motor size/sweep 450mm (fan blade only) 230 volts, single phase 50 Hz , 1400RPM. Heavy duty single sheet, (a) Air grill of suitable size made out of 0.5mm thick PGI sheet including GSS arrangement with a knob for easy and smooth movement. (b) Front and side panel made out of 1mm thick PGI sheet of suitable size and shape. (c) Water tank height should not less than 11 inch made out of 2mm thick PGI sheet. (d) Submerssible pump electric driven single phase 230volt , 50Hz of suitable discharge and headup but motor capacity not less than 18 watt. Make:- Khaitan/ Crompton or equivalent make. (e) Service cord of 3 core copper wire 1.5Sqmm with plug top 5 Amp length not less than 2 metres. (f) Electronic fan dimmer 1000watts AC 230volts for controlling the fan speed. (g) Complete electric wiring of desert coolers as required to operate fan and pump alongwith 5Amp switches. (h) Make of Cooler fan Motor : Khaitan/Havells/ Crompton Greaves / Marathon/ Almonard. (j) Make of PGI sheet : Tata/Jindal/ National
Supply and install testing & commissioning voltage stabilizer for automatic operation, single phase naturally air colled Indoor type copper wound & designed for input variation between 100V to 300 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 2.0 KVA complete all as specified and directed.
Sood Enterprises