Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance PROP NO A 80 FIRST FLOOR FLAT NO 3 CHATTAR PUR ENCLAVE PHASE 2 NEW DELHI SOUTH WEST DELHI DELHI 110074 | SOUTH DELHI | DELHI | 110074 | Admitted-Finance |
| 2 | Admitted-Finance 1008 A PREMIER ENGINEERING COMPANY PURVI RITHANI MEERUT DELHI ROAD MEERUT UTTAR PRADESH 250103 INDIA | MEERUT | UTTAR PRADESH | 250103 | Admitted-Finance |
| 3 | Not Admitted-Finance | Not Admitted-Finance Others-FDR not submitted |
| 4 | Not Admitted-Finance | Not Admitted-Finance Others-FDR not submitted |
Tender Value
Refer Docs
EMD Value
₹18,800
Closing Date
13 Jan 2023, 11:30 amClosed
EE(EnM)M-11
Apollo BPS Near Apollo Hospital Sarita Vihar Mathura Road New Delhi - 110076
SITC of LT Panel Distribution and Protection System for the Operation of Hydrant (Filling Point) at B-1 Vasant Kunj Water Emergency under Mehrauli Constituency AC 45.
2023_DJB_234392_30
NIT No. 35/EE(EnM)M-11/2022-23
Open Tender
Miscellaneous Works
Works
30 days
EE(EnM)M-11
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Delhi Jal Board
₹18,800
25 Feb 2023
6 Jan 2023
13 Jan 2023
6 Jan 2023
13 Jan 2023
6 Jan 2023
LT Distribution panel sheet steel enclosure made out of 2mm CRCA sheet totally enclosed, powder coated free standing, floor mounted type, dust& vermin proof, outward opening, lockable double doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets to provide IP-54 protection .The each part of the fabricated panel will be strictly subjected to seven tank treatment. The various components, assemblies and sub equipments of the panel will be as per standard given in relevant IS. The bus bar Size: 20 mm X 10 mm (suitable for 200 Amp.) of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized in aluminium. The control wiring of the panel will be done with PVC flexible copper wires of 1.5mm cross section. Each wire will be terminating with a ferule crimped to the wire. Size of Panel : 1200 mm x1000 mm x 375 mm. Having following components of approved make. The LT panel shall be mounted on the suitable base frame of MS angle size :- 50mmx50mmx6mm with 450mm depth., Note:-Each LT Panel will contain four No. of pump operational systems.
MCCB 415V, 4 Pole, 3 phase High breaking capacity 50 KA 50 Hz, 200 Amp with spreader & handle . Make:- L&T/Siemens
MCCB 415V, 3 Pole, 3phase 50KA 50Hz, 63 Amp with spreader & handle. Make:- L&T/ Siemens/ DJB approved
MCB Single pole 6 Amp. Make:- L&T/Havells/DJB approved
MCB Triple pole 32 Amp. Make :-L&T/Havells/DJB approved
Over load relay range 14-23 Amp Make:- L&T/Siemens /DJB approved
Digital Amp. Meter:-Make AE/L&T/DJB approved
Digital Volt Meter 0-500 Volt .Make:- AE/L&T/DJB approved
Shunt power capacitor(Heavy Duty) 5 KVAR for reactive power management
Motor protection/phase failure Relay Make:- L&T/Siemens/DJB approved
Power contactor 220V 3phase 40 Amp. Make:- L&T/Siemens/DJB approved
Current Transformer 200/5 & 30/5. Make:- AE /Advance/DJB approved
Star-delta timer 0-30 sec Make:- Siemens/L&T/DJB approved
Indicating lights LED type RYB & On/OFF, Make:-L&T/Havells/DJB approved
Changeover switch on load for capacity 100 Ampere.
Auxiliary Relay Make:- Siemens/L&T/DJB approved
S/o of RCCB, 3 phase 415 volt AC , 40 Amp rating . Make:-Havells/ L&T/Siemens /DJB approved
S/o of 1.5 sq mm flexible 4 core copper wire for control wiring for remote push button station Make:- Finolex/Havells/Gloster/DJB approved
S/o of 6 sq mm flexible single core copper wire for control wiring for power wiring Make: Finolex/ Havells/ Gloster/ DJB approved
Providing of aluminium armoured cable of size : 3.5 core X 95 sq mm Make :- Havells/Gloster/ Grandly / DJB approved
Automatic phase sequence contractor 50 Amp with automatic manual facility corrector with control accessories auto manual switch, single phasing protection delay power supply etc.
SMPS power supply 24 volt DC & Auxiliary Rely and electronic card system with on delay clutch & off delay clutch .
Pump start stop button station installed at individual hydrant with wiring and other accessories required as per site .
Fixing of the above components in panel enclosure with terminal blocks, channels, ferrules, thimble, support insulator on bus bar required hard wares, control wiring in 1.5 sq mm single copper wire complete in all respect with the help of dash fastner etc. as per site requirement.
Loading ,unloading by crane or heavy labour and cartage up to site cleaning & dressing the surface for installation of the panel at site on base frame, laying of cable, termination of cable both incoming & out going
Testing & commissioning of panel, as per required parameters with relevant IS Testing of the panel prior to switching on as follow :- (1) Continuity and earth testing (2) Meggaring of all equipments for phase to phase, neutral to body, neutral to earth and phase to earth. (3) Checking for all tightness of nut and bolts (4) Alignments of doors etc. (5) Interlocking tests.
M G Traders and Engineers
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .