GE (AF) Kalaikunda PO Kalaikunda Air Field Dist Paschim Medinipore St West Bengal Pin 721303
REPAIR/MAINTENANCE OF DG SETS, FIRE ALARM SYSTEM, LIGHTING CONDUCTOR/ARRESTOR, DIFFERENT TYPES OF EARTHING INFRASTRUCTURE AND MISC WORKS AT AFS SALUA UNDER GE (AF) KALAIKUNDA.
2021_MES_454382_1
8676/E8
Open Tender
Electrical and Maintenance Works
Works
270 days
AF STN SALUA
As per Tender Documents
7 documents required · 7 mandatory
₹500
Yes
GE (AF) Kalaikunda
₹80,000
Yes
9 Aug 2021
24 Jun 2021
16 Jul 2021
24 Jun 2021
15 Jul 2021
3 Jul 2021
Amount
Comprehensive maintenance of DG set of capacity 20 KVA with cleaning, oiling, greasing, minor repairs of any kind to diesel engine & AC generator including replacement of spare parts like clamps, tappet cover gasket, water pump gasket, radiator gaskets, minor repair of self starter, alternator/dynamo, adjustment of carbon brush of any type, adjustment of AVR & Tappets, replacement of battery brass terminal, repair to battery post, replacement of toggle switches, repairing to wiring in control panel of Gen set using existing size of copper wire, cleaning of diesel storage tank, replacement of level indicator, outlet valves as required & connected accessories through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by GE, complete all as specified and as directed.(Make: Cummins/Kriloskar/Ashok Leyland) Note :- Spares required for replacement will be measured & paid separately 2. Each maintenance job shall be covered period of 09 Months
Comprehensive maintenance of DG set of capacity 30 KVA with cleaning, oiling, greasing, minor repairs of any kind to diesel engine & AC generator including replacement of spare parts like clamps, tappet cover gasket, water pump gasket, radiator gaskets, minor repair of self starter, alternator/dynamo, adjustment of carbon brush of any type, adjustment of AVR & Tappets, replacement of battery brass terminal, repair to battery post, replacement of toggle switches, repairing to wiring in control panel of Gen set using existing size of copper wire, cleaning of diesel storage tank, replacement of level indicator, outlet valves as required & connected accessories through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by GE, complete all as specified and as directed. ( Make: Cummins/Kriloskar/Ashok Leyland) Note :- Spares required for replacement will be measured & paid separately 2. Each maintenance job shall be covered period of 09 Months
Comprehensive maintenance of DG set of capacity 82.5 KVA with cleaning, oiling, greasing, minor repairs of any kind to diesel engine & AC generator including replacement of spare parts like clamps, tappet cover gasket, water pump gasket, radiator gaskets, minor repair of self starter, alternator/dynamo, adjustment of carbon brush of any type, adjustment of AVR & Tappets, replacement of battery brass terminal, repair to battery post, replacement of toggle switches, repairing to wiring in control panel of Gen set using existing size of copper wire, cleaning of diesel storage tank, replacement of level indicator, outlet valves as required & connected accessories through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by GE, complete all as specified and as directed. (Make: Cummins/Kriloskar/Ashok Leyland) Note :- Spares required for replacement will be measured & paid separately 2. Each maintenance job shall be covered period of 09 Months
Comprehensive maintenance of DG set of capacity 125 KVA with cleaning, oiling, greasing, minor repairs of any kind to diesel engine & AC generator including replacement of spare parts like clamps, tappet cover gasket, water pump gasket, radiator gaskets, minor repair of self starter, alternator/dynamo, adjustment of carbon brush of any type, adjustment of AVR & Tappets, replacement of battery brass terminal, repair to battery post, replacement of toggle switches, repairing to wiring in control panel of Gen set using existing size of copper wire, cleaning of diesel storage tank, replacement of level indicator, outlet valves as required & connected accessories through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by GE, complete all as specified and as directed. ( Make: Cummins/Kriloskar/Ashok Leyland) Note :- Spares required for replacement will be measured & paid separately 2. Each maintenance job shall be covered period of 09 Months
Comprehensive maintenance of DG set of capacity 250 KVA with cleaning, oiling, greasing, minor repairs of any kind to diesel engine & AC generator including replacement of spare parts like clamps, tappet cover gasket, water pump gasket, radiator gaskets, minor repair of self starter, alternator/dynamo, adjustment of carbon brush of any type, adjustment of AVR & Tappets, replacement of battery brass terminal, repair to battery post, replacement of toggle switches, repairing to wiring in control panel of Gen set using existing size of copper wire, cleaning of diesel storage tank, replacement of level indicator, outlet valves as required & connected accessories through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by GE, complete all as specified and as directed. (Make: Cummins/Kriloskar/Ashok Leyland) Note :- Spares required for replacement will be measured & paid separately 2. Each maintenance job shall be covered period of 09 Months
Overhauling/calibration of fuel injection pump including replacement of service kit, bearing, spring washers, copper washers, benjo bolt, gasket.washer manifold,injection nozzles ,plunger complete for the following capacities complete as specified and as directed. (Note: other spares required for replacement will be measured and paid as supply only) Make: Cummins/Kriloskar/Ashok Leyland)
(a) DG Set of capacity – 250 KVA
(a) DG Set of capacity – 125/82.5 KVA
(b) DG Set of capacity – 30/20 KVA
Overhauling/calibration of injector nozzles including replacement of nozzles, washers, etc. and pressure setting as required for DG Sets of following capacities and replacement of timing shaft with coupling complete all as specified and as directed. NOTE: Spare parts shall be measured and paid separately under seperate items .
(a) DG Set of capacity – 250 KVA
(b) DG Set of capacity – 125/82.5 KVA
(c) DG Set of capacity – 30/20 KVA
Overhauling of self starter including replacement of carbon, armature coil, field coil, bush and bendix pinion and other related components to the following capacities DG sets :NOTE: Spare parts shall be measured and paid separately under seperate items.
(a) DG Set of capacity - 250 KVA
(b) DG Set of capacity – 125/82.5 KVA
(c) DG Set of capacity – 30/20 KVA
Overhauling of dynamo including replacement of armature coil, carbon set, field coil, clutch patti, bearing etc and other related items as required and re-fixing the same on mountings and testing complete for following capacities DG sets : Note: Spare parts shall be measured and paid separately under seperate items .
(a) DG Set of capacity - 250 KVA
(b) DG Set of capacity – 125/82.5 KVA
(c) DG Set of capacity – 30/20 KVA
Dismantling the radiator and cleaning the same completely and detect the leakage/breakage and repair the radiator by soldering/brazing and testing complete all as specified and as directed for the following capacity of DG Sets :-
(a) DG Set of capacity - 250 KVA
(b) DG Set of capacity – 125/82.5 KVA
(c) DG Set of capacity – 30/20 KVA
Supply for pouring of coolant suitable for radiator for Kirloskar/Jackson make engine as per the requirement of time to time as per OEM specification for various capacities of DG Set (Make : SERVO/CASTROL/PUROCOOL)
Supply and filling in replacement of Engine oil 20W40 210 litres or as per OEM specification to top up/ refilling of all DG set as per the direction of Engineer-in-charge.(Make Gulf/Castrol/Volvalin)
Supply& fixing the following items in DG set of 250 KVA capacity.
(a) Diesel filter element as per OEM specification
(b) Oil Filter element as per OEM specification
(c) Air cleaner hose pipe with clamp as per OEM specification
(d) Radiator hose pipe with clamp as per OEM specification
(e) Safety control valve as per OEM specification
(f) flexible pipe for fuel pump to PT pump with banjo washer , nut bolt as per OEM specification
(g) flexible pipe for Disel tank to filter with banjo washer , nut bolt as per OEM specification
(h) Air cleaner Filter as per OEM specification
(l) Automatic voltage regulator as per OEM specification
Supply & fixing the following items in DG set of 125/82.5 KVA capacity as per OEM specification
(a) Diesel filter element.
(b) Oil Filter element
(c) Air cleaner hose pipe with clamp
(d) fuel indicator assembly
(e) flexible pipe for diesel tank to filter with banjo washer, nut bolt
(f) Radiator hose pipe with clamp
(l) Automatic voltage regulator
(j) Air cleaner Filter
Supply the following items in DG set of 30/20 KVA capacity. as per OEM specification
(a) Diesel filter element
(b) Oil Filter element
(c) Air cleaner hose pipe with clamp
(d) Radiator hose pipe with clamp
(e) flexible pipe for fuel pump to PT pump with banjo washer , nut bolt
(f) flexible pipe for Disel tank to filter with banjo washer, nut bolt
(g) By pass filter
(h) Automatic voltage regulator
(j) Air cleaner Filter
Dynamo spare parts of 250 KVA as per OEM specification
(a) Dynamo rectifier assembly
(b) Dynamo plate set (set of two pcs)
(c) Dynamo carbon (Set of 2 Pcs)
Dynamo spare parts of 125/82.5 KVA
(a) Dynamo Rotor assembly
(b) Dynamo rectifier assembly
(c) Dynamo starter assembly
(d) Dynamo bearing 6211ZZ
(e) Dynamo carbon (Set of 2 Pcs)
Dynamo spare parts of 30/20 KVA
(a) Dynamo rectifier assembly
(b ) Dynamo cutout assembly
(c) Dynamo starter assembly
(d) Dynamo bearing 6211ZZ
(e) Dynamo carbon (Set of 2 Pcs)
FIP spare parts of capacity 125/82.5 KVA as per OEM specification
(a) Delievery valve
(b) FIP plunger
FIP spare parts of capacity 30/20 KVA as per OEM specification
(a) Delievery valve
(b) FIP plunger
Injector spare parts of capacity 125/82.5 KVA as per OEM specification
(a) Injector nozzle
(b) Injector washer
Injector spare parts of capacity 30/20 KVA as per OEM specification
(a) Injector nozzle
(b) Injector washer
Material ,labour and repair/replacement of canopy hinges of enclouser type DG Sets any size as per OEM specification all as specified and directed by Engg-in-charge.
Material , labour for replacement external Battery charger suitable for 12 V DC battary as per OEM specification all as specified and directed by Engg-in-charge.
Supply & connect in replacement of battery 150 AH, 25 plate with initial Charger Specific gravity 12.60 of 12 volts complete all as directed by Engineer-in-Charge. (Make:- EXIDE/Amron or equivalent
Supply & connect in replacement of battery 180 AH, 25 plate with initial Charger Specific gravity 12.60 of 12 volts complete all as directed by Engineer-in-Charge. (Make:- EXIDE/Amron or equivalent
Supply and fixing Battery lead incluiding clamp both ends as per OEM specification complete .
M&L for opening of DG set AC and DC control panel mounted on engine & AMF Panel for servicing, cleaning, replacement of unserviceable spare parts with and including complete wiring of AMF Panel for 250 KVA DG Sets as per OEM specification complete all as dirtected
M&L for opening of DG set AC and DC control panel mounted on engine & AMF Panel for servicing, cleaning, replacement of unserviceable spare parts with and including complete wiring of AMF Panel for 82.5/125 KVA DG Sets as per OEM specification complete all as dirtected
M&L for opening of DG set DC and AC control panel mounted on engine & AMF Panel for servicing, cleaning, replacement of unserviceable spare parts with and including complete wiring of AMF Panel for 20/30 KVA DG Sets cas per OEM specification complete all as dirtected
Taking down carefully diesel engine driven generating set capacity of the following capacitiy after decoupling alternator, dismantling parts of diesel engine for top overhauling & inspection of rocker level bush, cylinder head valve, valve seat, oil chamber gasket, piston ring, cylinder liner, connecting rod, bearing, connecting rod brush, handling conveyance of defective cylinder head to nearest workshop for decarbonising, valve grinding, polishing, seat cutting & fitting, re-assembling of parts including replacement of engine oil as per exterior grade/specification and unserviceable parts, miscellaneous parts such as nuts, bolts, washers, screws, circlip, benjo bolt, copper washers etc. and re-fixing engine assembly in original position and testing for smooth operation for the following capacities of DG set complete all as specified and as directed. (Note: other spare parts required for replacement will be measured and paid as supply only) Make of DG Set: Kirloskar/ Ashok Leyland
(a) DG Set of capacity – 250 KVA
(b) DG Set of capacity -125/82.5 KVA
(c) DG Set of capacity - 30/20 KVA
Supply only power contactor 4 pole for 250 KVA DG AMF Panel as per OEM recommendation/ specfication complete
Supply only SMPS for 250 KVA DG Set AMF panel as per OEM recommendation/ specfication complete
Supply only PCB board for 250 KVA DG AMF Panel as per OEM recommendation/ specfication complete
Supply only relay/LVM for 250 KVA DG AMF Panel as per OEM recommendation/ specfication complete
Supply only Battary charger for 250 KVA DG AMF Panel as per OEM recommendation/ specfication complete
Supply only controller circuit for 250 KVA DG AMF Panel as per OEM recommendation/ specfication complete .
Supply only power contactor 4 pole for 125/82.5 KVA DG AMF Panel as per OEM recommendation/ specfication complete
Supply only SMPS for 125/82.5 KVA DG Set AMF panel as per OEM recommendation/ specfication complete
Supply only Battary charger for 125/82.5 KVA DG AMF Panel as per OEM recommendation/ specfication complete
Supply only power fuse link with breaking capacity 80 KA for 125/82.5 KVA DG AMF Panel as per OEM recommendation/ specfication complete
Supply only PCB board for 125/82.5 KVA DG AMF Panel as per OEM recommendation/ specfication complete .
Supply only relay/LVM for 125/82.5 KVA DG AMF Panel as per OEM recommendation/ specfication complete
Supply only controller circuit for 125/82.5 KVA DG AMF Panel as per OEM recommendation/ specfication complete .
Supply only power contactor 4 pole for 30/20 KVA DG AMF Panel as per OEM recommendation/ specfication complete
Supply only SMPS for 30/20 KVA DG Set AMF panel as per OEM recommendation/ specfication complete
Supply only relay/LVM for 30/20 KVA DG AMF Panel as per OEM recommendation/ specfication complete
Supply only PCB board for 30/20 KVA DG AMF Panel as per OEM recommendation/ specfication complete.
Supply only Battary charger for 30/20 KVA DG AMF Panel as per OEM recommendation/ specfication complete
Supply only controller circuit for 30/20 KVA DG AMF Panel as per OEM recommendation/ specfication complete.
Decoupling alternator from the DG set engine, transportation to nearest workshop for repair, dismantling parts of alternator i.e. stator, rotor, slip ring, MX unit/AVR, carbon brass with holder for rewinding of armature with suitable size of super enamelled copper wire including heating varnishing providing required insulating materials for alternator cap 30 KVA as per OEM recommendation/ specfication complete. Note: Spare parts deemed to be included in quoated rates
Rewinding of MX unit with suitable size of super enamelled copper wire including heating varnishing providing required insulating materials for alternator cap 30 KVA as per OEM recommendation/ specfication complete.Note Spare parts deemed to be included in quoated rates
Supply only back filling compound (Magnesium sulphate ) in existing earth pits through G I pipes as per site requirment all as directed .
M&L for carrying out brazing to earthing strip joint between earthpit and test point after removing the nut bolt ,scraping the strip,preparing the surface all as specified by Engr-in-charge
M & L in repair Air termination, single pointed, copper rod 12mm dia and 300 mm long complete fixed on wall/roof including fixing arrangement all as specified and directed..
Supply and fixing copper strip of size 20 x3.15 mm as earth continuity conductor or main earthing lead fixed on "V" type porcelain insulator ( ceramic bus bar support insulator off white colour of min size of 36 mm width x 60 mm length with 36 mm width bus bar mounting base) saddle to wall, buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required including copper strip brazing to each joints and connected with by providing brass nut bolts and washers all as specified and directed by Engr in Charge
Supply and fixing in repair copper strip of size 32 x 6 mm as earth continuity conductor or main earthing lead fixed on "V" type porcelain insulator ( ceramic bus bar support insulator off white colour of min size of 36 mm width x 60 mm length with 36 mm width bus bar mounting base) saddle to wall, buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20 x 3 mm copper strip brazing to each joints and connected with by providing brass nut bolts and washer all as specified and directed by Engr in Charge.
S&F in replacement of Porcelain insulator of existing size for isolation of conductor from the building wall by providing 15cm long fastners complete all as specified.
S&F for Test Point junction box of suitable size with terminal block, IP 66 weather proof including four hexagonal anticorrisove screws for out door installation including provn of Test points as per IS specifications of shape and size 75x75x25 mm drilled and screwed incl 3 nos 8 mm dia 25 mm long hex head screw, made out of phospher bronze mounted and fixed on box with suitable grouting arrangements Suitable nut bolts, washers of various size as approved, complete duly fixed with ground/earth/roof conductor rigidly complete all as specified.
M&L for earthing complete with copper earth plate electrode 600x600x3.15mm thick buried directly in ground (Earth plate not less than 3.0 M in deep below ground level) with top edge of the plate not less than 2.4m below normal ground level connected to copper earth strip 20X3 mm by means earth lead by brass nut bolts washer including brazing the copper strip with copper plate as shown in electrical plate No 3 connected to earthing test point all as specified and directed including necessary earth work in any type of soil/hard rock strata and PCC 1:3:6 type B1 for chamber and RCC chamber cover 50mm thick in lieu of CI cover and copper strip protected by 40mm GI pipe light grade complete. Including filling of agriculture soil brought from out side defence land for earth pit as directed by Engineer-in-charge. Excavation and removal of excavated soil and filling of agriculture soil brought from out side defence land shall be included in the overall rate quated. No extra payment shall be paid. Note :- (a). The quoted rate includes the rate of Magnesium Sulphate of 40Kg per earth pit poured with salt and charcoal (To obtained earth resistance value and prepare test sheet of newly constructed earth pit shall be responsibility of contractor and submitted to Engineer- incharge ) (b). If the desired earth resistance not obtained the earthing shall be re-done by contractor without any extra cost to Govt . (c) 40 mm dia light grade GI pipe for earth lead strip protection and earth strip up to 7.5 Mtr incl in quoted rates beyond that both are measured and paid separetely. All the joints in copper strip and connection with Earth Plate to be welded through brazing and in addition by proving brass nut bolt and washer are deemed to be included in the unit rate. 5. Cost of brazing/ welding and brass nut bolts and washer are deemed to be included in the unit rate.6. Cost includes disposal of excavated soil from site and clear the site before completion of work at that location
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose/hard soil ,complete all as specified and directed.
Returning filling in any type of soil, including, spreading levelling watering and well ramming in layers not exc. 25 cm complete all as specified and directed.
Removing excavated soils to a distance not exceeding 50 Metres and depositing where directed at a level n. exc. 1.5 M above the starting point complete all asspecified and directed.
Taking out old existing galvanized steel water tubing 20mm bore including connected fittings & fixtures from trenches/wall/floor complete all as specified and as directed
All as per item No. 62 above but 25mm bore complete all as specified and as directed
All as per item No. 62 above but 40mm bore complete all as specified and as directed
All as per item No. 62 above but 50mm bore complete all as specified and as directed
Supply, laying, jointing and testing of 50 mm bore galvanised steel water tubing, medium grade with all fittings and laid in trenches/walls/floors including all ISI marked fitting complete all as specified and as directed.
All as per item No. 66 above but 40mm bore complete all as specified and as directed
All as per item No. 66 above but 25mm bore complete all as specified and as directed
All as per item No. 66 above but 20mm bore complete all as specified and as directed
Demolition of cement concrete (unreinforced) of any description and in any position not otherwise specifically provided for in ground/ floors complete all as specified and as directed.
Materials and Labour for plain cement concrete (1:3:6) Type D-2 using 40 mm graded aggregate in foundations, filling and mass concrete complete all as specified and directed.
Materials and Labour for plain cement concrete (1:3:6) type C1 using 20 mm graded aggregate in lintels up to 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings up to 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded or chamfered angles and throating, as directed including necessary from work complete all as specified and directed.
Supply and Erect, steel tubular swaged poles complete with cast iron base plate,finial taper plug, bolts, nuts & screws as specified, type 410 SP-31 (9.00 Metres Long), complete all as specified and directed.
Supply, installation, commissioning and testing of LT Bus Bar Feeder Piller Box type factory made CPRI approved weather, dust & vermin proof Feeder Piller Box outdoor type having provision provision of double door openings with rubber beadings cubical type of size 1.0x0.75x0.40 Mtr or as directed by the manufacturer, made out of 3.15 mm CRCA sheet compartmentalized with rubber beadings, angle iron 50 x 50 x 6 mm shall be used for making legs/ frame, duly including applying two coats of Powder coated paint over a coat of red oxide zinc chrome primer over exposed external & internal surfaces, including provn of Aluminium Busbar, including provn of Aluminium Busbar 400 Amps including ,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 160 Amps and 25 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting: 6-10 x In,complete and suitable insulators and cable gland for terminal connections of cables and fixed with suitable size nuts and botls of size as directed including provn of PCC Platform of suitable size with PCC 1:2:4 as per manufacturer,s all as directed by the Engineer-in-charge. Note: The schematic diag of LT Panels shall be approved by GE before procurement.
Material, T&P and labour for Cleaning of under ground Sewage Sumps of Sewage Pump house having minimum well after plugging all entries of sewage to inside the sumps carefully with necesary plugging materials, Complete using the cleaning devices as per rule 5 and protective gear and safety devices as per rule 4 of the Prohibition of Employment as Manual Scavengers and their Rehabilitation Rules, 2013 and de-watering of sumps with the help of necessary pumping sets, Cleaning and removing of all silt, dust, sediments to a separate temporary sumps made by contractor for dispossal of sewage materils from the main sewage sump and washing cleaning the bottom floor and side walls with bleaching powder solution, remove the plugs from the inlets, and writing the date of cleaning with white paint over black base paint, etc. all as directed by Engineer-in-Charge.
S&F Lighting Stike Counter as per existing specification suitable for fixing in lighting protection system complete all as directed by Engineer-in-Charge.
Supply and fix Detectors Complying with and type certified to EN - 45 Addressable type smoke detector Photoelectric /Optical with base with self built intelligence Addressable type multisensor detector with heat and smoke combination as per IS: 11360 as per OEM specfication
Supply and fix in replacement of Fire alarm control panel complying with BS EN 54 Double loop panel of capacity from 99 detectors & 99 modules upto 200 detector and modules as per OEM specfication
Supply only electronically addressable intelligent resettable type manual call point with mounting base complying with EN 54 standard and LPCB approved with the specifications as appended below:- a)Power- 24V, ≤ 0.6 mA (Standby Current) ≤1.8mA (Alarm Current) b) Class A , c) Initiating Mode- Pressing the action plate manually Resuming Mode-Manually Resumed by a special Key, d) Ingress Protection IP-43 & Material-ABS Make:as per OEM specification
Supply and fix in replacement of Addressable sounder as per OEM specfication or atleast 50 minutes with sound level 65db to 120db measured at 1.5 m with sound output variation of +5db 500m range complete all as specified and directed.
Supply and fix in replacement of Control Relay Module as per OEM specfication
Supply and fix in replacement of Isolator Module as per OEM specfication
Supply and fix in replacement of Respons Indicator as per OEM specfication
Comprenesive maintenance and repair including renewal/replacement of defective parts of all existing fire detection system complete consisting of addressable fire control panel 5 Nos., Conventional Fire Alarm Panel 07 Nos., Remote Terminal Unit panels 20 Nos., smoke/heat detector, response indicator, sounder, Manual call Point, Amlifier 03 nOS., Loud speaker, Loop isolator, Zone monitor module, Modem etc. to make 100 % serviceability of the complete incl checking of fire detector, checking the connection of batteries, the alarm function of control and indicating eqpt be checked by the operation of trigger device in each zone as described, the system installed in Fire station every month during first or last week as directed by engineer-in-charge. Note:- (i) Cost of new components shall be paid for separately under relevant item (ii)Works shall be executed through specialist firm who was sufficient experienced on the scope of work. Before commencement of work, approval shall be obtained from the GE (ii) Service Engineer shall visit minimum once in a month to every panel and take serviceability certificate duly signed by the user. (iii). Each maintenance job shall be covered period of 09 Months
Comprenesive maintenance and repair including renewal/replacement of defective parts of all existing Electrically operated motorised double leaf sliding gate at Tech gate and Ops gate including finding out any defects through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by GE, complete all as specified and as directed and making the system functional by replacing/ repairing the defected parts to the entire satifcation of the Engineer-in-charge. Note : Spares required for the maintenance shall be deemed to be included in quotated rate only PCB shall be measured and paid seperately .
Supply Only PCB for the existing specification / OEM Specification motor of electrically operated gate complete
NATIONAL CONSTRUCTION CO
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .