| 1 | L1₹13.0 LAccepted-AOC PLOT NO 1134 1196 MORIVALI VILLAGE TAL AMBARNATH DIST THANE AMBERNATH 421505 | AMBERNATH | THANE | MAHARASHTRA | 421505 | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹15.9 L+₹2.7 L (20.5%)Rejected-Finance | L2 | Rejected-Finance BEING NOT L1 | |
| 3 | L3₹19.4 L+₹6.2 L (47.2%)Rejected-Finance | L3 | Rejected-Finance BEING NOT L1 | |
| 4 | L4₹21.6 L+₹8.4 L (63.7%)Rejected-Finance | L4 | Rejected-Finance BEING NOT L1 |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
26 Jan 2022, 6:00 pmClosed
GE AF OJHAR
GE AF OJHAR
REPAIR MAITANENCE OF DG SETS AND AMF PANEL AND MISC ITEMS AT AF STATION OJHAR
2021_MES_496947_1
8839/E8
Open Tender
Civil Works
Item Rate
335 days
OJHAR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF OJHAR
₹30,000
Yes
18 Feb 2022
23 Dec 2021
28 Jan 2022
24 Dec 2021
26 Jan 2022
14 Jan 2022
Amount
Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 250/200 KVA such as injector & valve tappet setting, checking of vibration damper, checking turbocharger, oil leakage, tightening mounting screws & nuts, replacment of filters & oil, checking inlet & Exhaust manifold capscrews, checking of fan hub & water pump, removing the existing engine oil, clean the oil sump and refilling with directed quantity of new oil & coolant top up etc complete entire satisfaction of Engr-in-charge.(Total -2 nos DG Set) Make;- Cummins
(a) Supply only lubrication oil filter for 250/200 KVA DG sets as per existing make/model/type
(b) Supply only paper bypass filter for 250/200 KVA DG sets as per existing make/model/type
(c )Supply only fuel filter for 250/200 KVA DG Sets as per existing make/model/type
(d) Supply only air cleaner inner for 250/200 KVA DG Sets as per existing make/model/type
(e) Suply only air cleaner outer for 250/2000 KVA DG Sets as per existing make/model/type
Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 62.5/75/82.5 KVA such as injector & valve tappet setting, checking of vibration damper, checking turbocharger, oil leakage, tightening mounting screws & nuts, replacment of filters & oil, checking inlet & Exhaust manifold capscrews, checking of fan hub & water pump, removing the existing engine oil, clean the oil sump and refilling with directed quantity of new oil & coolant top up, etc complete entire satisfaction of Engr-in-charge.(Total -5 nos DG Set) Cummins/Kirloskar/Greaves
(a) Supply only lubrication oil filter for 62.5 / 75 /82.5 KVA DG sets as per existing make/model/type
(b) Supply only paper bypass filter for 62.5 / 75 /82.5 KVA DG sets as per existing make/model/type
© Supply only fuel filter for 62.5 / 75 /82.5 KVA DG Sets as per existing make/model/type
(d) Supply only air cleaner inner for 62.5 / 75 /82.5 KVA DG Sets as per existing make/model/type
(e) Supply only air cleaner outer for 62.5 / 75 /82.5 KVA DG Sets as per existing make/model/type
Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 40 KVA such as injector & valve tappet setting, checking of vibration damper, checking turbocharger, oil leakage, tightening mounting screws & nuts, replacment of filters & oil, checking inlet & Exhaust manifold capscrews, checking of fan hub & water pump, removing the existing engine oil, clean the oil sump and refilling with directed quantity of new oil & coolant top up, etc complete entire satisfaction of Engr-in-charge.( Total -7 nos DG Set) Make Cummins/Kirloskar/Greaves
(a) Supply only lubrication oil filter for 40 KVA DG sets as per exissting make/model/type
© Supply only fuel filter for 40 KVA DG Sets as per existing make/model/type
(d) Supply only air cleaner inner for 40 KVA DG Sets as per existing make/model/type
(e) Supply only air cleaner outer for 40 KVA DG Sets as per existing make/model/type NOTE FOR ITEM NO 1 to 17:- (i) Maint spares parts and engine oil etc shall be measured and paid separately in relavent items of schedule and any other check as per menufacturer's instructions & minor repair as directed by Engineer-in-charge also deemed in the quoated rate of schedule
Taking down radiator from Gen set of capacity 200/250 KVA after disconnecting the water connecting pipe and descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete and replacement of coolant solution and hose radiator with clips complete all as directed by Engineer-in-Charge.
Taking down radiator from Gen set of capacity 62.5/75/82.5 KVA after disconnecting the water connecting pipe, descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete and replacement of coolant solution and hose radiator with clips complete all as directed by Engineer-in-Charge.
Taking down radiator from Gen set of capacity 40 KVA after disconnecting the water connecting pipe, descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete and replacement of coolant solution and hose radiator with clips complete all as directed by Engineer-in-Charge.
Supply only coolant concentrate Make : Valvoline
Dismantling and taking out Dynamo/alternator assembly of 12 Volts/24 Volts from the DG sets replacing the spare parts such as carbon brushes, springs, spring holders, brushes, bearings or any other part required for full functioning of machine and fixing and testing complete as specified and directed by Engineer-in-Charge
Dismantling and taking out dynamo/alternators from DG set for rewinding and taking out the old coil, cleaning thoroughly and wound with new super enameled copper cord of existing size and gauge, varnishing, drying, heating as per manufacturer norms and fixed with dynamo/alternator properly testing and commissioning suitabl;e for40 to 62.50 KVA all as specified and directed by Engineer-in-Charge
S&F in replacement of radiator hoses of any size and any capacity of DG set and fixed properly with new jublee clips, clamps, nuts and testing complete as directed by Eng-in-charge
Dismantling and taking out the FIP (PT Pump Assy) for repairing by replacing the worn out gasket, filter, suction valve, discharge valve and fixing the same after calibration and testing complete as directed by Engr-in-charge of capacity 200 KVA / 250 KVA/ DG set. Note : Repairing & Calibration shall be carried out by authorised dealers only.
As per item No 25 above but for DG set of capacity 82.5KVA/75KVA/62.5KVA
As per item No 25 above but for DG set of capacity 40KVA
M&L in repair overhauling/calibration of injector assembly for any make/model/capacity of DG sets including renewal of wornout parts such as copper gasket, injector nozzle and testing complete as directed by Engr-in-charge Note :- Repairing/Calibration shall be carried out by authorised dealer only.
Supply and fixing in repair AVR unit for 250/200 DG Set & testing etc complete as specified and directed by Engr-in-charge Make : Kirloskar/Cummins
Supply and fixing in repair AVR unit for 82.5KVA/75KVA/62.5KVA DG Set and testing complete as directed by Engr-in-charge . Make : Kirloskar/Cummins
Supply and fixing in repair AVR unit for 40KVA DG Set and testing etc complete as directed by Engr-in-charge . Make : Kirloskar/Cummins
Dismantling and taking out the water body pump assembly complete from the DG set upto capacity 75 KVA at site and Supply and fixing of new water body pump complete.
Supply & fix battery terminals made of brass superior quality incl taking down old one etc complete as directed.
Dismantling and taking out the dfective self starter assembly of any capacity (12V/24V) form the DG set and re-fixing the same after repair works including replacing the spare parts such as carbon brushes, springs, spring holder bushes, bearings, or any other spare part not mentioned herein but essentially required for proper functioning of the starter assembly complete all as specified and directed.
Dismantling and taking out self starter from DG set and taking out unserviceable old coil , cleaning thoroughly slot and rewinding the starter with super enameled copper conductor of existing size and gauge incl varnishing drying, heating and re-fixing the same after repair incl testing all as specified and directed.
Supply & Fixing flexible pressure hose for lubricant oil and fuel for any size/capacity/model/make of DG set incl taking down old one etc complete all as specified.
Supply & Fix belt fan drive for DG sets of 250/200 KVA capacity incl taking down old one etc as directed..
S & F seafty switch suitable for any model/make of DG set upto 75 KVA.
S & F water temperature sensor suitable for any model/make of DG set upto 250 KVA.incl taking down old as directed.
S & F water temperature cut out suitable for any model/make of DG set upto 250 KVA.incl taking down old as directed.
Supply and fix ignition switch and key for DG sets of 250/200 KVA capacity incl taking down old one as directed.
Dismantling the radiator of 82.5 to 40 KVA DG set its position and soldering of copper pipes, where leakage incl rectifying leaks & cleaning radiator and PVC hose and fitting the same place and testing complete as specified
Material and labour for draining out old engine/lubrication oil from chamber of the DG sets, cleaning of chamber thoroughly and filling new engine/lubrication oil of grade 20W40 complete all as specified and directed.
Supply and fixing in repair rotating rectifier assembly for 250/200 KVA DG set of any make and model.
Supply and fixing in repair rotating rectifier assembly upto 82.5/75/62.5/40 KVA DG set of any make and model.
Supply and fixing rectifier diode for 250/200 KVA DG sets as per exising make/model/ size incl taking down old one etc complete as specified and directed
Supply and fixing rectifier diode for DG sets upto 82.5 KVA capacity as per exising make/size/ model incl takding down old one etc complete as specified and directed
S & F battery leads 95 Sqmm copper cable unth as reqd at site etc complete as specified and directed by Engr-in-charge
S & F asbestos rope 20mm dia for tightly covered the silencer exhaust pipe etc complete as specified and directed
Material and labour for dismantling and taking out the alternator above 40 KVA but upto 82.5 KVA capacity from the DG sets from coupling and opening the stator & rotor including cleaning of dust from windings for proper ventilation, renewal of carbon brushes with brush holder and re-assembling the rotor & stator complete including applying suitable greasing & oiling of bearing & moving parts and refixing the same on its position and testing complete all as specified and directed.
Supplying, fixing lead acid battery 12 volts, 180 AH suitable for DG set including initial charging (Model No. FXPO-MHD1800 Exide New express or equivalent of other specified make) including connection & testing and taking down old one etc complete all as specified and directed.
Supplying, fixing lead acid battery, 12 volts, 110 AH with lead acid suitable for DG set including initial charging (Make- EXIDE / AMRON ) including connction and testing incl taking down old one complete as specified and directed .
Supply only distilled water for batteries.
Supply and fixing turbo kit suitable for 40 to 82.5 KVA DG sets.
Supply, fixing and testing Self Starter 12 Volt, DC for DG Set of capacity upto 82.5 KVA (Make of DG Set Kirloskar/Cummins as per existing size and make) complete all as specified and directed.
Supplying & fixing Exhaust Gasket as per existing make/model/type of capacity of DG set 62.5/75/82.5 KVA DG Set incl taking down old one etc complete as specified and directed
Supplying & fixing Exhaust Gasket as per existing make/model/type of capacity of DG set 40 KVA DG Set incl taking down old one etc complete as specified and directed Note : 1 to 57 - (i) DG set should be repair within 12 hours after receiving the massage from department. If the contractor fail the repair of DG set within perioud, the penality should be paid 250/per hours to department. (ii) Any minor material/spare reqd for proper functioning wheather not cover in CA Contractor will provide the same for functioning of D G set.
Material and labour for servicing/repair of AMF Panel of DG Set up to 250 KVA capacity for smooth functioning of the same with renewal / repair of AMF panel, wiring control timer, engine starting relay, contact point repal, AMF relay, HRC fuse of existing rating etc complate for DG sets installed at various pockets under AGE E/M Ojhar all as specified and as directed. Note:- The rate quoted by the contractor shall be deemed to included the cost of spares/relays or any other part not mentioned herein but essential required to make the AMF panel completely functional and no extra payment shall be made for the same.
Supply and fixing engine start relay of suitable capacity as required at site Mak- L&T or as approved by AO.
Supply and fixing under voltage relys make- PIC/EC
Supply and fixing auxilary contact suitable for 62.2/75 DG Sett AMF pane incl taking down old one etc complete as specified and directed .
Supply and fixing Batter charger 12 V,DC, 2 Amp complete as specified and directed .
Supply and fixing Fuse (F 8) with Holder 15 Amp complete as specified and directed .
Supply and fixing Fuse (F 1 to F 7) with Holder 02 Amp complete as specified and directed .
Supply and fixing thermal over load relay suitable suitable for MN 30-40 relay rang incl taking down old one etc complete as specified and directed .
Supply and fixing Genset Control unit display type ( rating DSE452201) as per existing make, model and capacity etc suitable for up to 82.5 KVA DG Set incl taking down old one etc complete as specified and directed .
Supply and fixing Foam sound obsorver as per existing make, suitable to fit in DG set door inner side up to 82.5 KVA DG Set incl taking down old one etc complete as specified and directed .
Supply and fixing Inter face card as per existing make, model and capacity etc suitable for up to 82.5 KVA DG Set incl taking down old one etc complete as specified and directed .
Supply and fixing push button as per existing make, model and capacity etc suitable for 40/62.5 KVA DG Set incl taking down old one etc complete as specified and directed .
S&F off load changeover switch 63 Amps TPN with sheet metal enclosure ,side handle operated, 50 Hz, fixed to walls/ panels with suitable size clamps, nuts, bolts and washers complete all as specified and directed including making connections and testing of following capacities:- Make - L&T/Schneider/C&S/indoasian/HPL
All as per Item No 71 above but 100 Amps
All as per Item No 71 above but 200 Amps
Supply & Fixing in repairs "ON LOAD" type Change over switch 200 Amps TPN front handle operated, on existing LT/AMF Panels, suitable for three phase, 415V, 50 Hz AC supply of following ratings :- Make - L&T/Schneider/C&S/indoasian/HPL
All as per Item No 74 above but 100 Amps
All as per Item No 74 above but 63 Amps
S&F MCCB TP of capacity 125 Amps, 50 Hz, 415V with rupturing capacity of 16 KA with fixed thermal magnetic settings including spreader terminals complete incl taking down old one etc complete all as specified and directed.
S&F MCCB TP of capacity 100 Amps, 50 Hz, 415V with rupturing capacity of 16 KA with fixed thermal magnetic settings including spreader terminals complete incl taking down old one etc complete all as specified and directed.
S& F XLPE insulated PVC sheathed stranded aluminium conductor, heavy duty, conforming to IS 1554 Part I / ISI marked, including suitabe size cable glands & lugs, cables to be laid in trenches, fixed along the poles /or through GI pipe laid under floors road etc complete of sizw 95 sqmm 3.5 core incl taking down old one as specified and directred
Supply and fix in repair Isolator TPN 63 Amps 415 volts 10 KA. Make : Legrand/ HPL/ L & T.
Supply and fix in repair MCB SP 6 to 32 Amps 240 volts 10 KA C series. Make : Standard/ HPL/L & T.
Supply and fix in repair MCB SPN 32 Amps 240 volts 10 KA. Make : Standard/ HPL/ L & T.
Current Transformer with CT ratio 100/5 as per sample.
Contactor FP, 3 Phase 63 A FP , AC as per sample
M&L for maintenance of DG set Canopy door by taking down door from DG set denting the damaged portion of MS door and weilding the same if reqd for any desire shape and cleaning the old painted srface of Door and painting with synthetic enamel paint as existing colour to achive good finish.
Dismantling and taking out the dfective door lock assembly of any capacity of the DG set and re-fixing the same after repair works including replacing the defective spare parts as reqd at site. complete all as specified and directed.
DIAMOND ENTERPRISES
SHRI SULAI ELECTRICALS
KALWA TRANSPORTER AND SUPPLIERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .