Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance F 20 SHASTRI NAGAR DELHI52 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance NULL | Admitted-Finance |
Tender Value
₹2.9 L
Closing Date
22 Sept 2021, 2:00 pmClosed
Ex. Engineer(Elect.)/CNZ
C-Block, Defence Colony, New Delhi 110024
Improvement of E.I and Fans and Rewiring of Dispensary, Near Community Center Amar Colony in ward No. 59-S under Central Zone.
2021_SDMC_88517_1
EE(Elect.)/CNZ/2021-22/23-03
Open Tender
Electrical Works
Item Rate
30 days
C-Block, Defence Colony, New Delhi
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Exempted
23 Sept 2021
16 Sept 2021
23 Sept 2021
16 Sept 2021
22 Sept 2021
16 Sept 2021
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. Group C
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.(a)2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.(a)4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. a) 3x2.5
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. a) 6x2.5
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.(a) 3 x 4 sq. mm
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. a) 6 x 4
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 1 & 2 Module (75 mmX75 mm)
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as requiredb. 4 Module (125 mmX75 mm)
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required 8 Module (125mmX125mm)
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. A) 20 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.a) 25 mm
Supplying and fixing following modular switch/ socket on theexisting modular plate & switch box including connections but excluding modular plate etc. as required (a) 5/6 A switch
Supplying and fixing suitable size GI box with modular plateand cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plateand cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 5/6 &15/16A modular switch, connections etc. as required.
Installation of exhaust fan in the existing opening ,including making good the damage ,connection,testing,commissioning etc.as required.(a) Up to 450 mm sweep
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)(a). 12 way, Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)a) 8 way (4 + 24), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a) Single pole
Supplying and fixing following rating ,double pole,24o volt,isolator in the existing MCB DB complete with connections,testing and commissioning etc. as required.(a) 63 amps
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 A
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
P/F 6 SWG dia GI wire on surface or in recess for loop earthing along with existing surface / recess conduit/submain wiring cable as reqd.
Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete as required.
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Up to 35 sqmm
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size on wall surface as reqd Upto 35 sq. mm (clamped with 1mm thick saddle)
Supply of 12'' ( 300 mm )sweep 1400 rpm exhaust fan heavy duty complete with shutter,blade etc as required
S.I.T.C. of 1200 mm sweep, BEE 5 star rated Ceiling fan with Brush less direct current (BLDC) motor, class of insulation: B, 3 Nos.blades, 30 cm long downrod, 2 Nos canopies, shackle kit, safety rope, copper winding, Power factor not less then 0.9, service value (CMM/W) minimum 6.85, Air delivery minimum 215 6.85,350 rpm (tolerance as per IS :374-2019, THD less than 10% remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, earthing etc, complete as reqd.
S/I/T/C of Surface mounting CRCA housing 36W LED luminaire with acrylic cover diffuser with following specifications including fixing on existing wall/recess with connections as reqd. (a)Total system wattage = 36 watt +/- 5% (b )Luminous efficacy >=95 lumens /watt. (c)Power factor >=0.
S/I/T/C of LED Tube Type luminiare 20 Watt rating complete with polycarbonate housing batten integrated electronic driver prewired with high efficient LEDs with the following: (a) Total System Wattage 20 Watt +/- 5%. (b) Luminous Efficieny lumens/watt >= 95 (c ) Power Factor>= 0.95
SITC of single phase monoblock pumpset complete with all accessories workable of 240 volts 50 Hz AC supply 1.0 HP (0.75 KW) single phase pumpset head from 6-34 meter suction and delivery 25x25mm.
Supply of XLPE insulated and PVC sheathed Al. conductor armoured cable 1.1 KV grade confirming to IS 7098 as required. 2 x 10 sq.mm
S/I/T/C of 60 watt LED Flood Light luminaire fitted with lens made of pressure die cast aluminium housing & toughened glass cover complete with the following specifications as required with IP 66 protection .(a) Total System Wattage 60 Watt +/- 5%. (b) Luminous Efficieny >=100 (c ) Power Factor>= 0.95 (d) Protection Class- IP-66
P & F of Hot Press Sheet Moulded Compound (SMC),fire retardant (Temp. resistanceup to 200 C),IP-55 weather proof pole box of inner dimension 200 mmx160 mmx98 mm (NS) complete with suitable arrangement for fixing of 2 nos.of 6 to 32 amp single pole MCB & 63 A Double pole( MCB/isolator excluded) with neutral link duly shorting on DIN channel with 2 nos.of MS clamps with SS back plate of suitable size with danger monogram property printed on the cover etc. as required.
S.N. Enterprises
GURUNANAK ENTERPRISES
Maanu Electricals
Gautam Electrical
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .