EX.ENGG(E)/Z-III
Kolkata Municipal Corporation, Hudco building 8th floor, 15N. Nellie Sengupta Sarani, Kolkata -700087
SUPPLY, INSTALLATION AND COMMISSIONING OF AIR CONDITIONING SYSTEM AT NEWLY CONSTRUCTED KALIGHAT HAWKERS BUILDING ALONG WITH ASSOCIATED ELECTRICAL RELATED WORKS WITHIN WARD NO. 83 UNDER BR. VIII.
2024_KMC_655662_1
KMC/LTG/Z-III/2023-2024/665
Open Tender
ELECTRICAL WORKS M/R
Item Rate
45 days
KALIGHAT HAWKERS BUILDING
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹2 L
16 Mar 2025
30 Jan 2024
7 Feb 2024
30 Jan 2024
7 Feb 2024
30 Jan 2024
Amount
PART A: Air Conditioning
Supply of TOP Discharge modular type only cooling variable refrigerant volume / flow air conditioner consisting of one outdoor unit and multiple indoor units. Factroy fited with epoxy resin is applied for strong protection from various corrosive external conditions such as salt contamination and air polluiton including fumes from factrories.Moreever the hydrophilic film keeps water from accumulating on the heat exchnagers's fin,minimizing moisture build up and make it more corrosion resistant, the anitcorrission should be third party certified Considering single 22 HP Outdoor due to lake for space for installation,oudtoor should hang with the wall therefore less number of outdoor / less weight considred
Capacity of ODU – 22 HP ( Unit should be capable of delivering 22 HP @ 39 deg C considering deration factors.
For the VRF SYSTEM (COP shall be more than 3.46 and above at AHRI-1230 condition of 35deg C outdoor DB /19 air over condenser coil and should meet LEED rating)
OEM should have own Compressor
22HP Single Outdoor
Ducable type indoor units
Supply, Installation, testing and commissioning of Ceiling suspended ducted type unit suitable for R410A refrigerant. The unit indoor unit shall have necessary filters, cooling coil, electronic expansion valve, fan, fan motor, Condensate drain pump, decorative panels, With all required scaffolding, wired thermostat with digital control unit etc., as per tender drawing and specification.
2.3TR 915 CFM Static 10mm wg
3.02TR 1141 CFM 10mmwg
4.5TR 1801CFM 14mmwg
Coded Remote
Necessary Ref joints, Y -Branches, T- joints, valves for the above indoor units
Installation,testing, commissioning of VRV System
Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/ with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquidlines,all accessories as per specifications etc. as required :
As per approved drawing
Providing & fixing of UPVC Pipe complete with fittings, supports as per specifications and duly insulated with 9 mm thickness "Class O" closed cell nitrile rubber/XLPE complete etc. as required and as per direction of Engineer-in-charge .
40 mm dia
32 mm dia
25 mm dia
20 mm dia
Supply, installation, testing and commissioning of pre fabricated galvanized sheet metal duct including Fixing/holding arrangements, bends/ Guide vanes for supply air system complete with flanges, gaskets & supports etc as per SMACNA standard.
Supply,installation,testing and commissioning of duct thermal insulation with 19 mm thick Nitrile Rubber for indoor supply air ducting.
Supply, installation testing and commissioning of duct acoustic insulation Inside the Duct with Engineered Nitrile Rubber.
Air Distribution Product
Supply, erection, testing & commissioning of Aluminium powder coated Diffuser with VCD
Supply, erection, testing & commissioning of Aluminium powder coated grilles with VCD having flange all around.
Supply, erection, testing & commissioning of Aluminium powder coated Diffuser without VCD
Supply, erection, testing & commissioning of Aluminium powder coated grilles without VCD having flange all around
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc., as per specifications.
Supply & fixing of control cum transmission wiring of Copper Shielded conductor cable along with conduit for looping between indoor & outdoor VRF system & to main Central remote controller system.
SITC of Nitrogen for flusing purpose & making the system commision with all respect to work and check the lead and hold the pressure for minimum 48 Hours .
Supplying & Charging of Top up Refrigerant (R410 A) in the VRF/ VRV system over and above the initially charged refrigerant of the system etc. as required.
Lifting of Outdoor & Indoors
Supply of Canvass connection for the ductable Unit
Misc. Items
PART B: ELECTRICAL WORK
Electrical Cost for installation of Air Conditioner including supply and fixing of Cable, Electrical Panels, distribution Board consisting of MCB, MCCBs etc.
Note: 1) All the above rates should be quoted inclusive of all taxes & duties, LWC as applicable, with cost of maintenance, servicing, supply & replacement of spares for 1 (One) year from the date of commissioning. 2) Total is rounded off to the nearest rupees.
ANAMICA ENTERPRISE
RELIABLE CONSTRUCTION
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .