| 1 | L1₹2.7 CrAdmitted-Finance | ₹2.7 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.8 Cr+₹3.3 L (1.22%)Admitted-Finance | ₹2.8 Cr+₹3.3 L (1.22%) | L2 | Admitted-Finance |
| 3 | L3₹3.0 Cr+₹24.3 L (8.92%)Admitted-Finance | ₹3.0 Cr+₹24.3 L (8.92%) | L3 | Admitted-Finance |
| 4 | Rejected-Technical | - | - | Rejected-Technical DISQUALIFIED |
| Sl No | Description | Qty | Unit | Trade Linkers Associates L2 | CIVICTRA ENGINEERING AND CONSTRUCTIONS L1 | JK Electric Engineers Pvt. Ltd. L3 |
|---|---|---|---|---|---|---|
| 1.00Design, Engineering, Manfacture, Shop Testing, Supply including packing and forwarding, Transportation and delivery at site as per Technical Specifications and approved drawings | ||||||
| 2.00(A) 132 Kv Transformer Bay | ||||||
| 3.00Main Equipments | ||||||
| 4.00 | 3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 2500 Amps of 3 phase, 50 c/s and 31.5KA for 1 second). | 1 | No | 13,75,775.76 ₹13,75,775.76 | 14,32,331 ₹14,32,331 | 12,66,160 ₹12,66,160 Lowest |
| 5.00 | 145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades | 3 | Set | 5,55,655.48 ₹16,66,966.44 | 5,46,905 ₹16,40,715 | 3,66,520 ₹10,99,560 Lowest |
| 6.00 | 145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with Earthing Blades | 1 | Set | 6,33,383.54 ₹6,33,383.54 | 6,23,409 ₹6,23,409 | 4,33,160 ₹4,33,160 Lowest |
| 7.00 | Single phase, 50 c/s 145KV Current Transformers (800-400-200/1-1-1-1-1 A or as per site specifications), 31.5KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA, 3No.PS Core,01 No.5P10 & 01 No.0.2S | 3 | No | 2,60,874.26 ₹7,82,622.77 | 2,56,766 ₹7,70,298 | 2,13,248 ₹6,39,744 Lowest |
| 8.00 | Neutral Current Transformer with Current Rating (800-400-200/ 1A) and VA Burden 15VA Ratio as per Site requirement 02 No.PS Core for 132kv side | 1 | No | 1,56,464 ₹1,56,464 | 1,54,000 ₹1,54,000 Lowest | 2,13,248 ₹2,13,248 |
| 9.00 | Single Phase 50 c/s, outdoor metal oxide gapless type, 120KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all associated accessories, auxiliaries. | 3 | No | 78,028.8 ₹2,34,086.4 | 76,800 ₹2,30,400 | 70,638 ₹2,11,914 Lowest |
| 10.00 | 132KV Control and Relay Panel for Transformer bay simplex/Duplex as per site requirement completely wired including Substation automation supporting IEDs/numerical relays including Differential relay, Directional 3 O/C 1 E/F protection and numerical communicable REF protection relay,overload Fluxing Protection , LBB Protection with IEC 61850 / SCADA Compatibility | 1 | No | 13,76,351.83 ₹13,76,351.83 | 13,54,677 ₹13,54,677 | 8,99,640 ₹8,99,640 Lowest |
Tender Value
₹3.1 Cr
EMD Value
₹6.2 L
Closing Date
21 Apr 2025, 2:00 pmClosed
Executive Engineer TLMD-II Pampore
Office of the Executive Engineer TLMD-II Pampore
Augmentation of 132/33KV GSS Tethar from 50 MVA to 70 MVA by way of addition of old 20 MVA Power Transformer and Miscellaneous works
2025_PDD_274172_1
TLMD-II/18 of 2024-25
Open Tender
Electrical Works
Turn-key
180 days
Grid Station Tethar
Please refer Tender documents.
7 documents required · 7 mandatory
₹5,500
Yes
Executive Engineer TLMD-II Pampore
₹6.2 L
Yes
Superintending Engineer O and M Circle ist JKPTCL
30 Aug 2025
12 Mar 2025
22 Apr 2025
12 Mar 2025
21 Apr 2025
20 Mar 2025
12 Mar 2025 - 19 Mar 2025
19 Mar 2025
Amount
Design, Engineering, Manfacture, Shop Testing, Supply including packing and forwarding, Transportation and delivery at site as per Technical Specifications and approved drawings
(A) 132 Kv Transformer Bay
Main Equipments
3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 2500 Amps of 3 phase, 50 c/s and 31.5KA for 1 second).
145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades
145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with Earthing Blades
Single phase, 50 c/s 145KV Current Transformers (800-400-200/1-1-1-1-1 A or as per site specifications), 31.5KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA, 3No.PS Core,01 No.5P10 & 01 No.0.2S
Neutral Current Transformer with Current Rating (800-400-200/ 1A) and VA Burden 15VA Ratio as per Site requirement 02 No.PS Core for 132kv side
Single Phase 50 c/s, outdoor metal oxide gapless type, 120KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all associated accessories, auxiliaries.
132KV Control and Relay Panel for Transformer bay simplex/Duplex as per site requirement completely wired including Substation automation supporting IEDs/numerical relays including Differential relay, Directional 3 O/C 1 E/F protection and numerical communicable REF protection relay,overload Fluxing Protection , LBB Protection with IEC 61850 / SCADA Compatibility
132KV Post Insulators Solid Core Type/ Polymer Type, Power Frequency Withstand Voltage 275KVP Dry lightning impulse withstand voltage ± 650 (KVP)
STRUCTURES
Galvanized Structures (MS)
Galvanized Nuts and Bolts
Power and Control cables
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
2 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
4 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
4 Core, 16 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complet
Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self?supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns.
Conductor and hardware fittings
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN.
Single Suspension Fittings For Single 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Single Suspension Fittings For Twin 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected.
T Clamps 500mm2 /500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P I Clamps 0.5 made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P G Clamps 0.5 made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Earthwire 7/3.15 mm wire for ground conductor
Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS ground wire
CABLE TRAYS/CABLE RACKS/ACCESSORIES
Cable Trays of size 400mm x 3000mm made of M.S angles 40x40x6mm,40x6 Flat.
Cable Trays of size 300mm x 2500mm made of M.S angles 40x40x6mm,40x6 Fla
Cable Ducts With Covers as per the design of existing
Main Duct of Size 1200mm x 1200mm with 6 mm M.S Chequered Trench Covers of size 1300x500 mm
Main Duct of Size 1200mm x 1200mm with 75mm Concrete Covers grade M15 of size 1300x500 mm
Sub Main Duct of Size 600mm x 600mm with 75mm Concrete Covers grade M15 of size 700x500 mm
Tee off Duct: 150mm sand filled HDPE pipes from Sub main to Equipments in the outdoor area
(B) Installation of 132/33 Kv three phase Power Transformer
STRUCTURES
Galvanized Structures
Galvanized Nuts and Bolts
Power and Control cables
3.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
CONDUCTOR AND HARD WARE FITTINGS
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
(C) 33 Kv Transformer Bay
Main equipments
33KV VCB (36 KV, 2000 Amps of 3 phase, 50 c/s and 25KA for 3 sec) outdoor type with all accessories and auxiliaries
36kV, 50c/s , 2500 Amp, 25kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades
Single phase, 50 c/s 36KV Current Transformers (1200-600-300 /1-1-1 A or as per site specifications) , 25KA for one second, rated dynamic current 25KA(peak), Class A insulation, Burden 20 VA,2 No.PS Core, 01 No.5P10/20,01 No.0.2S Class
Single Phase 50 c/s, outdoor metal oxide gapless type, 30KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all associated accessories, auxiliaries
33KV Control and Relay Panel for Transformer Bay Simplex completely wired including Substation automation supporting IEDs/numerical relay with IEC61850/SCADA Compatibility
STRUCTURES
Galvanized Structures
Nuts and Bolts
Power and Control cables
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
2 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
4 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self?supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns.
CONDUCTOR AND HARD WARE FITTINGS
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Single Suspension Fittings For Single 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected.
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition
Spacers For Twin 500mm2 must be one-piece construction of aluminum alloy of an approved type without any projection, cuts, abrasions etc. or chattering parts and shall conform to IS:10162
P I Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P G Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Earthwire 7/3.15 mm
Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS ground wire
CABLE TRAYS/CABLE RACKS/ACCESSORIES
400mm x 3000mm made of MS angle 40x40x6mm,40x6 flat
300mm x 2500mm made of MS angle 40x40x6mm,40x6 f
Set of spares for 132 & 33 Kv bay equipments supplied as per BOQ and as mentioned in SBD
Handling, Storage, Preservation, Erection, Testing and commissioning of equipments and material including all comsumables required like glands, Ferrules, Lugs, Printed sleeves, cable ties, cable glands, Tags, minor cutting, wielding works etc. complete in all respects.
(A) 132 Kv Transformer Bay
Main Equipments
3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 2500 Amps of 3 phase, 50 c/s and 31.5KA for 1 second).
145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades
145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with Earthing Blades
Single phase, 50 c/s 145KV Current Transformers (800-400-200/1-1-1-1-1 A or as per site specifications), 31.5KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA, 3No.PS Core,01 No.5P10 & 01 No.0.2S
Neutral Current Transformer with Current Rating (800-400-200/ 1A) and VA Burden 15VA Ratio as per Site requirement 02 No.PS Core for 132kv side
Single Phase 50 c/s, outdoor metal oxide gapless type, 120KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all associated accessories, auxiliaries.
132KV Control and Relay Panel for Transformer bay simplex/Duplex as per site requirement completely wired including Substation automation supporting IEDs/numerical relays including Differential relay, Directional 3 O/C 1 E/F protection and numerical communicable REF protection relay,overload Fluxing Protection , LBB Protection with IEC 61850 / SCADA Compatibility
132KV Post Insulators Solid Core Type/ Polymer Type, Power Frequency Withstand Voltage 275KVP Dry lightning impulse withstand voltage ± 650 (KVP)
STRUCTURES
Galvanized Structures (MS)
Galvanized Nuts and Bolts
Power and Control cables
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
2 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
4 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
4 Core, 16 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complet
Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self?supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns.
Conductor and hardware fittings
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN.
Single Suspension Fittings For Single 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Single Suspension Fittings For Twin 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected.
T Clamps 500mm2 /500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P I Clamps 0.5 made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P G Clamps 0.5 made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Earthwire 7/3.15 mm wire for ground conductor
Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS ground wire
CABLE TRAYS/CABLE RACKS/ACCESSORIES
Cable Trays of size 400mm x 3000mm made of M.S angles 40x40x6mm,40x6 Flat.
Cable Trays of size 300mm x 2500mm made of M.S angles 40x40x6mm,40x6 Fla
Cable Ducts With Covers as per the design of existing
Main Duct of Size 1200mm x 1200mm with 6 mm M.S Chequered Trench Covers of size 1300x500 mm
Main Duct of Size 1200mm x 1200mm with 75mm Concrete Covers grade M15 of size 1300x500 mm
Sub Main Duct of Size 600mm x 600mm with 75mm Concrete Covers grade M15 of size 700x500 mm
Tee off Duct: 150mm sand filled HDPE pipes from Sub main to Equipments in the outdoor area
(B) Installation of old 20 MVA, 132/33 Kv three phase Power Transformer
1. Errection, testing & commissioning of 20 MVA, 132/33 KV three phase power transformer with OLTC, HV & LV Connectors and other required accessories / fittings including filtration and dehydreration of T Oil at GSS Tethar. 2. Loading of Power transformer along with accessories at GSS Awantipora 3. Carriage of transformer along with accessories from GSS Awantipora upto GSS Tethar 4. Unloading of power transformer along with its accessories at requisite site. 5. Extra T Oil of 10 Barrels to be supplied 6. Replacement of damaged Gaskits, OTI,WTI, Breather & MOG etc, if required.
STRUCTURES
Galvanized Structures
Galvanized Nuts and Bolts
Power and Control cables
3.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
CONDUCTOR AND HARD WARE FITTINGS
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
(C) 33 Kv Transformer Bay
Main equipments
33KV VCB (36 KV, 2000 Amps of 3 phase, 50 c/s and 25KA for 3 sec) outdoor type with all accessories and auxiliaries
36kV, 50c/s , 2500 Amp, 25kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades
Single phase, 50 c/s 36KV Current Transformers (1200-600-300 /1-1-1 A or as per site specifications) , 25KA for one second, rated dynamic current 25KA(peak), Class A insulation, Burden 20 VA,2 No.PS Core, 01 No.5P10/20,01 No.0.2S Class
Single Phase 50 c/s, outdoor metal oxide gapless type, 30KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all associated accessories, auxiliaries
33KV Control and Relay Panel for Transformer Bay Simplex completely wired including Substation automation supporting IEDs/numerical relay with IEC61850/SCADA Compatibility
STRUCTURES
Galvanized Structures
Nuts and Bolts
Power and Control cables
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
2 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
4 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self?supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns.
CONDUCTOR AND HARD WARE FITTINGS
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Single Suspension Fittings For Single 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected.
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition
Spacers For Twin 500mm2 must be one-piece construction of aluminum alloy of an approved type without any projection, cuts, abrasions etc. or chattering parts and shall conform to IS:10162
P I Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P G Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Earthwire 7/3.15 mm
Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS ground wire
CABLE TRAYS/CABLE RACKS/ACCESSORIES
400mm x 3000mm made of MS angle 40x40x6mm,40x6 flat
300mm x 2500mm made of MS angle 40x40x6mm,40x6 f
Civil works including Design, Supply, Execution and preperation of drawings
Design & laying of Earth Mat as per approved design for 132KV Yard, 33 KV Yard and 132/33 Kv Transfrmer including cost of electrodes , excavation of pits, fixing of risers, yard to yard connecting the mesh with LAs , NCT and Transformer body etc. (614 RM)
Earth work excavation
Manual carriage of disposable earth beyond 100mts (60% of Excavated earth)
Mechanical carrige of Disposable earth at an average lead of 5 Km
Supply of good and soft earth including filling, levelling & Royality etc
Mechanical carrige of good earth at an average lead of 20 Km
Manual carriage of good earth from unloading site to site of work
Loading and unloading of earthing material
Laying of 100mts of MS Flat/ Round steel
Surface cleaning ,jointing by welding etc
Driving of Spikes
Providing of Steel, galvanised Flat iron 75mmx12mm/50mmx6mm) and 40mm dia round steel bars
laying of 132KV Foundations Viz; 4 No Isolator, 1 No SF6 Breaker, 3 No CT, 3 No LA, 1 No NCT,6 No PI in 132 Kv Transformer Bay and 33KV foundations Viz; 4 No Isolator, 1 No VCB, 3 No CT, 3 No LA in 33 Kv Transformer Bay as per approved drawings
Earth work in excavation by mechanical means (Hydraulic excavator) over areas ( exceedind 30 cm in depth 1.5 mtr in width as well as 10 sq.m on plan ) including disposal of excavated earth, lead upto 50 m. & , lift upto 1.50 m disposad earth to be levelled and neatly dressed in All kinds of soil
Providing and laying of lean pad 1:4:8 with 40mm crushed stone aggregate 4.0x4.0x0.10
Form work
Providing and laying of RCC conc. 1:1.5:3 (M20) with 20mm bajri
Mech.transport of construction material average lead 20 km
20mm bajri
40mm bajri
Manual carriage of construction of material from unloading site to site of work lead 100 mtr
20mm bajri
40mm bajri
Back filling
Excavation of good earth in soft soil
Mech carriage of good earth av lead 20km
Manual carriage of good earth from unloading site to site of work av distance 100 mtr
Manual carriage of disposable soil upto loading site av distance 100 mtr
Mech transportation of disposable soil av lead 3 km
Providing of tor steel reinforcement including cutting , bending & binding
Manual carriage of cement Av. 100 mtr
Manual carriage of steel
Providing & fixing of stubs as per approved drawing
LAYING of 5 RM RAIL TRACK FOR 50 MVA TRANSFORMER
Excavation in earth work (all sorts)
Close Timbering
Lean Pad 1: 4 :8 with 40 mm bajri
Concreting M-15 1: 1.5:3
Steel work
Form work For steel shuttering
Carriage by Mech. Transport Av. Lead 20 KM
Bajri 20 mm
Bajri 40 mm
Carriage of Surplus excavated material Av.distance 3 KM
Manual carriage Av Distance 100 Mts.
Bajri
Disposable earth
Carriage of cement 100mtr
Carriage of steel
Back filling of earth
MS Rail 90 LB (2x40)
M S Angle 22 RM
Welding Rod
Oxygen Gas Cylinder
Acetylene Gas
Hire Charges for welding Set 3 phase 15 KVA
Unloading of M S Rails, Angle iron & other material
Carriage of Rail
Fixing/ Welding of U Lugs with Beam at an interval of 900 mm on both sides
Measuring, cutting & placing of rails On Lugs along with alignments
Leveling & welding of rails with Lugs on both sides of Lugs .
Fixing of Angle iron with Web of rail along the length Including cutting & straightening etc
Construction of 50 MVA 132/33KV TRANSFORMER FOUNDATION
Earth work excavation all sorts (125 cum)
Shuttering and centering
Steel
SCI pipe 100 mm dia
Rail assembly
Brick Masonry
Plaster 15 mm in 1:4 mix
Carriage of material 20km av by Mech Transport
Bajiri
Bricks
Steel
Cement
Carriage of material at an Av. Lead of 100mt
Bajiri
Bricks
Steel
Cement
Construction of fire Protection Wall at Grid StationTethar
Earthwork in excavation by manual means in trenchs for foundations , drains , pipes , cables etc ( exceeding 1.5 m in width ) and for shafts , wells ,cesspits and the like not exceeding 10 sqm on plan , depth upto 1m from cutting edge ,disposed earth to be levelled and neatly dressed in all kinds of soil
Providing and laying of Soling stone
Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering. All work upto plinth level in 1:4:8 (1 cement:4 coarse sand:8 graded stone aggregate 40mm nominal size). Crushed.
Reinforced cement concrete work in walls( any thickness), including attached piliasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts, etc upto floor five level excluding cost of centring, shuttering, finishing and reinforcement. 1:2:4 (1 cement:2 coarse sand:4 graded stone aggregate 20mm nominal size). Crushed.
Centring and shuttering including strutting, propping, etc and removal of form for: walls( any thickness) including attached pilliasters, butresses, plinth and string courses
Reinforcement for RCC works including straightening, cutting , bending, placing in position and binding all complete. Thermo-mechanically treated bars
Brick work with common burnt clay F.P.S ( non modular ) bricks of class designation 75 in foundation and plinth in cement mortar 1:6 ( 1 cement : 6 coarse sand )
12 mm thick cement plaster in single coat in cement mortor(1:6) mix
Extra for brick work in superstructure
Carraige of materials from source of supply to site of work, Av Lead 20 Kms
Crusher Aggregate
Bricks
Soling Stone
Concreting and laying of Yard metal in 132KV yard,33KV yard & Transformer Bays (1150 Sqm)
Surface dressing of ground removal of inequalities less than 15cms ( de- vegetation)
Supply & laying stone soling 100mm thick including mechanical from nearest source & mannual carriage
Providing & laying Cement Concreate 1:3:6, 100mm Thick including mechanical from nearest source & mannual carriage
Supply, spreading & levelling of metal Crushed (Aggregate 40 mm size) (1150X0.10) including mechanical from nearest source & mannual carriage
Trade Linkers Associates (BID ID -2354749)
JK Electric Engineers Pvt. Ltd. (BID ID -2355417)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
BOQ.xls
BOQ • 0.43 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .