Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | l1₹30.5 LAccepted-AOC WZ 1000 NANGAL RAYA PANKHA ROAD SOUTH WEST DELHI DELHI 110046 | DELHI | SOUTH WEST DELHI | DELHI | 110046 | ₹30.5 L Quoted ₹30.9 L | l1 | Accepted-AOC BEING LOWEST |
| 2 | l2₹32.4 L+₹1.6 L (5.07%)Rejected-Finance | ₹32.4 L+₹1.6 L (5.07%) | l2 | Rejected-Finance being not lowest |
| 3 | l3₹33.2 L+₹2.4 L (7.65%)Rejected-Finance | ₹33.2 L+₹2.4 L (7.65%) | l3 | Rejected-Finance being not lowest |
| 4 | l4₹35.3 L+₹4.4 L (14.2%)Rejected-Finance A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | ₹35.3 L+₹4.4 L (14.2%) | l4 | Rejected-Finance being not lowest |
| 5 | l5₹36.8 L+₹5.9 L (19.1%)Rejected-Finance | ₹36.8 L+₹5.9 L (19.1%) | l5 | Rejected-Finance being not lowest |
Tender Value
₹47.5 L
EMD Value
₹95,100
Closing Date
5 Jun 2021, 6:00 pmClosed
SHRI ARJUN PATRO,IDSE
GE(U) E/S DELHI CANTT-10
MANNING AND OPERATION OF RECEIVING DISTRIBUTION SUB STNS REPAIR AND REPLACEMENT OF LT DISTRIBUTION PANELWITH CONNECTED WORKS AT THE AREA OF KABUL LINE SUB STATION, NEW MAP SUB STATION OLD MAP SUB STATION BAIRD PLACE SUB STATION AND ASSOCIATED ARE
2021_MES_443257_1
GE ELECT/D-23/2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
334 days
GE(U) E/S DELHI CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE(U) ELECTRIC SUPPLY
₹95,100
Yes
16 Jun 2021
17 May 2021
7 Jun 2021
18 May 2021
5 Jun 2021
31 May 2021
Amount
Maintanance services to be provided for 11 KV Kabul line Sub station as per details as under (a) The installation is main receiving sub station and complaint center minimum 01 electrician shall be provided (per shift) around the clock (24 x 7) . The electrician shall have adequate knowledge of above maintioned job and GE/Engr-in-charge can reject the proposed electrician giving reasoned rejection. No claim shall be admissible on account of rejection of person. (b) Details of equipment :- Transformer step down 11 KV/0.433 KV of capacity 630 KVA capacity -2 Nos, 11 KV 10 pole structure - 01 No, 11 KV VCB - 10 Nos, Battery Bank - 01 No, LT Panel - 02 Nos and Capacitor Panel - 02 Nos (c) The following checking, testing, supervision shall be carried out by electrician in respect of equipments mentioned at para (b) above:-(i) Recording of all parameters of system as per indication of all equipments installed in the log sheet as directed by ngr-in-charge round the clock on daily basis. (ii) Maintainance of fault register (iii) Maintainance of shutdown register (iv) Proper operation of 11 KV Breaker (v) Giving of Shutdown by draw out of trolley of breaker. (vi) Proper operation of 11 KV GO DO. (vii) Fixing of burnt out fuse on GO of 11 KV 4/6/8/10 pole structure. (viii) Checking of LED indication for breaker ON, OFF, Trip, Spriing charge, trip circuit healthy on daily basis. (ix) Checking of annunciatore, hooter, indicators, meters, TNC switch, emergency trip push button, MCB for AC DC isolation,heater, thermostate on daily basis (x) Checking of status of Main protection numerical relay Auxillary protection relays such as trip circuit supervision relay.(xi) Attending of all complaint of the Sub station area. (xii) Cleaning of dust & foreign particles on and around the panel, loose connection earthing connection in the sub station. (xiii) Testing of earth resistance of all earthing as directed by Engr-in-charge. (xiv) Checking of DC voltage of system as directed by Engr-in-charge.
Note : (i) The contractor will ensure suitable repalcement of electrician while on leave/weekly holidays and Wages for the same deemed to be included in the quoted rate. (ii ) The contractor shall ensure that electricians/ operator always be present in each shift. In case of absence of any worker the penalty @ Rs 100.00 per hours per electricians/ operator shall be imposed on the contractor. (iii) The contractor shall be responsible for maintaining the complete area (i.e. inside boundary wall ) such as building , hard standing , foothpath etc in neat and clean position . All necessary T&P for cutting /cleaning of grass and vegitation will be arranged by contractor without any extra cost. (iv) The contractor shall provide uniform , raincoat, protective clothing such as hand gloves ,helmet, safety belt , first aid box and shoes etc to all persons on duty and the cost of the same is deemed to be included in quoted rate. (v) Person employed should be working experience of working on HT and LT Installation. (vi) The contractor shall provide log sheet and maintain the the same on daily basis and the cost of the same is deemed to be included in quoted rate.
Worker's wage per person per day per shift (inclusive of GST as applicable)
Employees Provident Fund as per existing rules (Prescribed Rate of EPF as applicable on (minimum wages without GST ) + GST Rate as applicable on Prescribed Rate of EPF as applicable on (minimum wages without GST )
Employees state insurance as per existing rules. (Prescribed Rate of ESI as applicable on (minimum wages without GST) + GST Rate as applicable on Prescribed Rate of ESI as applicable on (minimum wages without GST )
Contribution of Bonus as per existing rules. (Prescribed Rate of BONUS as applicable on (minimum wages without GST) + GST Rate as applicable on Prescribed Rate of BONUS as applicable on (minimum wages without GST)
Over head & profit on total of srl No 1.02 to 1.05 as applicable.
LWC as per existing rules on total of srl no 1.02 to 1.06. The bidder should note that the minmum wages including all statutory provisions as mentioned in item no 1.02 to 1.06 are exclusive of GST for calculating of labour cess. Refer Sch 'A'Note No 33 (e) on Page No 17 of Tender Document.
NOTE For Item 1 and sub items :- (a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, ie proof of payment. (b)The rate quoted shall not be less than minimum wages as notified by Government of India / State Government / Local body whichever is higher including all statutory provisions such as EPF,ESIC,Bonus,taxes etc as applicable and also not less than applicable rates for contribution of employer towards EPF,ESIC, BONUS and LWC under respective heading /subitems. In case the rates quoted are less than the minimum wages as notified by the Government of India / State Government / Local body whichever is higher including all statutory provisions such as EPF,ESIC,Bonus,taxes etc on the last due date of bid submission. his tender will be treated as non bonafide and will not be considered for acceptance.In such case,the lowest bidder shall be determined from amongst the valid/bonafide bids only. (c) 'NIL' or 'Zero' quoting against OH & Profit will be treated as 'Non-bonafide'.
(d) Contractor is required to quote upto two digits after decimal place or otherwise it will be consdered by rounding off to two digits after decimal place in accordance with Rules for Rounding off of Numerical Values in accordance with IS:02 OF 1960(Revised 2016) of BIS. (e) Any variation in minimum wage, liability of EPF/ESIC/Bonus/LWC/GST shall be adjusted for reimbursement/recovery as under:- (i) Variation in minimum wage including other related statutory provisions shall be adjusted in terms of Condition 63 of GCC (IAFW-2249). (ii)Variation in percentage/rate of GST and LWC shall be adjusted as per instructions in Annexure XVI of MES Manual on Contracts which deals with ‘Reimbursement/Refund on Variation in Taxes Directly Related to Contract Value’
Maintanance services to be provided for 11 KV Baird Place Sub station as per details as under:- (a) The installation is main receiving sub station and complaint center minimum 01 electrician shall be provided (per shift) around the clock (24 x 7) . The electrician shall have adequate knowledge of above maintioned job and GE/Engr-in-charge can reject the proposed electrician giving reasoned rejection. No claim shall be admissible on account of rejection of person. (b) Details of equipment :- Transformer step down 11 KV/0.433 KV of capacity 1000 KVA capacity -1 Nos, 11 KV VCB - 07 Nos, Battery Bank - 01 No, LT Panel - 02 Nos and Capacitor Panel - 01 Nos (c) The following checking, testing, supervision shall be carried out by electrician in respect of equpments mentioned at para (b) above:- (i) Recording of all parameters of system as per indication of all equipments installed in the log sheet as directed by ngr-in-charge round the clock on daily basis. (ii) Maintainance of fault register (iii) Maintainance of shutdown register (iv) Proper operation of 11 KV Breaker (v) Giving of Shutdown by draw out of trolley of breaker. (vi) Proper operation of 11 KV GO DO. (vii) Fixing of burnt out fuse on GO of 11 KV 4/6/8/10 pole structure. (viii) Checking of LED indication for breaker ON, OFF, Trip, Spriing charge, trip circuit healthy on daily basis. (ix) Checking of annunciatore, hooter, indicators, meters, TNC switch, emergency trip push button, MCB for AC DC isolation,heater, thermostate on daily basis (x) Checking of status of Main protection numerical relay Auxillary protection relays such as trip circuit supervision relay (xi) Attending of all complaint of the Sub station area. (xii) Cleaning of dust & foreign particles on and around the panel, loose connection earthing connection in the sub station. (xiii) Testing of earth resistance of all earthing as directed by Engr-in-charge. (xiv) Checking of DC voltage of system as directed by Engr-in-charge.
Note : (i) The contracotor will ensure suitable repalcement of electrician while on leave/weekly holidays and Wages for the same deemed to be included in the quoted rate. (ii ) The contractor shall ensure that electricians/ operator always be present in each shift. In case of absence of any worker the penalty @ Rs 100.00 per hours per electricians/ operator shall be imposed on the contractor. (iii) The contractor shall be responsible for maintaining the complete area (i.e. inside boundary wall ) such as building , hard standing , foothpath etc in neat and clean position . All necessary T&P for cutting /cleaning of grass and vegitation will be arranged by contractor without any extra cost. (iv) The contractor shall provide uniform , raincoat, protective clothing such as hand gloves ,helmet, safety belt , first aid box and shoes etc to all persons on duty and the cost of the same is deemed to be included in quoted rate. (v) Person employed should be working experience of working on HT and LT Installation. (vi) The contractor shall provide log sheet and maintain the the same on daily basis and the cost of the same is deemed to be included in quoted rate.
Worker's wage per person per day per shift (inclusive of GST as applicable)
Employees Provident Fund as per existing rules (Prescribed Rate of EPF as applicable on (minimum wages without GST ) + GST Rate as applicable on Prescribed Rate of EPF as applicable on (minimum wages without GST )
Employees state insurance as per existing rules. (Prescribed Rate of ESI as applicable on (minimum wages without GST) + GST Rate as applicable on Prescribed Rate of ESI as applicable on (minimum wages without GST )
Contribution of Bonus as per existing rules. (Prescribed Rate of BONUS as applicable on (minimum wages without GST) + GST Rate as applicable on Prescribed Rate of BONUS as applicable on (minimum wages without GST)
Over head & profit on total of srl No 2.02 to 2.05 as applicable.
LWC as per existing rules on total of srl no 2.02 to 2.06 as applicable. The bidder should note that the minmum wages including all statutory provisions as mentioned in item no 2.02 to 2.06 are exclusive of GST for calculating of labour cess. Refer Sch 'A'Note No 33 (e) on Page No 17 of Tender Document.
NOTE For Item 1 and sub items :- (a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, ie proof of payment. (b)The rate quoted shall not be less than minimum wages as notified by Government of India / State Government / Local body whichever is higher including all statutory provisions such as EPF,ESIC,Bonus,taxes etc as applicable and also not less than applicable rates for contribution of employer towards EPF,ESIC, BONUS and LWC under respective heading /subitems. In case the rates quoted are less than the minimum wages as notified by the Government of India / State Government / Local body whichever is higher including all statutory provisions such as EPF,ESIC,Bonus,taxes etc on the last due date of bid submission. his tender will be treated as non bonafide and will not be considered for acceptance.In such case,the lowest bidder shall be determined from amongst the valid/bonafide bids only. (c) 'NIL' or 'Zero' quoting against OH & Profit will be treated as 'Non-bonafide'.
(d) Contractor is required to quote upto two digits after decimal place or otherwise it will be consdered by rounding off to two digits after decimal place in accordance with Rules for Rounding off of Numerical Values in accordance with IS:02 OF 1960(Revised 2016) of BIS. (e) Any variation in minimum wage, liability of EPF/ESIC/Bonus/LWC/GST shall be adjusted for reimbursement/recovery as under:- (i) Variation in minimum wage including other related statutory provisions shall be adjusted in terms of Condition 63 of GCC (IAFW-2249). (ii)Variation in percentage/rate of GST and LWC shall be adjusted as per instructions in Annexure XVI of MES Manual on Contracts which deals with ‘Reimbursement/Refund on Variation in Taxes Directly Related to Contract Value’
Supply, install, test and commissioning in replacement of factory made tested LT panel board of size not less than 1.7 mtr x 1.0 mtr x 1.7 mtr cubical double door compartment outdoor type floor mounted on Medium Channel 75/40 mm suitable for , 415 volts 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated Aluminium bus bar of rating not less than 1.5 times of incoming/ outgoing ACB/MCCBs installed on proceline/ SMC insulator. The panel shall be dust and vermin proof IP -65 class protection and made of 3.15 mm CRCA MS sheet and inner compartment 2.0 mm, 40X40X6 mm thick MS angle iron frame work, powder coated finished over one coat of red oxide on out side surface and painted in side with two coats of red oxide primer and rear opening type with apran for cable entery closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked , 1100 volts grade of appropriate size (but not less than 2.5 sqmm) and comprising of the following including necessary PCC in 1:2:4 type B1 using 20mm graded stone aggregate for platform of suitable size:-
INCOMING:- (i) ACB 4 pole, 1000 Amps Micro processor release manual drawout Adjustable type, 50 Hz, 415 Volts, 50 KA -1 No (ii) Voltmeter digital type - 01 No (iii) Ammeter digital type - 01 No (iv) CT ratio 1000/5 Amp class-1 ISI marked - 01 Set of three (v) Indicating lamp one set of three
OUTGOINGS:- (i) MCCB 4 pole, 320 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 3 Nos (ii) MCCB 4 pole, 200 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermo and Fixed Magnetic setting - 1 No (iii) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermo and Fixed Magnetic setting - 2 No Note :- (i) Location- Behind GE (C )
All as item no-3.00 above (here in before) but as followings:- LT panel board of size not less than 1.4 mtr x 0.6 mtr x1.5 mtr
INCOMING:- (i) MCCB 4 pole, 400 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos (ii) Voltmeter digital type - 01 No (iii) Ammeter digital type - 01 No (iv) CT ratio 400/5 Amp class-1 ISI marked - 01 Set of three (v) Indicating LED lamp, one set of three
OUTGOINGS:- (i) MCCB 4 pole, 160 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 2 Nos (ii) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermo and Fixed Magnetic setting - 2 No (iii) MCCB 4 pole, 63 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermo and Fixed Magnetic setting - 1 No Note :- (i) Location- Near BSO, GE (C )
All as item no-3.00 above (here in before) but as followings:- LT panel board of size not less than 1.0 mtr x 0.9 mtr x 1.5 mtr
INCOMING:- (i) ACB 4 pole, 630 Amps Micro processor release manual drawout Adjustable type, 50 Hz, 415 Volts, 50 KA -1 No (ii) CT ratio 600/5 Amp class-1 ISI marked - 01 Set of three
OUTGOINGS:- (i) MCCB 4 pole, 315 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos (ii) MCCB 4 pole, 250 Amps, 50 Hz, 415 Volts, 35 KA Adjustable Thermal and Fixed Magnetic setting - 2 No (iii) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Fixed Magnetic setting - 1 No Note :-Location- Kabul line area
All as item no-3.00 above (here in before) but as followings:- Panel size should not be less than 1.6 mtr x 0.9 mtr x 1.6 mtr
INCOMING:- (i) ACB 4 pole, 630 Amps Micro processor release manual drawout Adjustable type, 50 Hz, 415 Volts, 50 KA -1 No (ii) CT ratio 600/5 Amp class-1 ISI marked - 01 Set of three
OUTGOINGS:- (i) MCCB 4 pole, 250 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 3 Nos (ii) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermo and Fixed Magnetic setting - 2 No Note :-Near P-108, Kabul Line
All as item no-3.00 above (here in before) but as followings:- Panel size should not be less than 1.1 mtr x 0.6 mtr x 1.5 mtr
INCOMING:- (i) MCCB 4 pole, 400 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos (ii) CT ratio 400/5 Amp class-1 ISI marked - 01 Set of three
OUTGOINGS:- (i) MCCB 4 pole, 200 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 2 Nos (ii) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermo and Fixed Magnetic setting - 1 No Note :-Near P-139, S/F Qtr
All as item no-3.00 above (here in before) but as followings:- Panel size should not be less than 1.45 mtr x 0.5 mtr x 1.45 mtr
INCOMING:- (i) On Load Change Over switch of Cap 630 Amp, 4 pole, 415 Volt, AC-01 No (ii) ACB 4 pole, 630 Amps Micro processor release manual drawout Adjustable type, 50 Hz, 415 Volts, 50 KA -1 No (iii) CT ratio 600/5 Amp class-1 ISI marked - 01 Set of three
OUTGOINGS:- (i) MCCB 4 pole, 320 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 2 Nos (ii) MCCB 4 pole, 250 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Fixed Magnetic setting - 1 No (iii) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Fixed Magnetic setting - 1 No Note :-Kabul Line area
Supply, installing, testing and commissioning in replacement outdoor type stainless steel (SS 316) cubical enclosure compartmentalized exterior and interior mirror type brushed suitable for highly corrosive environment, high creep resistance, better mechanical properties like ductility, yield strength, hardness etc.The enclosure shall be made of 2 mm thick SS 316 sheet. The fixing of double doors shall be on SS hinges with anti-theft provision (the door can’t be removed from enclosure without cutting enclosure). All fabrication/welding shall be done with TIG/MIG or as approved by Engineer in charge suitable for SS 316. Sliding handle and locking arrangement front and rear both side . Enclosure shall be suitable for AC supply system 415 volts 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated Aluminium bus bar installed on proceline/ SMC insulator of rating not less than 1.5 times of incoming/ outgoing ACB/MCCBs . IP-55 class protection and mounted on channel 75 mm welded with panel of SS 316 with 04 Nos foundation bolt of size not less than 20mm dia and 300 mm long. The enclosure shall have provision of cable alley . Cable entry from bottom side including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 sqmm).
Panel size should not be less than 1.8 mtr x 0.9 mtr x 1.7 mtr INCOMING:- (i) ACB 4 pole, 630 Amps Micro processor release manual drawout Adjustable type, 50 Hz, 415 Volts, 50 KA -1 No (ii) Voltmeter digital - 01 No (iii) Ammeter digital type - 01 No (iv) CT ratio 600/5 Amp class-1 ISI marked - 01 Set of three (v) Indicating LED lamp one set of three
OUTGOINGS:- (i) MCCB 4 pole, 320 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos (ii) MCCB 4 pole, 125 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermo and Fixed Magnetic setting - 6 No Note :-Offr Enclave
All as item no-9.00 above (here in before) but as followings:- Panel size should not be less than 1.6 mtr x 0.9 mtr x 1.6 mtr
INCOMING:- (i) ACB 4 pole, 630 Amps Micro processor release manual drawout Adjustable type, 50 Hz, 415 Volts, 50 KA -1 No (ii) Voltmeter digital type - 01 No (iii) Ammeter digital type - 01 No (iv) CT ratio 600/5 Amp class-1 ISI marked - 01 Set of three (v) Indicating LED lamp one set of three
OUTGOINGS:- (i) MCCB 4 pole, 200 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 5 Nos (ii) Space free for one compartment. Note :-Offr Enclave
Note for item No- 3 to 10:- (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimbles. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel paint/ Flourcent refelctive lettring . (iii) All MCCB should be connected to Bus bar directly through expended links (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture. (iv) Costruction of Foundation & taking out of the old UNSV LT Panel with connected cables and reconnection of the cables with new thimbles gland of suitable sizr after installation of new panel are deemed to the above quoted rate.
M&L in replacement Earthing complete with galvanized steel earth plate electrode of size 60cm x 60cm x 6 mm thick, buried directly in ground (earth pit not less than 3.5 m below normal ground level) with top edge of earth plate not less than 2.5m below normal ground level, connected to galvanized strip 32 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other nuts and washers of galvanised iron side complete all as specified, including testing and commissioning complete all as directed. Note : (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in soft/loose soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 type C2 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement 6mm dia both ways as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe medium grade etc. (b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI lead wire and protection pipe upto 7.5 meter beyond the earth plates electrode.
Supply, laying, jointing, testing and commissioning in replacment of LT underground cables 1100 volts grade any size PVC insulated XLPE and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-7098, Part-II marked, laid in trenches/ duct/ under road/ footpath/ etc complete all as specified and directed. Cables of the following size
630 sqmm single core
185 Sqmm 3.5 core
120 sqmm 3.5 core
95 sqmm 3.5 core
25 sqmm 3.5 core
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft/losse soil) for laying of cables or GI pipe and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified. Note : Measurement shall be taken after punning down.
S&F sub class B bricks having minimum compressive strength 75 Kg/ Sq cm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge.
Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge.
Material and labour for fixing/commissioning in replacement for ATS 4 pole of capacity 400 Amps alongwith enclosure and controller with complete including fixing arrangement i.e suitable size of MS flat, nuts, bolts, washer, fixing of LT cables of any size with suitable size of lugs all as specified and directed.
Material and labour for fixing/commissioning in replacement for ATS 4 pole of capacity 200 Amps alongwith enclosure and controller with complete including fixing arrangement i.e suitable size of MS flat, nuts, bolts, washer, fixing of LT cables of any size with suitable size of lugs all as specified and directed.
Material and labour for shifting of LT panel from one site to another site including necessary Foundation , reconnection of LT cables (incoming/outgoing) as directed by Engr In Charge.
Note : (i)contractor should provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge.
ALLIED CONSTRUCTION
R.P. Enterprises
M/s Adhikari construction co.
Rajindera Enterprises
V r traders
Buddham Builders
MV Engineers And Contractors
IK ONKAR ENGINEER AND CONTRACTOR
Ridhi engineers and builders
RUHI ASSOCIATES
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .