Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.7 CrAdmitted-Finance | ₹9.7 Cr | L1 | Admitted-Finance |
| 2 | L2₹10.3 Cr+₹51.0 L (5.23%)Admitted-Finance | ₹10.3 Cr+₹51.0 L (5.23%) | L2 | Admitted-Finance |
| 3 | L3₹11.2 Cr+₹1.5 Cr (15.1%)Admitted-Finance | ₹11.2 Cr+₹1.5 Cr (15.1%) | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | COUNTRY CONSTRUCTION L1 | Nichi Manufacturing Pvt. Ltd. L2 | Ali Mohammad Baba and Sons L3 |
|---|---|---|---|---|---|---|
| 1.00(A)Design, manufacture, supply, packing & forwarding, transportation, unloading, delivery at site of equipments and materials. | ||||||
| 2.00Power Transformer | ||||||
| 3.00 | 50 MVA, 132/33 kV Three Phase Power Transformers with OLTC, SCADA Compatible RTCC, NIFPES , HV and LV connectors and other required accessories and fittings with inbuilt NCTs. | 3 | No | - | - | - |
| 4.00Power and Control cables including termination of the cables | ||||||
| 5.001100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete as per specification. | ||||||
| 6.00 | 4 core, 2.5 sq mm | 1,400 | m | - | - | - |
| 7.00 | 8 core, 2.5 sq mm | 1,400 | m | - | - | - |
| 8.00 | 12 core, 2.5 sq mm | 1,400 | m | - | - | - |
| 9.00 | Cable Glands, ferrules & Lugs for all above cables etc. | 1 | Lot | - | - | - |
| 10.00ANCILLARY ITEMS | ||||||
Tender Value
₹8.8 Cr
EMD Value
₹17.5 L
Closing Date
25 Jun 2020, 4:00 pmClosed
Executive Engineer TLMD-II Pampore
Executive Engineer TLMD-II Pampore
Replacement of 09 no. age old 16.66 MVA single phase Power Transformers by 03 no. 50 MVA 132/33 kV 3 phase Power Transformers at 132/33 kV Grid Station Pampore by way of Design, Manufacture, supply, unloading, installation, testing commissioning
2020_PDD_96004_1
TLMD-II/01 of 2020
Open Tender
Electrical Goods/Equipments
Item Rate
210 days
132/33 kV Grid Station Pampore
Please refer Tender documents.
6 documents required · 6 mandatory
₹9,000
Executive Engineer TLMD-II Pampore
₹17.5 L
Yes
8 Oct 2020
23 Apr 2020
26 Jun 2020
23 Apr 2020
25 Jun 2020
23 Apr 2020
Amount
(A)Design, manufacture, supply, packing & forwarding, transportation, unloading, delivery at site of equipments and materials.
Power Transformer
50 MVA, 132/33 kV Three Phase Power Transformers with OLTC, SCADA Compatible RTCC, NIFPES , HV and LV connectors and other required accessories and fittings with inbuilt NCTs.
Power and Control cables including termination of the cables
1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete as per specification.
4 core, 2.5 sq mm
8 core, 2.5 sq mm
12 core, 2.5 sq mm
Cable Glands, ferrules & Lugs for all above cables etc.
ANCILLARY ITEMS
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps single 500mm2 / single 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
CT clamps suitable for twin 500mm sq ACSR
CT clamps suitable for single 500mm sq ACSR
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Spacers For Twin 500mm2 must be one-piece construction of aluminum alloy of an approved type without any projection, cuts, abrasions etc. or chattering parts and shall conform to IS:10162
Mandatory spares
Set of spares for 132/33Kv power transformer,ancilliary items etc. as per schedule of spares given in SBD.
(B) HANDLING, STORAGE, PRESERVATION, ERECTION (EXCEPT CIVIL WORKS), DEHYDRATION, TESTING & COMMISSIONING OF EQUIPMENTs AND MATERIAL
Power transformer
50 MVA, 132/33 kV Three Phase Power Transformers with OLTC, SCADA Compatible RTCC, NIFPES , HV and LV connectors and other required accessories and fittings with inbuilt NCTs.
Power and Control cables
1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete as per specification.
4 core, 25 sq mm
8 core, 2.5 sq mm
12 core, 2.5 sq mm
Cable Glands, ferrules & Lugs for all above cables etc.
ANCILLARY ITEMS
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps single 500mm2 / single 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
CT clamps suitable for twin 500mm sq ACSR
CT clamps suitable for single 500mm sq ACSR
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Spacers For Twin 500mm2 must be one-piece construction of aluminum alloy of an approved type without any projection, cuts, abrasions etc. or chattering parts and shall conform to IS:10162
Nichi Manufacturing Pvt. Ltd.
Ali Mohammad Baba and Sons
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.38 MB
SBD1TPamp.pdf
Tender Documents • 1.51 MB
SBD2TPamp.pdf
Tender Documents • 3.27 MB
BOQ_181771.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .