Jay Prakash, Staff Officer(EnM), Jagannath Area, MCL PH 06760-269717, 06670-269751(Extn)2023 Fax 06760-269527 E-mail so-enm-jaga.mcl(at)coalindia.in
Repairing and overhauling of 20MVA, 132/33kV Transformer with LV coil replacement for one phase and Replacement of 03 nos. of HV bushing 145kV, 800A at Site with complete testing, commissioning and final charging at 132/33kV Nandira S/s JagannathArea
2023_MCL_269975_1
GM(JA)/EnM/ e-Tender/2023/E-568/61 dated03/02/2023
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
TALCHER
AS PER NIT
5 documents required · 5 mandatory
₹54,900
26 May 2023
6 Feb 2023
27 Feb 2023
7 Feb 2023
24 Feb 2023
7 Feb 2023
7 Feb 2023 - 12 Feb 2023
Amount
Complete Repairing and Overhauling of 20MVA 132/33kV transformer, Make: TARAPUR Transformer Ltd with necessary HV/LV/Tapping Coil Repairing Work at Site
A. Pre commissioning Testing of Transformer: 1. Insulation Resistance Test Polarization Index, 2.Winding Resistance Test, 3.Magnetic Balance Test, 4.Magnetising Current Test, 5. Open circuit test and short circuit test. 5. Tandelta test of bushing and winding SFRA Test, 6. Transformer Turns Ratio, 7. DGA of Transformer, 8. Voltage Ratio Test, 9. Vector Group Test. ( BEFORE & AFTER THE WORK)
C. Machines Required to be arrange at Site by Party: 1. Oil filtration plant (Capacity 12000 lph), 2. Dry air plant (Capacity 90 m3/hr), 3. Heating arrangement, 4. Impact wrench, 5. Empty oil tanker, 6. Vaccum Machine.
D. Dry out of core coil assembly with dry nitrogen/dry air and heaters and checking dew point, vacuum and hot oil circulation with double stage/high vacuum 6KLPH Filter Machine & Filtartion of trf oil upto 10000 ltr in separate storage tank till acheiving the desired BDV and PPM value of OIL. Topup of trf OIL (If required OIL shall supplied by MCL)
E. Final Testing and Succesfully Charging of Transformer with providing desired auxilary Protection System and acessories as per site requirement shall by complied as per INSTRUCTION OF Engineer I/C.
Supply and Erection of LV Coil Replacement/Repair (1 No.) after dismantling of Core and Windings from the Transformer. (SCRAPE COPPER HANDOVER TO PARTY)
Supplying and Erection of HV Bushing 145KV, 800A with all Precommissioning Tests.
Arrangement of Crane for Dismantling and Re-assembly of Core & Coil assembly, Transformer OIL, Arrangement of 03 Phase power Supply & Proper Illumination at Site Shall be Arranged by Department (MCL)
Total impact of GST for the purpose of CTC
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .