Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹22.6 LAccepted-AOC | L-1 | Accepted-AOC L-1 | |
| 2 | L-2₹32.8 L+₹9.2 L (39.1%)Rejected-AOC WZ 88A JANAK PARK HARI NAGAR NEW DELHI 110064 | NEW DELHI | NEW DELHI | DELHI | 110064 | L-2 | Rejected-AOC L-2 | |
| 3 | L-3₹35.4 L+₹11.8 L (50.0%)Rejected-AOC 216 BHARAT NAGAR INDRAPURI BHOPAL MADHYA PRADESH 462021 | BHOPAL | MADHYA PRADESH | 462021 | L-3 | Rejected-AOC L-3 | |
| 4 | L-4₹38.3 L+₹14.7 L (62.5%)Rejected-AOC | L-4 | Rejected-AOC L-4 | |
| 5 | L-5₹39.9 L+₹16.3 L (69.2%)Rejected-AOC | L-5 | Rejected-AOC L-5 |
Tender Value
Refer Docs
EMD Value
₹97,000
Closing Date
18 Dec 2021, 6:00 pmClosed
GE I RND Delhi
MILITARY ENGINEER SERVICES, GARRISON ENGINEER (I) RND, LUCKNOW ROAD, TIMARPUR, DELHI-110054
REPLACEMENT OF FIRE FIGHTING SYSTEM AT JCB BUILDING NEAR METCAFE HOUSE AREA UNDER GE I RnD DELHI
2021_MES_482151_1
GE/RND-66/DLI/2021-2022
Open Tender
Civil Works
Item Rate
180 days
Delhi
Class-D, Cat c(vi)
2 documents required · 2 mandatory
₹500
Yes
GE I RND Delhi
₹97,000
Yes
24 Jan 2022
16 Oct 2021
20 Dec 2021
16 Oct 2021
18 Dec 2021
6 Dec 2021
Amount
S&F in replacement of MS ERW pipe of bore 150 mm confirming to IS-1259 PART-2, medium grade complete all as specified & directed.
S&F in replacement of MS ERW pipe of bore 100 mm confirming to IS-1259 PART-2, medium grade complete all as specified & directed.
S&F in replacement of MS ERW pipe of bore 50 mm confirming to IS-1259 PART-2, medium grade complete all as specified & directed.
S&F in replacement of MS ERW pipe of bore 25 mm confirming to IS-1259 PART-2, medium grade complete all as specified & directed.
S&F in replacement of SS (Stainless Steel) Single head landing valve with 80 mm nominal bore flanged inlet, SS spindle (IS : 6603) controlled 63 mm dia instantaneous female outlet type. SS coupling, blank cap, chain, twist release type lug & all accessories conforming to IS:5290. Including fixing with anchor fastener and flanged tapping from wet riser . (For Internal Hydrant/Outert Hydrant post).
S&F in replacement of Hose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm with double door with 4 mm thick plain glass of size 200mm X 100mm and door frame made of 16 gauge MS sheet duly painted fire red out side and brilliant white inside yard complete all as specified & directed.
S&F in replacement of 63 mm dia instantaneous pattern SS (Stainless Steel) Short branch pipe, 20 mm dia nozzle conforming to IS 903, suitable for inter connection to hose pipe coupling complete all as specified & directed
S&F in replacement of Non-percolating rubber reinforced lined fire hose pipe (as per IS : 636) Type-A of 63 mm dia and length 15 meter. The hose shall be rated for burst pressure of 35.7 Kg/Sqcm. Hose shall be complete with ISI marked SS male & female coupling (IS:903) bound & riveted to hose pipe with aluminum rivets & 1.5 mm GI wire. (For Internal Hydrant & External Hydrant) complete all as specified & directed.
S&F in replacement of Cast Iron Air Valves with single air Outlets, conforming to IS - 14845 of size 100 mm dia bore and fixing up in Cast Iron Water supply mains of size 100 mm dia complete all as specified & directed.
S&F in replacement of cast iron Non Return Valve of dia 100 mm with GM sheet PN 1.6, ISI mark as per IS-5312 PART-2, including flange joints such as packing , nut & bolts complete all as specified & directed.
All as per item No. 10 above but of 150 mm dia.
S&F in replacement of 150mm bore hand operated butterfly valve of pressure not less than 15 Kg / Sqcm with complete set as per IS-13095 Complete all as specified & directed.
S&F in replacement of 100mm bore hand operated butterfly valve of pressure not less than 15 Kg / Sqcm with complete set as per IS-13095 complete all as specified & directed.
S&F in replacement of 50mm bore hand operated butterfly valve complete set.as per IS-13095 complete all as specified & directed.
Supply and fixing in replacement of swinging type First Aid hose reel in red colour drum with 30 mtr long and 20 mm dia heavy duty rubber water hose, 20 mm dia gate gun metal valve stop cock, (IS:778, class - II) terminating with SS coupling & nozzle of 6 mm outlet with shut off valve confirming to IS 8090 - 1976 complete with MS socket for tap-off, drum and brackets (including painting) for fixing on wall with anchor fastener, bolts & nuts complete all as specified & directed.
S&F in replacement of Gun metal fire brigade inlet connection for connecting to external fire hydrant ring main consisting of two way 63 mm dia instantaneous type male coupling with built in check valve and 150 mm dia , flanged out let complete with all accessories complete all as specified & directed.
S&F in replacement of Detectors Complying with and type certified to EN-45 Addressable type smoke detector Photoelectric / Optical with base with self built intelligence as per IS: 11360 complete all as specified & directed.
S&F in replacement of signage shop glow in dark FIRE EXIT sign board with man running arrow symbol and stair of dimension 12" x 6" X 8 mm decorative transparent acralic, including fixing arrangement complete all as specified and directed.
M&L of Pressure gauge 4"dial 0-14 kgs rating complete all as specified & directed.
S&F in replacement of air cushioning tank 250mm dia x 1000 mm high with dished top, made of minimum 6mm thick MS pipe/plate complete with 20mm dia. Brass air valve (ball type), 20 mm dia stop valve, pressure gauge with brass stop cock, nipple tees elbows and all accesories complete all as specified and directed.
S&F in replacement of branch pipe with nozzle of 20mm dia for hose reel conforming to IS 8090
S&F in replacement of Sprinkler concealed type (Standard response) as per IS:15106/TAC guidelines 68 degree temperature rating pendent type complete all as specified and directed.
M&L for chemical earthing complete including earth work in any type of soil with clamp SITC of copper bounded Rod / Earthing termination bonded steel earth rods of 3 mtrs minimum length, 17.2 mm dia, interconnected with copper bonded flanges (Minimum copper bonding shall be 0.25 mm) along with Rod-to-Conductor connectors, and other accessories as per IS 3043, NBC 2016, IEEE 80, UL 467. CPRI tested at 25KArms along with 30 Kg pure carbon-based Earth Enhancement compound tested by NABL accredit lab for RDHS complying IEC 62561-7 in a sealed bag and inspection pit covers. Including copper strip 25x5mm not more than 7.5 meters complete all as specifeid and testing on completion with & including followings :- (a) PCC earth pit 30x30x30 cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15 mm thick plaster in CM 1:6 including RCC pit cover 25mm thick reinforced with 6mm dia TMT bar 75mm centre to centre with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover. (b) Angle iron frame made of 40x40x4 mm angle iron for 30x30cm PCC pit for holding the pit cover. (c) Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm, drilled and screwed including 3 Nos 8mm dia 25mm long hexagonal head screw - 02 Nos.
M&L for painting with two coat of synthetic enamelled paint over a coat of red oxide primer on new steel surface including preparation complete all as specified and directed.
M&L provision of fire point with shade and accessories like as bucket, fire bitter, fire hook, digging tool with supporting angle 2.0 RM each of size 75mmx6mm thick 1.5 RM-02 Nos horizontal bracing of size 75mmx6mm and both side 0.5 meter covered with MS sheet of minimum thickness 3mm of minimum covered area 1.5 Sqm of sheet with support of angle iron 50x50x5mm thick of 1.0 RM-02 Nos (One at each end) and providing of hooks of 200mm length of round bar minimum size 20mm-05 Nos including earth work, PCC and 02 coat of red paint on all surface & equipment as directed with 3 buckets of 10 ltrs MS sheet of minimum thickness 3mm and carrying handle 10mm dia and two nos fire bitter and one No fire hook as directed including gaity (digging tool) with handle and base complete all as specified & directed.
S&F in replacement of twisted 2 core 1.5 Sqmm shielded PVC insulated FPLR cable ISI Marked unsheathed cable copper conductor.
S&F in replacement of Rigid mild steel conduit, medium grade welded of 20mm diameter concealed/Surface in wall/Ceiling/above false ceiling and all fixing accessories/ materials. .
M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including 250mm dia HDPE pipe of 0.4 mpa working pressure for 150 mm dia MS pipe complete all as specified & directed. .
Supply, installing, testing and commissioning factory fabricated and tested LT Indoor type panel, platform mounted, of size 1500mmx1500mmx600mm suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated electrolytic Aluminium bus bars TPN of capacity 400 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, and made out of 2.00 mm thick CRCA mild steel sheet and mild steel & Mounting Channel frame work made out of angle iron of size 75 mmX5 mm ), front opening type with aprons for cable entry, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey RAL- 7035 shade. The scope of work also comprising of the following:-
OUTGOINGS :- Star Delta Starter 50 HP Each having the following :- 2 Nos. ( Main Pump ) (a) MCCB 125 A 25 KA 3 Pole Thermal Magnetic- 01 No (b) Contactor 70 A TP (Main & Delta) - 02 Nos (c) Contactor 50 A TP (Star) - 01 No. (d) B1 Metal Over Load relay 30-50 A - 01 No. (e) Star delta timer Micon Series - 01 No. (f) Digital Amp Meter (0-100A) - 01 No. (g) CT 100/5A - 01 No. (h) Single Phase Preventer - 01 No. (i) Push button Start/Stop with Elements - 02 Nos, (j) On, Off, Trip indicating Lights LED type 220 V AC- 1 Set. (Set of three). (k) Aux. Blocks 1 No+1 Nc - 1 Set.
Star Delta Starter 7.5 HP Each having the following :- 1 No. ( Jockey Pump ) (a) MCB 32 A 10 KA 3 Pole C Curve- 01 No (b) Contactor 18 A TP (Main & Delta) - 02 Nos (c) Contactor 12 A TP (Star) - 01 No. (d) B1 Metal Over Load relay 6-10 A - 01 No. (e) Star delta timer Micon Series - 01 No. (f) Digital Amp Meter (0-30A) - 01 No. (g) CT 30/5A - 01 No. (h) Single Phase Preventer - 01 No. (i) Push button Start/Stop with Elements - 02 Nos, (j) On, Off, Trip indicating Lights LED type 220 V AC- 1 Set. (Set of three). (k) Aux. Blocks 1 No+1 Nc - 1 Set. Notes : 1. Provison for Auto/Manual Mode incase of Auto failure 2. Control circuit for Pressure Maintain via Pressure Switch
Star Delta Starter 7.5 HP Each having the following :- 1 No. ( Water Pump ) (a) MCB 32 A 10 KA 3 Pole C Curve- 01 No (b) Contactor 18 A TP (Main & Delta) - 02 Nos (c) Contactor 12 A TP (Star) - 01 No. (d) B1 Metal Over Load relay 6-10 A - 01 No. (e) Star delta timer Micon Series - 01 No. (f) Digital Amp Meter (0-30A) - 01 No. (g) CT 30/5A - 01 No. (h) Single Phase Preventer - 01 No. (i) Push button Start/Stop with Elements - 02 Nos, (j) On, Off, Trip indicating Lights LED type 220 V AC- 1 Set. (Set of three). (k) Aux. Blocks 1 No+1 Nc - 1 Set. Notes : 1. Provison for Auto/Manual Mode incase of Auto failure 2. Control circuit for Pressure Maintain via Pressure Switch
Star Delta Starter 7.5 HP Each having the following :- 1 No. ( Supply Pump ) (a) MCB 32 A 10 KA 3 Pole C Curve- 01 No (b) Contactor 18 A TP (Main & Delta) - 02 Nos (c) Contactor 12 A TP (Star) - 01 No. (d) B1 Metal Over Load relay 6-10 A - 01 No. (e) Star delta timer Micon Series - 01 No. (f) Digital Amp Meter (0-30A) - 01 No. (g) CT 30/5A - 01 No. (h) Single Phase Preventer - 01 No. (i) Push button Start/Stop with Elements - 02 Nos, (j) On, Off, Trip indicating Lights LED type 220 V AC- 1 Set. (Set of three). (k) Aux. Blocks 1 No+1 Nc - 1 Set. Notes : 1. Provison for Auto/Manual Mode incase of Auto failure 2. Control circuit for Pressure Maintain via Pressure Switch
The panel manufacturer shall have following Govt. Approved Certificates: 1. CPRI Certification Degree of Protection IP-54 (should have IEC:60439-1 test) 2. CPRI Short Circuit withstand strenght should be 50k Arms for 1.0 Sec with intial peak of 105kA 3. CPRI Certification Rated current for short circuit not less than 4000 A with rated insulation voltage 660V 4. ISO 9001 CERTIFIED 5. The contractor shall be submit detailed drawing of panel with showing all fittings and accessories for approval of GE (I) R&D Delhi before procurement. The rates for civil work i.e. brick work PCC & earth work is also descrived to be including in quoted rates. Note : Old unserviceable starter, MCCB, Contactor will be deposited in MES store yard and taken on ledger charge.
M&L for Repair/Servicing to monoblock motor and pump set 7.5 HP with greasing and replacement of elctrical terminal including painting complete all as specified & directed (Jockey pump).
M&L for Repair/Servicing to Centrifugal motor and pump set 50 HP with greasing and replacement of elctrical terminal including painting complete all as specified & directed (Main Fire fighting pump).
M&L for Disconnecting of electrical connections from panel board including disconnecting the cable leads from the motor terminal box and taking down/out electric motor of capacity 50 HP from base plate of pump set after opening the nuts, bolts etc and transporting the motor to workshop for repair Opening the electric induction motor including taking down/out the burnt winding wire , cleaning the slots, rewinding the motor with super enamalled copper winding wire of existing gauge ,weight etc. including servicing to pump and all other insulating material to make it functional and back, re-installed after repair including testing complete all as specified and as directed .
M&L for Yard hydrant Post / Stand Post 80mm Dia MS both flanged type 1.5m Height as per IS complete all as specified & directed.
Excavation in trenches in soft/loose soil not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr in depth and getting out complete all as specified and as directed
All as per item No. 34 above but in hard/dense soil/cutting of road/hard standing/breaking of PCC etc.
Returning, filling in and including spreading, leveling and watering and well ramming in layers not exceeding 25 cm thick to achieve desired compactness complete all as specified & directed
Removing surplus excavated materials soil to a distance n. exc 50 m and depositing where directed at a level n exc 1.5 m above the starting point complete all as specified & directed
M&L for PCC (1:2:4) type B-1 using 20mm graded stone aggregate finished even and smoooth without using extra cement as on brick pillars complete all as specified & directed.
SANWARIYA ENTERPRISES
FIRE PROTECTION SYSTEM
FORTUNE STAR
Continental Engineers and contractors
Flint India
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .